Part No.
RMU
Hmm
Wmm
Dmm
Cable Fill
VCMX-45U-1012FO/FR-M
45
2134
254
305
82
VCMX-52U-1012FO/FR-M
52
2445
254
305
82
VCMX-59U-1012F0/FR-M
59
2756
254
305
82
A
B
SIDE
SIDE
FOOT SUPPORT
FRONT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A
A
B
B
C
C
D
D
VCMX-FO INSTALLED WITH GREAT LAKES RACKS
TOOLS:
17mm and 10mm sockets or wrench
ASSEMBLY
1.
The VCMX can be used in between two racks, at the end of a row or mounted to a single rack.
If used between two racks, space 154mm apart.
2. A.
Loosen but do not completely remove the first M10 bolt and star washer from the top of 4
post rack as shown in Front Rack View.
NOTE: Do not remove the bottom bolt!
B.
Remove second M10 bolt and star washer from the bottom of 4 post rack as shown in
Front Rack View.
NOTE: Do not remove the bottom bolt!
3.
Hook vertical cable manager through keyway holes onto the top bolt of the 4-post rack.
NOTE: Do not tighten any hardware until carriage bolts are in place.
4.
Secure the sides of the VCMX to rack with M6 carriage bolts, washers, and M6 nuts as
shown in Detail A.
5.
Reinstall bolt and start washer on bottom of frame through VCM
6.
Insert auxiliary foot support from inside of cable manager as show in Detail B.
7.
Tighten all bolts to secure vertical cable manager
Front Rack View
Loosen, but
DO
NOT REMOVE
bolt
and star washer
Remove Bolt and
Star washer
DO NOT
REMOVE
DO NOT REMOVE
3
DETAIL A
TOP VIEW
DETAIL B
BOTTOM VIEW
SECTION SIDE-SIDE
SCALE 0.11 : 1
FOOT SUPPORT DETAIL
REFER TO STEP 4
FOR MORE DETAILS
.
A
B
SIDE
SIDE
FOOT SUPPORT
FRONT
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A
A
B
B
C
C
D
D
DWG NO:
REV
SHEET:
OF
DRAWN
CHECKED & APP.
TITLE
DRAWING NOT TO SCALE
PART NUMBER:
MATERIAL TYPE:
MATERIAL GAUGE:
FINISH:
GREAT LAKES CASE & CABINET CO., INC.
P.O. BOX 551 EDINBORO, PA 16412
PHONE (814) 734-7303 FAX (814) 734-3907
E-MAIL [email protected]
Use of this document is subject to
a confidentiality and nondisclosure
agreement with Great Lakes Case
& Cabinet Co., Inc. (GLCC) and may
not be reproduced, disclosed or
utilized in whole or in part without
prior written authorization from GLCC.
NOTICE:
TOLERANCE UNLESS OTHERWISE NOTED:
A/- 1
.XXXX +/- .010
.XXX +/- .015
.XX +/- .030
.X FOR REF. ONLY
UNLESS OTHERWISE SPECIFIED
ALL DIMENSIONS ARE IN INCHES
DIMENSIONAL LIMITS APPLY
AFTER APPLICATION OF FINISH
INTERPRET DRAWING PER ASME Y14.5M-1994
THIRD ANGLE
PROJECTION
DATE
DATE
1
1
0
VL
2/20/2020
MS-5.02-67 REF
VCMXxxUxx
RECESSED 45U X 10"W VERTICAL CABLE
MANAGER ASSEMBLY INSTRUCTION
EST. WEIGHT :
N/A
REVISION HISTORY
REV
DESCRIPTION
DATE
APPROVED
0
-
2/20/2020
VL
REF DRAWING -
SPECIAL NOTES:
1) TYPICAL BEND RADIUS = R0.030 x 90° INSIDE UNLESS
OTHERWISE NOTED.
2) DIMENSIONS APPLY BEFORE APPLICATION OF FINISH: ADD
.005" TO EACH SURFACE FOR INSPECTION.
3) ALL LASER CUTS TO HAVE "NORMAL" PROCESSING
!
4) PREPARE THREADS PRIOR TO WELDING OR POWDERCOAT
PER TD-09-109.
5) FINISH PER TD-09-103 (POWDER COAT), CLASS B, TEXTURE
LEVEL 3, ALL SURFACES UNLESS OTHERWISE NOTED.
NOTE!
WHEN THE FOOT SUPPORT IS
INSTALLED ON THE OUTSIDE OF RACK
AS SHOWN, THE SHIM PLATE MUST BE USED
REFER TO STEP 4 FOR MORE DETAILS
.
FOOT SUPPORT SHOWN
ON OUTSIDE OF RACK,
SHIM PLATE MUST BE USED
ON TOP MOUNTING HOLE
SEE STEP
4.A
FOR REFERENCE
FOOT SUPPORT
SHOWN ON
INSIDE OF RACK,
SHIM PLATE MUST
BE OMITTED
SEE STEP
4.B
FOR REFERENCE
I032015
1.A.
LOOSEN, BUT DO NOT REMOVE
1st 1/2-13 BOLT & STARWASHER
FROM TOP OF 4-POST RACK AS SHOWN
1.B.
LOOSEN, BUT DO NOT REMOVE
2nd 1/2-13 BOLT & STARWASHER
FROM TOP OF 4-POST RACK AS SHOWN
DO NOT REMOVE
DO NOT REMOVE
REMOVE BOLT
AND STAR WASHER
LOOSEN, BUT
DO NOT REMOVE BOLT
AND STAR WASHER
1/2-13 HEX BOLT
1/2 STAR WASHER
1/4-20 CARRIAGE BOLT
1/4" FLAT WASHER
1/4-20 NUT
AUXILIARY FOOT