DC Inverter U-match Series Cassette Type Unit

16

(5).  The evacuation duration depends on the unit’s capacity, generally, 15 minutes for the 12K 

units, 20 minutes for the 18K units, 30 minutes for the 24/30/36K units, 45 minutes for the 
42/48/60 units. And verify if the pressure gauge at the low pressure side of the manifold 
valve assembly reads -1.0Mp (-75cmHg), if not, it indicates there is leak somewhere. Then, 
close the switch fully and then stop the vacuum pump.

(6).  Wait for some time to see if the system pressure can remain unchanged, 3 minutes for the 

units less than 18K, 5 minutes for the 18K~24K units, 10 minutes for the units more than 
42K. During this time, the reading of the pressure gauge at the low pressure side can not 
be larger than 0.005Mp (0.38cmHg).

(7).  Slightly open the liquid valve and let some refrigerant go to the connection pipe to balance 

the pressure inside and outside of the connection pipe, so that air will not come into the 
connection pipe when removing the hose. Note that the gas and liquid valve can be opened 
fully only after the manifold valve assembly is removed.

(8).  Place back the caps of the liquid valve, gas valve and also the service port.

Hose with the valve pin

gauge manifold

pipe

pipe

  

VAC valve

Vacuum pump

Service port

Low pressure gauge

High pressure gauge

Gauge manifold kit

Fig.20

Note: For the large-sized unit, it has the service port for both the gas valve and the liquid valve. 
During evacuation, it is available to connect two hoses of the manifold valve assembly to two 
service ports to quicken the evacuating speed.

4.4.2 Additional Charge 

Refrigerant suitable for a piping length of 5m is charged in the 09~42K outdoor unit at the 

factory, and for 48~60K outdoor unit refrigerant is charged for a piping length of 7.5m.

When the piping of 09~42k unit is longer than 7.5m or the piping of 48~60k unit is longer than 

9.5m, additional charging is necessary.

For the additional amount, see Table 10.

Table 10

                Model 

     Item 

Standard Pipe Length

Unnecessary Charge 

Pipe Length

Additional Refrigerant Amount 

for Extra Pipe

09~18K

5m

≤ 7.5m

30 g/m

24~42K

5m

≤ 7.5m

60 g/m

48~60K

7.5m

≤ 9.5m

60 g/m

Содержание GKH12K3FI

Страница 1: ...NM3FO DC Inverter U match Series Cassette Type Unit Thank you for choosing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please contac...

Страница 2: ...Installation of the Indoor Unit 9 4 2 Installation of the Outdoor Unit 10 4 3 Installation of the Connection Pipe 12 4 4 Vacuum and Gas Leakage Inspection 15 4 5 Installation of the Drain Hose 17 4 6...

Страница 3: ...Do not use an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire 8 Use the specified types of wires...

Страница 4: ...use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the...

Страница 5: ...Unit and Main Parts 1 Drainage device 2 Drainage pipe 3 Air flow flap 4 Connection pipe 5 Wired Controller 6 Wireless Controller 7 Big handle 8 Liquid Pipe 9 Gas pipe 10 Drainage pipe 11 Front Board I...

Страница 6: ...installing the unit 4 installation paperboard 1 used for ceiling drilling 5 Gasket mounting board 4 Used to prevent gasket from falling off 6 Wireless Controller Battery 1 2 To control the indoor uni...

Страница 7: ...wn through all the room 2 Make sure that the installation meets the requirement of the schematic diagram of installation spaces 3 Select the place where can stand 4 times of the weight of the indoor u...

Страница 8: ...free from being dirty or getting wet by rain as much as possible 2 Install the outdoor unit where it is convenient to connect with the indoor unit 3 Install the outdoor unit where the condensate water...

Страница 9: ...D24NK3FO 3 8 5 8 30 15 GKH30K3FI GUHD30NK3FO 30 15 GKH36K3FI GUHD36NK3FO 30 15 GKH42K3FI GUHD42NK3FO 50 30 GKH48K3FI GUHD48NK3FO 50 30 GKH36K3FI GUHD36NM3FO 30 15 GKH42K3FI GUHD42NM3FO 50 30 GKH48K3FI...

Страница 10: ...d at 40 and resistible to 90 see IEC 60364 5 52 If the working condition changes they should be modified according to the related national standard The specifications of the breaker listed in the tabl...

Страница 11: ...e Indoor Unit 4 1 1 Indoor unit dimension Fig 4 Table 7 Item Model A B C D E F GKH12K3FI 670 596 592 571 145 240 GKH18K3FI GKH24K3FI 950 840 780 680 160 240 GKH30K3FI 950 840 780 680 160 320 GKH36K3FI...

Страница 12: ...e paper template 4 1 3 Installing the Suspension Bolts 1 Using the installation template drill holes for bolts four holes Fig 6 2 Install the bolts to the ceiling at a place strong enough to hang the...

Страница 13: ...1085 427 1365 620 395 4 2 2 Condensate Drainage of the Outdoor Unit Only for the heat pump unit Fig 11 1 It is required to install a drain pipe for the outdoor unit to drain out the condensate water...

Страница 14: ...pread evenly and there are no cracks see Fig 12 Fig 12 4 3 2 Bending Pipes 1 The pipes are shaped by your hands Be careful not to collapse them Fig 13 2 Do not bend the pipes in an angle more than 90...

Страница 15: ...damaged Do not remove the flare nut until the connection pipe is to be connected so as to prevent dust and impurities from coming into the pipe system When connecting the pipe to the unit or removing...

Страница 16: ...cting the Pipe at the Outdoor Side Unit Tighten the flare nut of the connection pipe at the outdoor unit valve connector The tightening method is the same as that as at the indoor side 4 3 5 Checking...

Страница 17: ...from returning to the room 3 Restraint all pipes to the wall with saddles 4 4 Vacuum and Gas Leakage Inspection CAUTION Do not purge the air with refrigerants but use a vacuum pump to vacuum the inst...

Страница 18: ...when removing the hose Note that the gas and liquid valve can be opened fully only after the manifold valve assembly is removed 8 Place back the caps of the liquid valve gas valve and also the service...

Страница 19: ...inside the pipe 2 Keep pipe size equal to or greater than that of the connecting pipe 3 Install the drain piping as shown and take measures against condensation Improperly rigged piping could lead to...

Страница 20: ...sufficient gradient it is necessary to fit a riser pipe field supplied to it 5 If the air flow of indoor unit is high this might cause negative pressure and result in return suction of outdoor air Th...

Страница 21: ...insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Drain lift pipe Fig 30 2 Make sure the lift pipe is at most 280mm 3 Stand the lift pipe ver...

Страница 22: ...OOL running Drain hose Test hole cover Test hole Immiting water from the rest hole Plastic water pot The length of the pipe should be about 100mm Immiting water from the outlet vent terminal Above 100...

Страница 23: ...n ceiling and decoration panel after tightening the screws readjust the height of the indoor unit Fig 36 Fig 36 4 Wire the swing flap motor as shown in Fig 37 Fig 37 4 6 2 Installing the Panel 1 Place...

Страница 24: ...m Fig 38 4 7 Electrical Wiring 4 7 1 Wiring Precautions WARNING Before obtaining access to terminals all supply circuits must be disconnected The rated voltage of the unit is as shown as Table 5 and T...

Страница 25: ...the contracted capacity When the voltage is low and the air conditioner is difficult to start contact the power company to raise the voltage 4 7 2 Electrical Wiring 1 For solid core wiring Fig 39 1 C...

Страница 26: ...ause burning of the electric parts Connect the connection cords firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cord with cord...

Страница 27: ...5RN F Communication Cords 2 0 75mm2 H05RN F Three phase units GUHD36NM3FO GKH36K3FI GUHD42NM3FO GKH42K3FI GUHD48NM3FO GKH48K3FI GUHD60NM3FO GKH60K3FI Power cord 5 1 5mm2 H07RN F Power cord 3 1 0mm2 H0...

Страница 28: ...door connection cord and power cord respectively on the terminal boards with screws Faulty connection may cause a fire If the indoor unit connection cord to the outdoor unit and power supply are wired...

Страница 29: ...ines Fig 46 Three phase 36K 60K L1 L2 L3 N 1 2 Fig 45 5 Installation of Controllers Refer to the Installation Manual of the controller for more details 6 Test Running 6 1 Trial Operation and Testing 1...

Страница 30: ...25 Lc Activation failure 26 Ld Compressor phase sequence protection 27 LE Compressor stalling protection 28 LF Power protection 29 Lp Indoor and outdoor mismatch 30 U7 4 way valve direction changing...

Страница 31: ...panel is still allowed to realize the following functions by pressing the Auto button and the nearby Test button simultaneously for five seconds when the unit is Off 6 2 Working Temperature Range Tab...

Страница 32: ...oor cooling effect The air filter is dirty or blocked There is heat source or too many people inside the room The door or window is open There is obstacle at the air intake or outlet The set temperatu...

Страница 33: ...d deformation of the unit Do not wet the indoor unit in case of electric shock or fire hazard Increase the frequency of cleaning if the unit is installed in a room where the air is extremely contamina...

Страница 34: ...er screen Filtering element Support Bolt 5 Clean the filer screen Clean the filer screen by a vacuum cleaner or wash it by flashing water If the oil stain on the filter can not be removed or cleaned u...

Страница 35: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: