background image

Vertical Exposed Fan Coil Unit

17

Parameter list:

S.N

Name

Description

01

Power failure memory

ON: enable (by default); OFF: disable  

02

Energy saving function

ON: enable; OFF: disable (by default) 

03

Drying function

ON: enable; OFF: disable (by default)  

04

Temperature unit setting

F: Fahrenheit; C: Celsius (by default)

05

Fan operation at temperature 
set points 

00: the fan works as to the set speed;
01: the fan works at the low speed;

02: the fan stops (by default)

06

Temperature calibration 

Adjustable range: -5°C~+5°C (a precision of 0.5°C, 0°C by default)

07

Temperature control range

1: narrow ; 2: medium (by default); 3: wide 

08

Cooling temperature set in the 
energy saving mode

Adjustable range: 16°C~30°C (a precision of 0.5°C, 16°C by 

default);
When the temperature unit is Fahrenheit, the adjustment range of 

the temperature is 61°F~86°F (a precision of 1°F).

09

Heating temperature set in the 
energy saving mode

Adjustable range: 16°C~30°C (a precision of 0.5°C, 30°C by 

default);
When the temperature unit is Fahrenheit, the adjustment range of 

the temperature is 61°F~86°F (a precision of 1°F).

10

Ambient temperature display

ON: enable; OFF: disable (by default)

11

Factory data reset

ON: enable; OFF: disable (by default) 

Below are instructions for setting the parameters.

(1) 

Power failure memory

When the function is enabled, if a power failure occurs while the unit is working or stopped, the last 

screen of data that was collected will be displayed upon restoration of power.

When the function is disabled, if a power failure occurred while the unit was stopped, it will automatically 

restart with a unit stop display when power is restored.

As shown in the Figure 7 (the function has been disabled), on the parameter setting page, press 

 

 

(MODE) to switch the option number to 01.  

 (UP) or 

 (DOWN) is provided to allow a switch between 

ON and OFF (—enable or disable the function).

Figure 7

Содержание FP-102LM/D-K

Страница 1: ...al Exposed Fan Coil Unit Owner s Manual Original Instructions Commercial Air Conditioners Models FP 22LM D K FP 34LM D K FP 51LM D K FP 68LM D K FP 85LM D K FP 102LM D K FP 119LM D K FP 136LM D K FP 1...

Страница 2: ...ble for their safety Children should be supervised to ensure that they do not play with the appliance 2 This product has gone through strict inspection and operational test before leaving the factory...

Страница 3: ...tenance space 8 2 5 Installation of inlet and outlet pipes 8 2 6 Installation of the drain hose 9 2 7 Installation of the water valve 10 2 8 Electric wiring 12 3 Thermostat guide 13 3 1 Thermostat pan...

Страница 4: ...ly This unit should be grounded and there should be grounding lines for the power socket so as to prevent electrocution Do not connect the grounding lines to the gas lines water lines lightning rod or...

Страница 5: ...eaving water lines condensate lines and valves should be thermal insulated so as to prevent from dewing in summer Do not repair this unit by yourself as incorrect repair would lead to electrocution or...

Страница 6: ...s and electric connection lines should be secure enough Terminals also should be tightly fastened The connection line should not suffer external forces For the unit equipped with the wired controller...

Страница 7: ...or a swimming pool DISPOSAL This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health f...

Страница 8: ...ested to be not higher than 65 C normally 60 C otherwise it would lead to corrosion of copper tubes or abnormal noise 2 The suggested working environment temperature for cooling ranges 16 40 C and ran...

Страница 9: ...the the table below Suspension hole Suspension hole Unit mm Model FP 22LM D K 555 390 FP 34LM D K FP 51LM D K 710 FP 68LM D K FP 85LM D K FP 102LM D K 1010 FP 119LM D K FP 136LM D K FP 170LM D K 1433...

Страница 10: ...tal way Open the cover Loosen screws Lift the decorated panels on left or right side 1cm above After Before Remove it in Suspension hole Suspension hole a horizontal way Hang the unit by fiting the ho...

Страница 11: ...723 FP 102LM D K 1350 680 585 230 1023 FP 119LM D K 1350 680 585 230 1023 FP 136LM D K 1350 680 585 230 1023 FP 170LM D K 1773 680 585 230 1446 FP 204LM D K 1773 680 585 230 1446 2 4 Installation and...

Страница 12: ...n left or right side 1cm above After Before Remove it in a horizontal way Outlet pipe Inlet pipe Drain pipe Wire the electric box 2 6 Installation of the drain hose 2 6 1 Precautions for the drain hos...

Страница 13: ...t one end of the water pipe to the water inlet of the unit and then connect the other end to water valve During installation both the torque wrench and ordinary wrench should be used For the former th...

Страница 14: ...tor Insulation sleeve Water pipe Put the connection line through the PVC pipe and then bind them with the insulation sleeve Connection line of the actuator PVC pipe Insulation sleeve Water pipe Never...

Страница 15: ...the magnetic or electric trip off functions so as for shortcutting and overloading protection 6 The unit should be grounded reliably The yellow green line is the grounding line Do not put it into othe...

Страница 16: ...WN 3 2 Technical parameters Item Description Supply voltage AC85 265V 50 60Hz Temperature setting 16 30 C Operation temperature 0 50 C Humidity Relative humidity 5 95 no condensate Load current 2A res...

Страница 17: ...se the thermostat 3 3 1 ON OFF As shown in Figure 1 press ON OFF to start or stop the unit If it is on the screen provides the operation mode temperature and fan speed among which only temperature app...

Страница 18: ...ithout any operation in 5 seconds Figure 3 Celsius Fahrenheit 3 3 5 Timer 1 The unit is timed to start or stop ranging from 0 5 to 24 hours 2 As shown in the Figure 4 after starting the unit to keep p...

Страница 19: ...operating in 1 hour and another 1 C in another 1 hour The set temperature will rise 2 C at most and be steady at 28 C with the function automatically disabled In the heating mode using the sleep funct...

Страница 20: ...ecision of 1 F 09 Heating temperature set in the energy saving mode Adjustable range 16 C 30 C a precision of 0 5 C 30 C by default When the temperature unit is Fahrenheit the adjustment range of the...

Страница 21: ...be adjusted to the limit value As shown in the Figure 8 on the parameter setting page press MODE to switch the option number to 02 UP or DOWN is provided to allow a switch between ON and OFF Figure 8...

Страница 22: ...ng when the indoor ambient temperature reaches the specific temperature point As shown in the Figure 11 on the parameter setting page pressing MODE activates a switch to the option number 05 UP or DOW...

Страница 23: ...ure 13 on the parameter setting page press MODE to switch the option number to 07 UP or DOWN is provided to a switch between 1 2 and 3 the three ranges Figure 13 8 Cooling temperature set in the energ...

Страница 24: ...justment range of the temperature is 61 F 86 F with a precision of 1 F Figure 15 10 Ambient temperature display If the user enables the indoor ambient temperature display after the start up of the uni...

Страница 25: ...temperature The user is allowed to adjust the set temperature Figure 18 No Code Description 1 F5 Indoor ambient temperature sensor failure 3 5 Failure handling The product maintenance is performed by...

Страница 26: ...ter at the air inlet or outlet It would lead to poor cooling capacity 4 2 Trial run 1 Preparation before trial run y y Do not power the unit on until all installation has been finished y y Control and...

Страница 27: ...er There are foreign matters at the return inlet and air outlet Clear foreign matters The duct resistance exceeds the design value Lower the duct resistance or reselect the unit 4 The cooling or heati...

Страница 28: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail global cn gree com www gree com...

Отзывы: