9. Remote Air Temperature Sensor
Front side Back side
AP
RT6
CN1
15K
CN15
Remote Air Environment
Temp sensor
Electric box
PCB
2
Notes
(a) Distance between the indoor unit and the remote air temperature sensor should be less than 15m due to
length of the connection cable of remote air temperature sensor;
(b)
Height from floor is approximately 1.5m;
(c)
Remote air temperature sensor cannot be located where the area may be hidden when door is open;
(d)
Remote air temperature sensor cannot be located where external thermal influence may be applied;
(e)
Remote air temperature sensor should be installed where space heating is mainly applied;
(f)
After the remote air temperature sensor is installed, it should be set to “With” through the wired controller so
as to set the remote air temperature to the control point.