LDK 8000 User’s Guide
viii
Base Station earthing
The rear of the unit has two separate screw terminals for protective earth
(PE) and video
earth
(VE). These are normally connected by a metal strap.
The protective earth terminal is internally connected to the protective earth conductor of the
power cable. In normal circumstances the connection between the protective earth and the
video earth should
not
be broken. If required, the central earth connection wire of the studio
can be connected to terminal PE in accordance with VDE regulation 0800/part2.
Only if the studio (or OB van) is equipped with separate protective and video earth systems
may the metal strap be removed. Under these circumstances the video earth terminal must be
connected to the central functional earth potential (video earth) of the studio. This earth
potential should have functional protective and noiseless earth (FPE) qualities as stated in the
VDE regulation 0800/part2. A low impedance interconnection of both earth conductors must
be provided at the central studio earthing point.
Metal strap
VE
PE
Содержание LDK 8000
Страница 1: ...LDK 8000 User s Guide HDTV multi standard multi format camera system 3922 496 30571 March 2007 v2 0 ...
Страница 12: ...LDK 8000 User s Guide x ...
Страница 18: ...v2 0 LDK 8000 User s Guide Introduction 1 6 ...
Страница 34: ...v2 0 LDK 8000 User s Guide Configurations 3 6 ...
Страница 72: ...v2 0 LDK 8000 User s Guide Operating instructions 5 32 ...
Страница 106: ...v2 0 LDK 8000 User s Guide Connectors 7 10 ...
Страница 109: ...v2 0 LDK 8000 User s Guide Specifications 8 3 8 2 1 Dimensions Figure 8 1 Dimensions ...
Страница 110: ...v2 0 LDK 8000 User s Guide Specifications 8 4 ...