GREE U-Match 5 SERIES UNIT SERVICE MANUAL
16
(2) P4 (LCD displays 04)
(3) P5 (LCD displays 05)
(4) P6 (LCD displays 06)
(5) P7 (LCD displays 07)
Note: You can select P03, P04, P05, P06, P07 in fan mode of indoor fan motor, which means different fan mode combinations
are corresponding to different static pressure. Ex-factory defaulted mode is P05. You can set the mode through wired controller. S01,
S02, S03
„„
S12, S13 means the rotation speed of indoor unit is from low to high.
Combination relationship of P03, P04, P05, P06, P07
Static
pressure
selection
Super
high
speed
High
speed
Medium
high
speed
Medium
speed
Medium
low speed
Low
speed
Quiet
R1 speed
Quiet
R2 speed
Quiet
R3 speed
P03
S09
S08
S07
S06
S05
S04
S03
S02
S01
P04
S10
S09
S08
S07
S06
S05
S04
S03
S02
P05
S11
S10
S09
S08
S07
S06
S05
S04
S03
P06
S12
S11
S10
S09
S08
S07
S06
S05
S04
P07
S13
S12
S11
S10
S09
S08
S07
S06
S05
b.There are 9 selections for high static pressure duct:
(1) P1 (LCD displays 01)
(2) P2 (LCD displays 02)
(3) P3 (LCD displays 03)
(4) P4 (LCD displays 04)
(5) P5 (LCD displays 05)
(6) P6 (LCD displays 06)
(7) P7 (LCD displays 07)
(8) P8 (LCD displays 08)
(9) P9 (LCD displays 09)
Note: You can select P01, P02, P03, P04, P05, P06, P07, P08, P09 in fan mode of indoor fan motor, which means different fan
mode combinations are corresponding to different static pressure. Ex-factory defaulted mode is P05. You can set the mode through
wired controller. S01, S02, S03
„„
S12, S13 means the rotation speed of indoor unit is from low to high.
Combination relationship of P01, P02, P03, P04, P05, P06, P07, P08, P09
Static
pressure
selection
Super
high
speed
High
speed
Medium
high
speed
Medium
speed
Medium
low speed
Low
speed
Quiet
R1 speed
Quiet
R2 speed
Quiet
R3 speed
P1
S05
S03
S02
S02
S01
S01
S01
S01
S01
P2
S06
S04
S03
S03
S02
S02
S02
S02
S02
P3
S07
S05
S04
S04
S03
S03
S03
S03
S03
P4
S08
S06
S05
S05
S04
S04
S04
S04
S04
P5
S09
S07
S06
S06
S05
S05
S05
S05
S05
P6
S10
S08
S07
S07
S06
S06
S06
S06
S06
P7
S11
S09
S08
S08
S07
S07
S07
S07
S07
P8
S12
S10
S09
S09
S08
S08
S08
S08
S08
P9
S13
S11
S10
S10
S09
S09
S09
S09
S09
2.3.9.10 Selecting compensation of temperature sensor at air return
Under debugging state, press Mode button to adjust to
“
12
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 16 selections:
Содержание CF022N1520
Страница 25: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 20 Model GUD50W NhA T Model GUD71W NhA T GUD85W NhA T...
Страница 26: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 21 Model GUD100W NhA T Model GUD125W NhA T GUD140W NhA T...
Страница 27: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 22 Model GUD100W NhA X GUD125W NhA X GUD140W NhA X...
Страница 135: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 130 GUD85W NhA T Product Code CF090W1230...
Страница 195: ...JF00303775...