GREE U-Match 5 SERIES UNIT SERVICE MANUAL
15
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) With refrigerant lacking protection function (LCD displays 01)
(2) Without refrigerant lacking protection function (LCD displays 02)
2.3.9.4 Selecting blowing residual heating of indoor unit
Under debugging state, press Mode button to adjust to
“
05
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) Mode 1 (LCD displays 00)
(2) Mode 2 (LCD displays 01)
Note: Blowing residual heating of indoor unit
Mode 1: Unit stops when reaching temperature point and indoor fan motor does not stop in cooling mode; after unit stops when
reaching temperature point in heating mode, duct type unit and floor ceiling unit blow residual heat for 60s and then stop indoor unit,
while cassette type unit always operates in low fan speed and blows residual heat for 60s when there is malfunction.
Mode 2: After unit stops when reaching temperature point, the indoor fan motor stops operation with a 10s-delay no matter in
cooling mode or in heating mode.
2.3.9.5 Mode selecting of compressor electric heating belt
Under debugging state, press Mode button to adjust to
“
06
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) Mode 1 (LCD displays 00)
(2) Mode 2 (LCD displays 01)
Note:
Mode 1: Compressor electric heating belt starts when outdoor ambient temperature is below 35
℃
and stops when outdoor
ambient temperature is above 37
℃
. When outdoor ambient temperature is within 35
℃
~ 37
℃
, the belt will keep its previous
operation state.
Mode 1: Compressor electric heating belt starts when outdoor ambient temperature is below -2
℃
and stops when outdoor
ambient temperature is above 0
℃
. When outdoor ambient temperature is within -2
℃
~0
℃
, the belt will keep its previous operation
state.
2.3.9.6 Selecting low-power consumption mode
Under debugging state, press Mode button to adjust to
“
07
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) With low-power consumption mode (LCD displays 00)
(2) Without low-power consumption mode (LCD displays 01)
2.3.9.7 Selecting door control function
Under debugging state, press Mode button to adjust to
“
08
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) Without door control function (LCD displays 00)
(2) With door control function (LCD displays 01)
2.3.9.8 Selecting long-distance monitoring or centralized controller
Under debugging state, press Mode button to adjust to
“
10
”
in temperature displaying zone. Timer zone displays setting
state and press
▲
or
▼
button to adjust. There are 2 selections:
(1) Centralized controller (LCD displays 00)
(2) Long-distance monitoring (LCD displays 01)
2.3.9.9 Selecting fan mode of indoor fan motor
Under debugging state, press Mode button to adjust to
“
11
”
in temperature displaying zone. Timer zone displays setting state
and press
▲
or
▼
button to adjust.
a.There are 5 selections for low static pressure duct:
(1) P3 (LCD displays 03)
Содержание CF022N1520
Страница 25: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 20 Model GUD50W NhA T Model GUD71W NhA T GUD85W NhA T...
Страница 26: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 21 Model GUD100W NhA T Model GUD125W NhA T GUD140W NhA T...
Страница 27: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 22 Model GUD100W NhA X GUD125W NhA X GUD140W NhA X...
Страница 135: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 130 GUD85W NhA T Product Code CF090W1230...
Страница 195: ...JF00303775...