2.2 approximate air damper
Setting
Burners are supplied factory set at
the outputs shown.
When commissioning, the air damper
must be adjusted to obtain the
correct CO
2
level and the Installer
must amend the data label.
2.3 Vortex Pro Combi Oil
Boilers using Class C2
Kerosene
.
Vortex Combi e boilers are only for
use with kerosene.
!
nOtE
!
nOtE
The data given above is approximate
only and is based on the boiler being
used with a low level discharge flue.
The above settings may have to
be adjusted on site for the correct
operation of the burner.
Gas Oil is not suitable for use with a
Grant Vortex Pro Combi e boiler.
The net flue gas temperatures given
above are ± 10%.
When commissioning the air damper
must be adjusted to obtain the correct
CO
2
level.
2.4 Flue Gas analysis
To allow the boiler to be commissioned
and serviced, the boiler is supplied with
a combustion test point on the front
cleaning door. When this test point is
used please note the following:
• The test point is for CO
2
and smoke
readings only.
• The boiler efficiency and
temperature must be taken from
the flue.
• Final combustion readings must be
taken from the flue terminal (or test
point on flue elbow if Green system
is used) with all panels fitted.
Figure 2-1:
Vortex Pro External Combi e dimensions
All dimensions in the diagram above are in millimetres.
2.5 Boiler dimensions
Heat
SEDBUK
Nozzle Oil
Smoke Burner Fuel Flue
gas
CO
2
output
SAP 2009 pressure number head flow
temp
Model Burner type
kW
Btu/h
%
bar
kg/h °C %
21e
Riello RDB 2.2 21.0 71,650 89.5 0.60/80ºEH
9.0
0-1
T1
1.83
80 (flue)
12
235
(door)
26e
Riello RDB 1
26.0
88,700
90.2
0.75/80ºEH
8.0
0-1
T2
2.16
75 - 80
12
36e
Riello RDB 2.2 36.0 123,000
91.6
1.00/80ºEH
9.1
0-1
T5
3.01
78
12
7