Gree GMV6 DC Inverter VRF Units Service Manual
10
Model
-
GMV-2525WM/G-U
GMV-2590WM/G-U
GMV-2655WM/G-U
GMV-2720WM/G-U
Heating current input
A
25.0+25.0+25.0+28.8 25.0+25.0+28.8+28.8 25.0+28.8+28.8+28.8 28.8+28.8+28.8+28.8
Rated power input
kW
25.50+25.50+25.50+2
8.50
25.50+25.50+28.50+2
8.50
25.50+28.50+28.50+
28.50
28.50+28.50+28.50+28
.50
Rated current
A
38+38+38+40.9
38+38+40.9+40.9
38+40.9+40.9+40.9
40.9+40.9+40.9+40.9
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
Maximum drive IDU
NO.
unit
80(85)*
80(90)*
80(95)*
80(100)*
Gas pipe
mm
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Liquid pipe
mm
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Outline dimensions
(W × D × H)
mm
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
Packing dimensions
(W × D × H)
mm
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
Net weight
kg
355+355+355+360
355+355+360+360
355+360+360+360
360+360+360+360
Gross weight
kg
370+370+370+375
370+370+375+375
370+375+375+375
375+375+375+375
NOTICE!:
*The maximum connection quantity of indoor unit in the brace should be engineering
customized.
3
The Range of Production Working Temperature
—
Cooling
Heating
Ambient temperature
-15
℃
*(5
℉
)
~48
℃
(118.4
℉
)
DB
-25
℃
(-13
℉
)
~24
℃
(75.2
℉
)
DB
Indoor temperature
14
℃
(
57.2
℉
)
~25
℃
(77
℉
)
WB
15
℃
(59
℉
)
~27
℃
(80.6
℉
)
DB
Indoor humidity
≤80%
*
Note: Cooling at -15~ -5
℃
(5~23
℉
) is conditional. Please inquire our engineers for more
information. Generally, the lowest operating temperature for cooling is -5
℃
(23
℉
).
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16
℃
(60.8
℉
)
~45
℃
(113
℉
)
Heating
Ambient temperature: -7
℃
(19.4
℉
)
~16
℃
(60.8
℉
)
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...