Cassette Type Fan Coil Unit Owner`s Manual
5
4 Installation of the Cassette Type FCU
4.1 Schematic diagram of installation spaces
Ceiling
Fig.2
4.2 Selection of the installation location of the FCU
(1) Obstruction shall be put away from the intake or outlet vent of the FCU so that the airflow can
be blown through all the room.
(2) Make sure that the installation comply with the requirement of the schematic diagram of
installation spaces.
(3) Select the place where it can stand 4 times of the weight of the FCU and would not increase the
operating noise and oscillate.
(4) The horizontally of the installation place should be guaranteed.
(5) Select the place where condensate water can drain out easily.
(6) Make sure that there are enough space for care and maintenance. Make sure that the height
between the FCU and ground is above 2500mm.
(7) When installing the steeve bolt, check if the installation place can stand the 4 times of the weigh
of the unit. If not, reinforce it before installation. (Refer to the install cardboard and find where
should be reinforced)
Note!
①
There will be lots of lampblack and dust stuck on the acentric, heat exchanger and water
pump in dining room and kitchen, which would reduce the capacity of heat exchanger, lead to water
leakage and abnormal operation of the water pump. The following treatment should be taken under
this circumstance:
②
Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to
prevent the indraft of the lampblack by the air conditioner.
③
Keep the air conditioner far from the kitchen so that the lampblack would not be taken in by