26
Duct Type Split Air Conditioner
Service Manual
CONTROL
Fig. 3.11Timer setting under on state of the unit
Timer range: 0.5-24hr. Every press of ▲ or ▼ button will make setting time increased or decreased by 0.5hr.
If press either of them continuously, setting time will automatically increase/ decrease by 0.5hr every 0.5s.
Note:
a. If both timer on and timer off are set in unit on interface, the wired controller only display time of time
off. If both of them are set in unit off-state, only time of timer on is displayed.
b. Timer on in unit on-state is timed from the time of unit off and timer off in unit off-state is timed from the
time of unit on.
3.4.7 Air Exchange Setting
*
Turn on air Exchange function:
Under on-state of the unit, press
Function
button to go to the this function setting (
Air
mark blinks). AIR 1
displayed at the ambient temperature-displayed location (888) is defaulted (the last type of
AIR
will be displayed
after adjustment).Press ▲ or ▼ button to adjust air type. Press
Enter/Cancel
button to turn on/off air function.
After turning on this function, the air mark shows.
There are 10 types of AIR, but only 1-2 types are for remote control. Refer to the following details:
1――The unit continuously runs for 60min, and fresh air valve runs for 6 min.
2――The unit continuously runs for 60min, and fresh air valve runs for 12 min.
3――The unit continuously runs for 60min, and fresh air valve runs for 18 min.
4――The unit continuously runs for 60min, and fresh air valve runs for 24 min.
5――The unit continuously runs for 60min, and fresh air valve runs for 30 min.
6――The unit continuously runs for 60min, and fresh air valve runs for 36 min.
7――The unit continuously runs for 60min, and fresh air valve runs for 42 min.
8――The unit continuously runs for 60min, and fresh air valve runs for 48 min.
9――The unit continuously runs for 60min, and fresh air valve runs for 54 min.
10――The unit continuously runs for 60min, and fresh air valve always runs.
Turn off air Exchange function: During Air function, press
Function
button to go to the Air function. In this
case, air mark is blinking, and then press
Enter/Cancel
button to turn off this function. Air mark will subsequently
Содержание FG20/BNa-M
Страница 1: ...DUCT TYPE SPLITAIR CONDITIONER SERVICE MANUAL T1 R410A 50Hz GC201303...
Страница 4: ...1 Duct Type Split Air Conditioner Service Manual PRODUCT PRODUCT...
Страница 13: ...10 Duct Type Split Air Conditioner Service Manual CONTROL CONTROL...
Страница 45: ...42 Duct Type Split Air Conditioner Service Manual INSTALLATION...
Страница 53: ...50 Duct Type Split Air Conditioner Service Manual MAINTENANCE...
Страница 61: ...58 Duct Type Split Air Conditioner Service Manual 3 WIRING DIADRAM FGR20 BNa M I FGR20 BNa M O LL...
Страница 62: ...59 Duct Type Split Air Conditioner Service Manual FGR25 CNa M I FGR25 CNa M O...
Страница 63: ...60 Duct Type Split Air Conditioner Service Manual FGR30 BNa M I FGR30 BNa M O...
Страница 64: ...61 Duct Type Split Air Conditioner Service Manual FGR40 BNa M I FGR40 BNa M O...
Страница 69: ...66 Duct Type Split Air Conditioner Service Manual 2 Model FGR25 CNa M I Exploded View...
Страница 71: ...68 Duct Type Split Air Conditioner Service Manual 3 Model FGR30 BNa M I Exploded View...
Страница 73: ...70 Duct Type Split Air Conditioner Service Manual 4 Model FGR40 BNa M I Exploded View...
Страница 83: ...JF00300277...