Vertical Exposed Fan Coil Unit
17
Parameter list:
S.N
Name
Description
01
Power failure memory
ON: enable (by default); OFF: disable
02
Energy saving function
ON: enable; OFF: disable (by default)
03
Drying function
ON: enable; OFF: disable (by default)
04
Temperature unit setting
F: Fahrenheit; C: Celsius (by default)
05
Fan operation at temperature
set points
00: the fan works as to the set speed;
01: the fan works at the low speed;
02: the fan stops (by default)
06
Temperature calibration
Adjustable range: -5°C~+5°C (a precision of 0.5°C, 0°C by default)
07
Temperature control range
1: narrow ; 2: medium (by default); 3: wide
08
Cooling temperature set in the
energy saving mode
Adjustable range: 16°C~30°C (a precision of 0.5°C, 16°C by
default);
When the temperature unit is Fahrenheit, the adjustment range of
the temperature is 61°F~86°F (a precision of 1°F).
09
Heating temperature set in the
energy saving mode
Adjustable range: 16°C~30°C (a precision of 0.5°C, 30°C by
default);
When the temperature unit is Fahrenheit, the adjustment range of
the temperature is 61°F~86°F (a precision of 1°F).
10
Ambient temperature display
ON: enable; OFF: disable (by default)
11
Factory data reset
ON: enable; OFF: disable (by default)
Below are instructions for setting the parameters.
(1)
Power failure memory
When the function is enabled, if a power failure occurs while the unit is working or stopped, the last
screen of data that was collected will be displayed upon restoration of power.
When the function is disabled, if a power failure occurred while the unit was stopped, it will automatically
restart with a unit stop display when power is restored.
As shown in the Figure 7 (the function has been disabled), on the parameter setting page, press
(MODE) to switch the option number to 01.
(UP) or
(DOWN) is provided to allow a switch between
ON and OFF (—enable or disable the function).
Figure 7