SHEVS Control Centre RWZ 5 f
4
● Turn on line voltage. The indicators and the service display light up briefly. Subsequently, the indicator
s
flickers for about 15 s (calibration process). If the indicator
s
is permanently lit, there is a fault in a signal line
(see 5).
● Insert the accumulators in the enclosure as illustrated on the “Line voltage, Installation, Accumulators” plan
and connect them.
● The indicator
o
lights up, the indicator
s
goes out, the system is ready for operation. If a fault is still dis-
played, follow the instructions in section 5 “Detection of fault / Troubleshooting”. If necessary, decommission
the Control Centre again (see 2.2).
● While putting into service, check all functions and indicators of the Control Centre and its components. The
individual functions are described in section 3. Also simulate faults and check detection (see 5).
● To finish putting into service, retract all actuators completely (press button
z
).
i
After about 24 hours of continuous operation without mains failure, the accumulators are sufficiently charged
to achieve the full standby time in case of mains failure.
2.2
Putting out of service
● Disconnect the accumulators from the Control Centre (remove accumulator connection line or fuses F2.1 and
F2.2).
i
Charged accumulators have a shelf-life of about 6 months. They must be recharged if stored for a longer
period.
● Switch off line voltage.
3
Functions and operation
Before touching the control elements in the Control Centre it is mandatory to deflect static charge!
3.1
Indicators / control elements of the Control Centre
●
Indicators on the logic board:
−
o
(green):
Trouble-free operation
. Goes out when a fault is detected.
−
r
1 /
r
2 (red):
Alarm
in SHE group 1 / 2, see 3.4.
−
s
1 /
s
2 (yellow):
Fault
in SHE group 1 / 2, see 5.
−
w
(blue):
Wind and Rain Control
is active.
−
9
(blue):
Maintenance is due
(flashes) or
maintenance mode enabled
(lights up).
−
88
(red):
Service display
, see 5.2.
−
a
/
z
(blue):
Travel command in OPEN / CLOSE direction active.
●
Control elements on the logic board:
−
Button
Reset
r
:
Resetting the alarm function of both SHE groups.
−
Button
Reset
S
:
Switching off the warning tone in both SHE groups.
−
Buttons
h
/
D
:
Ventilation position
h
(see 3.5.2) and ventilation time
D
(see 3.5.3).
−
Button
Test
r
:
Switching to accumulator mode and running the alarm function in both the SHE
groups for maintenance purposes.
PFC-
r
(PFC alarm) and buzzer
S
are not enabled.
−
Button
µC-Reset
:
For service purposes only.