Enginnering Data
13
1.5 Technical Data
1.5.1 Data at Nominal Conditions
Section one --- countries and areas except the European Union
(1) 50Hz (without the return air box), standard, 3-row pipes
Standard Type (G Series)
Type
Item
Concealed
ceiling type
FP-34WA/
G-K
FP-51WA/
G-K
FP-68WA/
G-K
FP-85WA/
G-K
FP-102WA/
G-K
FP-136WA/
G-K
FP-170WA/
G-K
FP-204WA/
G-K
P
e
rfo
rman
c
e
Airflow
Hi
m
3
/h
340
510
680
850
1020
1360
1700
2040
Mid
248
393
510
638
788
1095
1275
1575
Low
213
263
340
425
525
730
850
1050
Cooling
capacity
Hi
W
1850
2800
3600
4500
5500
7350
9200
11000
Heating
capacity
Hi
W
3050
4620
5940
7400
9000
12100
15100
18100
Flow rate
m
3
/h
0.33
0.52
0.63
0.77
0.92
1.31
1.52
1.92
Water
resistance
kPa
15
30
23
25
35
40
46
40
Noise
12pa
dB(A)
34.5
35
40
40.5
44
45
46
49
30Pa
36
37
41
42
45.5
46
47.5
51
External static
pressure
Pa
12Pa for the standard type (with no diffuser and filter ); 30Pa for the high ESP type
Coil
Type
Copper, high-efficiency louvered fins
Pressure
≤1.6MPa
Motor
Type
Class B, capacitor start
Quantity
/
1
2
Power supply
220-240V
~
50Hz
Protection class
IP20
Input
power
12pa
W
37
52
62
76
96
134
152
189
30Pa
W
44
59
72
87
108
156
174
212
Power lines
mm
2
0.5×3
Protection class
I
Fan
Type
Front-forward multi-vane low-noise centrifugal fan
Quantity
/
1
2
3
4
Connection pipe
Inlet water
Rc3/4(female thread)
Outlet water
Rc3/4(female thread)
Condensate
R23/4(female thread)
Weight
Without return
air box
kg
11.2
13
14.3
15.5
16.6
23
26.2
28
Thermostat (optional)
Mechanical
Z54352A1
Digit
WK-110PA0
Deluxe digit
WK-010PA-K-K
Notes:
a) The left and right modes can be switched over on site. The correction coefficient for both
cooling and heating is 0.9.
Содержание FCU Series
Страница 1: ...Concealed Ceiling Type FCU...
Страница 3: ...Enginnering Data 1 Engineering Data...
Страница 57: ...Design Selection 55 Design Selection...
Страница 61: ...Unit Control 59 Unit Control...
Страница 63: ...Unit Installation 61 Unit Installation...
Страница 72: ...Unit Installation 70 2 2 Installation Steps...
Страница 73: ...Test Operation Troubleshooting Maintenance 71 Test Operation Troubleshooting Maintenance...
Страница 79: ...No JF00303582...