Section 4: Electrical

4 ELECTRICAL

! WARNING !

Electric shock may cause serious personal injury or death.

All electrical work must be undertaken by a competent person and 

in accordance with the current edition of BS7671 (the I.E.T. Wiring 

Regulations), including any amendments. Failure to observe this 

legislation could result in an unsafe installation and will invalidate 

all guarantees.
The equipment supplied must be wired according to these 

Installation Instructions to ensure that the heat pump and 

supplementary immersion heater function safely. All electrical 

connections made on-site are solely the responsibility of the 

installer.

4.1 GENERAL

The electric immersion heater is located at the top of the 

volumiser/header and is accessed by undoing the four screws and 

removing the sloping cover. Refer to Figure 4-1. 

Figure 4-1: 

Location of immersion heater

If the immersion heater fitted to the Grant Combined volumiser/

low loss header is to be used, it requires a 230V 50Hz single 

phase electrical supply. Refer to Section 4.2 – Electrical 

Connections.
In order for the immersion heater to be controlled by the Aerona³ 

as a supplementary heat source, the volumiser/header will also 

need to be connected to the heat pump terminal PCB. Refer to 

Section 4.2 – Electrical Connections.

4.2 

ELECTRICAL CONNECTIONS

! WARNING !

Ensure that all electrical supplies to the heat pump and 

volumiser/header are isolated before making any electrical 

connections.

The immersion heater is supplied factory-fitted in the volumiser/

header. However, check that it is securely fitted before proceeding 

with the electrical connections.

IMMERSION HEATER POWER SUPPLY

The immersion heater uses a dedicated power supply from a 

correctly sized circuit breaker in the consumer unit. The final 

supply connection must be made from a 2-pole switch located 

adjacent to the volumiser/header. 

To connect this power supply to the electrical terminals in the 

volumiser/header, refer to Figure 4-2 and proceed as follows:

1. 

Remove the access cover from the top of the volumiser/

header. To do this unscrew and remove the four screws and 

remove the cover.

2.  Feed the immersion heater supply cable through the upper 

(larger) of the two cable glands on the left-hand side of the 

volumiser/header and connect it to the LOWER immersion 

heater electrical terminals as follows:
• 

Live to Terminal L (Brown terminal block)

• 

Neutral to Terminal N (Blue terminal block)

• 

Earth to Earth Terminal (Green terminal block)

Refer to Figure 4-3 for volumiser/header connection 

diagram.

3.  Tighten the cable gland to securely grip the cable.

Figure 4-2: 

Electrical connections

Содержание HPIDSYSLLHKIT

Страница 1: ...UK DOC 0184 Rev 0 3 PROVISIONAL February 2022 Grant Combined Volumiser Low Loss Header Installation Instructions...

Страница 2: ...y means without prior written consent IMPORTANT NOTE FOR USERS These installation instructions are intended to guide the installer in the installation of the Grant Combined Volumiser Low Loss Header S...

Страница 3: ...RICAL 10 4 1 General 10 4 2 Electrical connections 10 4 3 Immersion heater 11 4 4 Electrical connections between lead and supplementary heat pumps 12 5 OPERATION 13 5 1 General 13 5 2 Aerona heat pump...

Страница 4: ...nt Combined volumiser low loss header is an insulated rectangular tank fitted with an integral 3kW electric immersion heater This is housed within a weatherproof external casing with a removable cover...

Страница 5: ...0 Inlet outlet connections 1 BSP Drain cock connection BSP Manual air vent connection BSP Materials Shell Mild steel Outer casing Galvanised mild steel polyester powder coated Insulation Mineral wool...

Страница 6: ...G The Grant Combined volumiser low loss header is supplied wrapped in bubble wrap with a separate kit of components in a plastic bag located inside the top cover Refer to list of components given in S...

Страница 7: ...System Return System Flow System Flow System Return Second Zone Figure 3 1 Heat pump connections on left hand side Heat pump 1 Flow Heat pump 2 Flow Heat pump 2 Return Heat pump 1 Return System Return...

Страница 8: ...the flow regulator window Refer to Figure 3 3 If two heat pumps of the SAME output are connected to the low loss header volumiser both flow regulators should be set to the SAME flowrate as calculated...

Страница 9: ...3 Installation Page 9 Flow from heat pump Flow from heat pump Alternative position Flow to system Flow to system Alternative positions Flow to system Alternative position Figure 3 4 Volumiser only con...

Страница 10: ...ected to the heat pump terminal PCB Refer to Section 4 2 Electrical Connections 4 2 ELECTRICAL CONNECTIONS WARNING Ensure that all electrical supplies to the heat pump and volumiser header are isolate...

Страница 11: ...on heat pump Terminal PCB to Terminal N A1 on the backup heater relay Refer to Figure 4 3 for header volumiser connection diagram 3 Tighten the cable gland to securely grip the cable 4 3 IMMERSION HEA...

Страница 12: ...the immersion heater needs to be replaced it must be fitted to the volumiser header using the gasket provided on the unit Only use a correctly shaped spanner Stilsons or pipe grips should NOT be used...

Страница 13: ...n 5 3 for the correct parameter settings If a second Grant Aerona heat pump is to be used refer to Section 5 5 for the correct parameter settings for the operation of a supplementary heat pump 5 3 PAR...

Страница 14: ...me for a defrost should never be more than 5 minutes including the compressor protection off time of 3 minutes so the total power used during a defrost period by the immersion element would not be mor...

Страница 15: ...Group Code Default Min Max Setting I 21 00 Enable outgoing water set point 0 Fixed set point 1 Climatic curve 1 0 1 0 I 21 01 Fixed outgoing water set point 45 C 23 0 60 0 55 NOTE Refer to the Aerona...

Страница 16: ...GRANT ENGINEERING UK LIMITED Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com...

Отзывы: