18
GPIO
Input
Input
The tally inputs expect contact closure to ground, through the ground pins on the
connector, to trigger a GPI input event.
Fig. 5-2: GPI Input
When the input transitions off or transitions on, the NV9680 notifies the GV
-
Orbit Server,
which carries out the task defined for the input (if a task has been configured).
During contact closure, a current of 1.2mA flows. A maximum of 48VDC can be applied to
the tally input for less than 5 seconds without failure. No voltage above 5VDC should be
continuously applied.
Output
A tally output is a solid state relay (no audible click) with a maximum resistance of 10
and
current capability of 150mA. It can withstand 200VAC.
Fig. 5-3: GPI Output
When a condition (defined for the relay) occurs, GV
-
Orbit Server notifies the NV9680 which
then opens or closes the relay. The relay switches the connected circuit on or off. This does
not power the circuit. You must provide a power source for the circuit.
+5V
Optical
Isolation
C
E
+5V
Tally Input
n
to internal bus
10K
Customers
Switch (or
Equivalent
Logic)
Optical
Isolation
Customers Load
+5V
499
+
from internal bus
Tally Output
n
V
Optional Grounding
Содержание NV9680
Страница 1: ...User s Guide 13 03082 300 AA 2020 11 24 NV9680 GV ORBIT GV CONVERGENT CONTROL PANEL ...
Страница 20: ...4 Preface Related Documentation ...
Страница 24: ...8 Introduction Other NV9680 Functions ...
Страница 32: ...16 Operation Setup Mode ...
Страница 38: ...22 Technical Details Drawings Fig 6 2 Front and Top Views of the NV9680 ...
Страница 40: ...24 Technical Details Drawings ...
Страница 44: ...28 Misc Topics Ordering Information ...