Design & Selection 

56

 

 

1. Selection Principle 

1.1 Selection Steps 

(1)  Select the unit type based on the air flow, cooling capacity and heating capacity. 

(2)  Select  the  unit  model  based  on  the  indoor  cold/heat  load,  inlet  air  temperature,  entering  water 

temperature and related data sheet. The cooling/heating capacity of the selected unit should be 

or larger than the indoor cold/heat load. 

(3)  Take consideration of noise of the building. 

(4)  According to the allowable noise level of the corresponding building (see the next page for more 

details), check if the selected unit can meet the noise requirement) 

(5)  Take hydraulic calculation to the duct system and then select the proper static pressure     

1.2 Allowable Noise Level for Buildings 

Type of Buildings 

A-weighted Sound Level (dBA) 

Recording studio, broadcast studio, dubbing room 

20~25 

Concert hall, theatre, television studio 

25~30 

Cinema, lecture theatre, meeting room 

30~35 

Office room, design office, reading room,   

35~40 

Restaurant, banquet hall, gym, hotel   

40~50 

Waiting room, shopping center 

45~55 

Cleaning room, office room with mechanical 

appliance 

55~65 

It is cited from Practical Design Manual of Heating Air  Conditioning. If undesirable; reselect the unit 

with lower noise.   

1.3 Example for Selection 

For a room of some hotel, the sensible heat cooling load is 3180W, and all heat cooling load is 4090W, 

the  inlet  air  dry  bulb  temperature  is  27

the  inlet  air  wet  bulb  temperature  is  19.5

,  the  air  flow  is 

600m

3

/h, and the entering water temperature is 7

. Based on these conditions, select a proper FCU. 

See the following figure for the connection diagram of the FCU. 

Содержание FCU Series

Страница 1: ...Concealed Ceiling Type FCU...

Страница 2: ...lection 55 1 Selection Principle 56 1 1 Selection Steps 56 1 2 Allowable Noise Level for Buildings 56 1 3 Example for Selection 56 Unit Control 59 1 Control logic 60 2 AC connected with PC long distan...

Страница 3: ...Enginnering Data 1 Engineering Data...

Страница 4: ...G K EM51002210 EM51002870 4 5 1 28 7 1 99 FP 102WA G K EM51002590 EM51002470 5 5 1 56 8 9 2 53 FP 136WA G K EM51002630 EM51002490 7 35 2 09 12 1 3 44 FP 170WA G K EM51002510 EM51002670 9 2 2 62 15 1...

Страница 5: ...3 75 FP 170WAS G K EM51002700 EM51002520 9 8 2 79 15 8 4 49 FP 204WAS G K EM51002550 EM51002740 11 25 3 2 18 6 5 29 G Series FCU FP 34WAHS G K EM51002770 EM51002130 2 25 0 64 3 6 1 02 220 240V 50HZ F...

Страница 6: ...35 1 52 FP 136WAT R EM51000840 EM51001080 8 10 2 30 7 00 1 99 FP 170WAT R EM51000850 EM51001090 10 35 2 94 8 30 2 36 FP 204WAT R EM51000860 EM51001100 11 00 3 13 8 95 2 54 4 Series FCU FP 34WAF R EM51...

Страница 7: ...9 35 2 66 FP 136WA G D EM51003020 EM51003010 7 35 2 09 12 1 3 44 FP 170WA G D EM51003120 EM51002300 9 5 2 7 15 8 4 49 FP 204WA G D EM51002340 EM51003200 11 5 3 27 18 8 5 35 G FP 34WAH G D EM51003340...

Страница 8: ...88 10 65 3 03 FP 136WAS G D EM51003110 EM51003100 8 3 2 36 13 5 3 84 FP 170WAS G D EM51002330 EM51003190 10 2 2 9 17 4 83 FP 204WAS G D EM51003300 EM51003290 12 2 3 47 20 5 69 G FP 34WAHS G D EM510023...

Страница 9: ...59 FP 136WAT R EM51000840 EM51001080 8 20 2 33 7 20 2 05 FP 170WAT R EM51000850 EM51001090 10 50 2 99 8 40 2 39 FP 204WAT R EM51000860 EM51001100 11 20 3 18 9 10 2 59 4 Series FCU FP 34WAF R EM5100071...

Страница 10: ...51003140 EM51003130 7 1 99 9 2 56 FP 204WA GHL K EM51003220 EM51003210 10 2 84 11 9 3 38 G FP 34WAH GHL K EM51003360 EM51003350 2 0 57 2 3 0 65 220 240V 50HZ FP 51WAH GHL K EM51003950 EM51003960 3 1 0...

Страница 11: ...6WAHS GHL K EM51003680 EM51003670 7 8 2 22 9 2 55 FP 170WAHS GHL K EM51003720 EM51003710 9 2 56 10 9 3 1 FP 204WAHS GHL K EM51003760 EM51003750 10 5 2 99 12 4 3 53 50Hz with the return air box 3 1 or...

Страница 12: ...4 40 1 25 FP 68WAHF BHL K EM51004320 EM51004310 5 00 1 42 5 45 1 55 FP 85WAHF BHL K EM51004360 EM51004350 5 70 1 62 6 15 1 75 FP 102WAHF BHL K EM51004100 EM51004090 7 10 2 02 7 30 2 08 FP 136WAHF BHL...

Страница 13: ...on height utilization and service time which can avoid unreasonable conceptualized control of the large sized duct system c Compact structure flexible arrangement and easy installation will save insta...

Страница 14: ...t type and right type structure can be selected flexibly as steps stated below Step 1 Remove the centrifugal fan cover plate and screws of the electric box Step 2 Move the side plate at the air outlet...

Страница 15: ...dB A 34 5 35 40 40 5 44 45 46 49 30Pa 36 37 41 42 45 5 46 47 5 51 External static pressure Pa 12Pa for the standard type with no diffuser and filter 30Pa for the high ESP type Coil Type Copper high ef...

Страница 16: ...35 40 33 40 Noise 12pa dB A 34 5 37 38 5 41 44 45 46 5 50 30Pa 36 38 41 43 46 47 47 5 51 5 External static pressure Pa 12Pa for the standard type with no diffuser and filter 30Pa for the high ESP typ...

Страница 17: ...External static pressure Pa 30pa Coil Type Copper high efficiency louvered fins Pressure 1 6MPa Motor Type Class B capacitor start Quantity 1 2 Power supply 220 240V 50Hz Protection class IP20 Input p...

Страница 18: ...citor start Quantity 1 2 Power supply 220 240V 50Hz Protection class IP20 Input power 30Pa W 43 59 70 84 105 151 174 206 Power lines mm2 0 5 3 Protection class I Fan Type Front forward multi vane low...

Страница 19: ...t Quantity Piece 1 2 Power supply 208 230VAC 60Hz Protection class IP20 Input power 12pa W 36 57 70 104 105 164 180 228 30Pa W 49 58 74 105 123 165 221 273 Power lines mm2 piece 0 5 3 Anti electric sh...

Страница 20: ...Quantity Piece 1 2 Power lines 208 230VAC 60Hz Protection class IP20 Input power 12pa W 36 63 70 104 114 182 180 228 30Pa W 49 64 74 105 123 183 221 273 Power lines mm2 piece 0 5 3 Anti electric shock...

Страница 21: ...2 042 2 229 Water resistance kPa 8 9 18 21 41 21 32 34 Noise 30Pa 40 42 44 46 47 48 50 52 External static pressure Pa 30pa Coil Type Copper high efficiency louvered fins Pressure 1 6MPa Motor Type Cl...

Страница 22: ...747 1 964 Water resistance kPa 8 15 24 35 56 17 32 31 Noise 30Pa 40 42 44 46 47 48 50 52 External static pressure Pa 30pa Coil Type Copper high efficiency louvered fins Pressure 1 6MPa Motor Type Clas...

Страница 23: ...V 50Hz Protection class IP20 Input power W 35 54 66 84 101 150 154 198 Power lines mm2 piece 0 5 3 Anti electric shock class I Fan Type Forward multiple vane low noise centrifugal fan Quantity piece 1...

Страница 24: ...ass IP20 Input power W 48 57 72 90 111 152 185 222 Power lines mm2 piece 0 5 3 Anti electric shock class I Fan Type Forward multiple vane low noise centrifugal fan Quantity piece 1 2 3 4 Connection pi...

Страница 25: ...tion class IP20 Input power W 35 58 66 78 102 161 150 192 Power lines mm2 piece 0 5 3 Anti electric shock class I Fan Type Forward multiple vane low noise centrifugal fan Quantity Piece 1 2 3 4 Connec...

Страница 26: ...Hz Protection class IP20 Input power W 46 57 72 83 108 164 185 221 Power lines mm2 pieces 0 5 3 Anti electric shock class I Fan Type Forward multi vane low noise centrifugal fan Quantity 1 2 3 4 Conne...

Страница 27: ...1 615 2 042 2 229 Water resistance kPa 3 713 8 943 14 54 18 79 35 75 19 06 29 01 35 41 Noise 30Pa 40 42 44 46 47 48 50 52 External static pressure Pa 30pa Coil Type Copper high efficiency louvered fi...

Страница 28: ...ins Pressure 1 6MPa Motor Type Class B capacitor start Quantity 1 2 Power supply 220 240V 50Hz Protection class IP20 Input power 30Pa W 43 59 70 84 105 151 174 206 Power lines mm2 0 5 3 Protection cla...

Страница 29: ...0 240 1 Ph 50Hz 2 FP 68 220 240V 1 Ph 50Hz 2 FP 85 220 240V 1 Ph 50Hz 2 FP 102 220 240 1 Ph 50Hz 2 FP 136 220 240 1 Ph 50Hz 3 FP 170 220 240 1 Ph 50Hz 4 FP 204 220 240 1 Ph 50Hz 4 1 5 5 Capacity Corre...

Страница 30: ...490 490 490 485 C 235 235 235 235 235 235 235 235 276 D 512 632 732 832 912 1212 1352 1452 1652 E 132 132 132 132 132 132 132 132 194 F 512 682 782 882 962 1262 1402 1502 1652 G 235 235 235 235 235 23...

Страница 31: ...a b FP 34WAF T R 490 45 310 FP 102WAF T R 980 45 310 FP 51WAF T R 620 45 310 FP 136WAF T R 1400 75 250 FP 68WAF T R 740 45 310 FP 170WAF T R 1500 75 310 FP 85WAF T R 820 45 310 FP 204WAF T R 1500 75 3...

Страница 32: ...oint support 01846000179 1 18 Electric Box Assy 01396001537 1 19 Electric Box Cover Plate 01426000259 1 20 Wire Clamp 71010003 1 21 Cable Cross Loop 26900000008 2 22 Insulation Gasket 70410503 1 23 Te...

Страница 33: ...33000064 33010089 1 FP 51WA H G FP 68WA H G FP 85WA H G FP 102WA H G FP 51WA H S G FP 68WA H S G FP 85WA H S G FP 102WA H S G Explosive Views FP 51WA H G Part Lists No Name Code Quantity 1 Water Tray...

Страница 34: ...Cooler Assy 01126000754 01126000775 1 4 Cover Plate Sub Assy 02226001410 1 5 End Plate 02226001407 2 6 Surface Cooler Cover Sheet 01496000327 1 7 Motor Retaining Plate 01846000180 1 8 Propeller Housi...

Страница 35: ...ive water joint support 1846000179 1 18 Electric Box Assy 01396001546 01396001547 1 19 Electric Box Cover Plate 1426000259 1 20 Wire Clamp 71010003 1 21 Cable Cross Loop 26900000008 1 22 Insulation Ga...

Страница 36: ...1 4 Cover Plate Sub Assy 01265200191 1 5 End Plate 02226001407 2 6 Surface Cooler Cover Sheet 01496000327 1 7 Motor Retaining Plate 01845200034 1 8 Propeller Housing Lower 26905200019 2 9 Centrifugal...

Страница 37: ...ater joint support 01846000179 1 18 Electric Box Assy 01396001329 01396001548 1 19 Electric Box Cover Plate 01426000259 1 20 Wire Clamp 71010003 1 21 Cable Cross Loop 26900000008 1 22 Insulation Gaske...

Страница 38: ...6 1 4 Cover Plate Sub Assy 01266000151 1 5 End Plate 02226001407 2 6 Surface Cooler Cover Sheet 01496000327 1 7 Motor Retaining Plate 01846000186 1 8 Propeller Housing Lower 26906000024 2 9 Centrifuga...

Страница 39: ...entrifugal fan assy 15406002320 1 11 Propeller Housing Upper 26906000023 1 12 Fan Motor 157073022 15707301 1 13 Bar Clasp 70819521 4 14 Fan Motor 70819522 1 15 Motor Support 01806000437 1 16 Side Plat...

Страница 40: ...y 15406002320 1 11 Propeller Housing Upper 26906000023 1 12 Fan Motor 157073022 15707301 1 13 Bar Clasp 70819521 4 14 Fan Motor 70819522 1 15 Motor Support 01806000437 1 16 Side Plate of the Air Outle...

Страница 41: ...327 1 7 Motor Retaining Plate 01846000191 1 8 Propeller Housing Lower 26906000024 4 9 Centrifugal Fan 10456000102 4 10 Centrifugal fan assy 15406002345 1 11 Propeller Housing Upper 26906000023 4 12 Fa...

Страница 42: ...ort 01806000437 2 16 Side Plate of the Air Outlet 02226001589 1 17 Divided collective water joint support 01846000179 1 18 Electric Box Assy 01396001531 01396001532 1 19 Electric Box Cover Plate 01426...

Страница 43: ...Cooler Assy 01155200024 01126000765 1 4 Cover Plate Sub Assy 01265200194 1 5 End Plate 02226001407 2 6 Surface Cooler Cover Sheet 01496000327 1 7 Motor Retaining Plate 01265200194 1 8 Propeller Housi...

Страница 44: ...rminal plate 2 0149643001 1 8 Right terminal plate 1 01496429 1 9 Surface Cooler Cover Sheet 01496426 1 10 Left terminal plate 2 0149642801 1 11 Water Faucet fixed Plate 01846365 1 12 Left terminal pl...

Страница 45: ...er Cover Sheet 01496426 1 10 Left terminal plate 2 0149642801 1 11 Water Faucet fixed Plate 01846365 1 12 Left terminal plate 1 01496427 1 13 Centrifugal fan 10319051 2 14 Supporter 01719521 1 15 Fan...

Страница 46: ...Hose 76710060 1 FP 85WAT R Part Lists No Name Code Quantity 1 Electric Box Cover Plate 01419521 1 2 Electric Base Plate Sub assy 01287301 1 3 Terminal Board 420001000003 1 4 Capacitor CBB61 330107471...

Страница 47: ...8 Right terminal plate 1 01496429 1 9 Surface Cooler Cover Sheet 01496426 1 10 Left terminal plate 2 0149642801 1 11 Water Faucet fixed Plate 01846365 1 12 Left terminal plate 1 01496427 1 13 Centrifu...

Страница 48: ...01 1 9 Terminal Board 420001000003 1 10 Capacitor CBB61S 3301074704 1 11 Air bleeding Hose 76710060 2 12 Electric Box Cover Plate 01419521 1 13 Capacitor CBB61S 3301074701 1 14 Water Faucet fixed Plat...

Страница 49: ...ear Volute Casing 22202029 4 18 Centrifugal fan 10319051 4 19 Front Volute Casing 22202030 4 20 Fan Motor 1570730220 2 21 Supporter 01719521 2 FP 204WAT R Part Lists No Name Code Quantity 1 Surface Co...

Страница 50: ...ning Plate 01729530 1 8 Air bleeding Hose 76710060 1 9 Surface Cooler Cover Sheet 01496426 1 10 Right terminal plate 2 01496430 1 11 Right terminal plate 1 01496429 1 12 Base Plate 02226579 1 13 Water...

Страница 51: ...aining Plate 01729529 1 8 Air bleeding Hose 76710060 1 9 Surface Cooler Cover Sheet 01496426 1 10 Right terminal plate 2 01496430 1 11 Right terminal plate 1 01496429 1 12 Base Plate 02226589 1 13 Wat...

Страница 52: ...1 18 Left terminal plate 2 01496428 1 19 Water Faucet fixed Plate 01847703 1 20 Left terminal plate 1 01496427 1 21 Centrifugal fan 10319051 2 FP 85WAF R Part Lists No Name Code Quantity 1 Supporter...

Страница 53: ...01729525 1 8 Air bleeding Hose 76710060 1 9 Surface Cooler Cover Sheet 01496426 1 10 Right terminal plate 2 01496430 1 11 Right terminal plate 1 01496429 1 12 Base Plate 02226597 1 13 Water Tray Assy...

Страница 54: ...1496442 1 9 Left End Plate Sub Assy 2 01496441 1 10 Water Faucet fixed Plate 0184770301 1 11 Capacitor CBB61S 3301074704 1 12 Terminal Board 420001000003 1 13 Electric Box Cover Plate 01419521 1 14 Ca...

Страница 55: ...8 Left End Plate Sub Assy 1 01496442 1 9 Left End Plate Sub Assy 2 01496441 1 10 Water Faucet fixed Plate 0184770301 1 11 Capacitor CBB61S 3301074702 1 12 Terminal Board 420001000003 1 13 Electric Bo...

Страница 56: ...Plate 0184770301 1 11 Capacitor CBB61S 3301074705 1 12 Terminal Board 420001000003 1 13 Electric Box Cover 01426320 1 14 Electric Base Plate Sub assy 01426319 1 13 Rear Volute Casing 22202029 4 16 Fr...

Страница 57: ...Design Selection 55 Design Selection...

Страница 58: ...Noise Level for Buildings Type of Buildings A weighted Sound Level dBA Recording studio broadcast studio dubbing room 20 25 Concert hall theatre television studio 25 30 Cinema lecture theatre meeting...

Страница 59: ...a sheet shows that its sensible heat cooling capacity is 4160W the water flow is 0 21L s water resistance is 30kPa and the air flow is 850m3 h g When the entering water temperature is 60 the heating c...

Страница 60: ...selection result is satisfactory When selecting units the practice is to match the design sensible heat load with the required sensible load In most cases there is enough latent heat for the coils to...

Страница 61: ...Unit Control 59 Unit Control...

Страница 62: ...nitoring system could control max 255 units and independently control the operation mode fan speed on off of the unit the control logic is as below 3 AC control principle sketch Following components c...

Страница 63: ...Unit Installation 61 Unit Installation...

Страница 64: ...nd metal pieces and cut sectional materials Before welding a groove should be made and fins and burrs of the work piece should be removed Equipped with the diamond cut sheet it can cut the non metalli...

Страница 65: ...the bricks concrete and ceramic tiles 2 Specific electric tools Hand held electric shears Usage it is used to cut the metal sheets especially for edge and angle trimming Rivet gun Usage it is used fo...

Страница 66: ...s made the general steel sheet Q195 or Q235A coated with zinc Generally it is 0 5 1 5mm thick No paint is required as its coating is corrosion proof It is widely used for the duct system under the moi...

Страница 67: ...fferent so corrosion resistance to different mediums varies It can be widely used for the duct system under the corrosive chemical environment Aluminum plate It is classified into the pure aluminum pl...

Страница 68: ...y applicable to insulation for buildings cold storages air conditionings and low temperature pipes Its operation is easy and simple Foam Rubber It is mainly made of buna n rubber and PVC It is a high...

Страница 69: ...reserved around the unit The air inlet and outlet should be far away from obstacles so that air flow can go through everywhere of the room When the heat exchanging room is too small it would lead to...

Страница 70: ...ring installation the unit should be kept horizontally The hanger should not bear the weight of ducts water pipes and others Besides check its security periodically 5 Valves should be equipped at the...

Страница 71: ...r hot water Water should be clean The unit should be entirely maintained every 2 3 years Water scale inside coils should be removed by chemical method so as to guarantee the heat exchanging performanc...

Страница 72: ...Unit Installation 70 2 2 Installation Steps...

Страница 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...

Страница 74: ...filter There are foreign matters at the return inlet and air outlet Clear foreign matters The duct resistance exceeds the design value Lower the duct resistance or reselect the unit 4 The cooling or h...

Страница 75: ...ree speed switch to XT 4 For FP 136wa H S Capacitor G1 is larger than capacitor G2 For some models only one motor is accessible The three speed switch enclosed by the dotted lines is optional WARNING...

Страница 76: ...1 Take out the front volute casing Fig 2 Remove the motor Loosen the fixing screws on the motor and remove the clamping band and the hoop see Fig 3 Loosen the grounding screws and disconnect the groun...

Страница 77: ...electric box see Fig 3 Loosen one fixing screw on the soleplate of the electric box see Fig 4 Turn the soleplate of the electric box Loosen fixing screws on the mounted plate Loosen tapping screws on...

Страница 78: ...ooting Maintenance 76 Remove the cooler Loosen the taping screws on the side plate see Fig 6 Loosen the taping screws on the end sides Take out the end plates Take out the cooler upwards Tapping screw...

Страница 79: ...No JF00303582...

Отзывы: