--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.

NOTES: Airflow based upon cooling performance at 230V with no electric heat and no filter.  Airflow at 208V is 

approximately the same as 230V because the mult-tap ECM motor is a constant torque motor. The 
torque doesn’t drop off at the speeds in which the motor operates.

5

.

AIRFLOW PERFORMANCE

Airflow performance data is based on cooling performance with a dry coil and no filter in place. Select performance table for appropriate unit 
size external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric 
heat operation. 

0[0]

0.1[.02] 0.16[.04]

0.2[.05] 0.3[.07]

0.4[.10]

0.5[.12]

0.6[.15]

0.7[.17]

0.8[.20]

SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts

External Static Pressure-Inches W.C.[kPa]

SCFM(Watts)

Tap(2)

Tap(1)

Motor

Speed

Tap(5)

Tap(4)

24

36

Tap(3)

-Factory

Model

Number

SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts

Tap(2)

Tap(1)

Tap(5)

Tap(4)
Tap(3)

-Factory

1016

955

924

914

870

827

790

741

691

657

139

146

156

157

165

174

185

195

202

209

955

892

863

853

804

768

729

671

630

---

118

125

134

135

142

152

162

169

178

---

927

829

791

789

739

701

643

597

---

---

109

105

112

113

121

131

137

147

---

---

887

766

683

671

631

567

522

465

---

---

97

87

82

83

93

99

108

112

---

---

829

698

589

547

366

347

277

234

---

---

81

71

63

60

54

60

64

72

---

---

1532

1471

1428

1386

1372

1327

1271

1210

1159

1101

 233

247

262

266

270

275

281

290

298

310

1408

1343

1297

1265

1246

1197

1141

1073

1015

880

197

209

214

219

222

227

238

245

256

273

1326

1230

1174

1151

1107

1024

896

828

807

726

148

165

172

175

183

190

202

217

221

225

1236

1175

1100

1075

1029

963

835

736

661

582

124

130

133

137

142

146

157

168

176

187

1182

1141

1020

995

944

818

648

553

461

363

124

112

105

103

107

112

124

129

140

149

SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts

Tap(2)

Tap(1)

Tap(5)

Tap(4)

48

60

Tap(3)

-Factory

SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts
SCFM
Watts

Tap(2)

Tap(3)

Tap(1)

Tap(5)

Tap(4)

-Factory

2072

2013

1970

1935

1923

1878

1830

1783

1736

1688

447

464

483

489

497

514

530

545

558

570

1860

1816

1783

1735

1679

1640

1591

1542

1504

1481

348

364

378

383

395

408

418

429

451

463

1702

1651

1598

1560

1547

1497

1438

1385

1331

1280

268

281

296

304

312

325

337

349

361

375

1393

1358

1197

1179

1155

1139

1074

1020

964

896

227

234

248

258

269

270

283

296

313

325

1365

1239

1148

1078

1050

965

904

886

831

797

220

226

231

243

264

269

281

293

301

317

1515

1463

1407

1386

1358

1308

1262

1215

1153

1073

205

218

229

235

239

251

263

276

285

301

1337

1265

1208

1156

1148

1095

984

955

963

789

145

157

167

173

178

186

197

212

225

235

2054

2015

1970

1947

1928

1886

1846

1804

1742

1654

 470

495

512

518

528

542

553

569

567

548

1883

1840

1797

1783

1754

1712

1670

1622

1579

1541

367

388

406

411

420

422

445

454

466

479

1721

1674

1625

1582

1566

1528

1484

1443

1401

1345

289

305

319

327

330

341

353

365

378

387

Содержание WATPM Series

Страница 1: ...e instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death 1 SAFETY 2 2 GENERAL 3 3 APPLICATIONS 5 4 ELECTRICAL WIRING 7 5 AIRFLOW PERFORMANCE 9 6 DUCTWORK 10 7 REFRIGERANT CONNECTIONS 10 8 AIR FILTER not factory installed 11 9 FILTER INSTALLATION DIMENSIONS 12 10 WIRING 13 PARTS LIMITED W...

Страница 2: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or death WARNING PROPOSITION 65 This appliance contains fiberglass insula tion Respirable particles of fiberglass are known to State of California to cause cancer All manufacturer products meet current f...

Страница 3: ... slab with supply air plenum and ductwork completely encased must be not less than 2 inches of concrete See NFPA 90A The unit can be positioned for upflow left and right downflow position This Air Handler provides the flexibility for installation in any upflow or downflow horizontal application The direct drive motors provides a selection of air volume to match any application 5 Speed motors provi...

Страница 4: ...05 16 NOTE 25 CLEARANCE IS REQUIRED IN THE FRONT OF THE UNIT FOR FILTER AND COIL MAINTENANCE SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION ELECTRICAL CONNECTIOS MAY EXIT TOP OR EITHER SIDE HIGH VOLTAGE CONNECTION 7 8 1 3 8 1 3 4 DIA KNOCK OUTS LOW VOLTAGE CONNECTION BREAKER SWITCH FOR ELECTRIC HEATER ONLY VAPOR LINE CONNECTION COPPER SWEAT LIQUID LINE CONNECTION COPPER SWEAT AUXILIARY DRA...

Страница 5: ... mounting tab over edge in opening With screwdriver or pencil pull blue tab with hole away from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if more than one is provided Replace single point wiring jumper bar if it is used on line side of breaker and tight...

Страница 6: ...PLICATIONS lower front service panel removed view AIRFLOW AIRFLOW Fig 4 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION TXV PRIMARY DRAIN CONNECTION VERTICAL DRAIN PAN AUXILIARY HORIZONTAL AUXILIARY UPFLOW DOWNFLOW STRAPS REAR WATER CATCHER TOP AIR STOP DRAIN CONNECTION DRAIN CONNECTION ...

Страница 7: ...d power wiring has been maintained Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Use of multiple supply circuits require grounding of each circuit to lug s provided in unit Horizontal units must be co...

Страница 8: ...e 29 7 26 2 42 7 37 5 55 8 48 8 33 6 30 1 35 46 6 41 4 50 45 59 6 52 7 60 60 240 208 240 208 X X X X X X X X X X X X X X X X X X X X X X X X X 5 28 5 24 9 30 25 7 5 41 5 36 3 45 40 10 54 5 47 6 60 50 5 30 30 7 5 45 40 10 60 50 5 7 5 10 15 20 15 60 24 36 MIN Circuit Ampacity MAX Fuse or Breaker HACR Ampacity Heat Kit Model Air Handler Model kW Electric Heat 5 7 5 10 15 20 48 Fan speed 1 2 3 4 5 X 5...

Страница 9: ... 64 72 1532 1471 1428 1386 1372 1327 1271 1210 1159 1101 233 247 262 266 270 275 281 290 298 310 1408 1343 1297 1265 1246 1197 1141 1073 1015 880 197 209 214 219 222 227 238 245 256 273 1326 1230 1174 1151 1107 1024 896 828 807 726 148 165 172 175 183 190 202 217 221 225 1236 1175 1100 1075 1029 963 835 736 661 582 124 130 133 137 142 146 157 168 176 187 1182 1141 1020 995 944 818 648 553 461 363 ...

Страница 10: ...D C 20036 If duct system incorporates flexible air duct be sure pressure drop Information straight length plus all turns shown in ACCA Manual D is accounted for in system Supply plenum is attached to the 3 4 duct flanges supplied with the unit Attach flanges around the blower outlet IMPORTANT If an elbow is included in the plenum close to the unit it must not be smaller than the dimensions of the ...

Страница 11: ...ure installation of these such filtration systems are installed correctly IMPORTANT DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM DO NOT FILTER THE SUPPLY AIR DUCT SYSTEM THIS WILL CHANGE THE PERFORMANCE OF THE UNIT AND REDUCE AIRFLOW 7 1 CONDENSATE DRAIN TUBING Consult local codes for specific requirements IMPORTANT 1 When making drain fitting connections to the drain pan use a thin layer of Te...

Страница 12: ...direction as airflow 9 FILTER INSTALLATION DIMENSIONS Fig 6 EXTERNAL FILTER BASE DIMENSIONAL DATA 24 18Χ20 457Χ508 18 3 466 21 6 548 1 25 4 20 8 16 3 36 48 60 20Χ22 508Χ559 20 7 526 23 9 608 1 25 4 23 18 8 H IN mm Return width A IN Return length B IN MODEL FILTER SIZE IN mm W IN mm D IN mm H W B RETURN AIR OPENING DEPTH A D FILTER RAILS FILTER COVER MANUAL BOLT NOTE Air filter is optional part not...

Страница 13: ...ns H P system with electric heating Wiring please refer to the Owner s Manual of the thermostat W2 D w1 These units must be wired and installed in accordance with all National and Local Safety Codes 24 48 60 Phase Voltage frequency Input Current Fuse Indoor unit A 15A 15A 15A 15A Line Quantity 3 3 3 3 Line Diameter AWG 14 14 14 14 Line Quantity 3 3 3 3 Line Diameter AWG 14 12 10 10 Line Quantity 4...

Страница 14: ...nit 2 To Be Wired In Accordance With NEC And Local Codes 3 If Any Of The Original Wire As Supplied Must Be Replaced Use The Same Or Equivalent Type Wire 4 Connect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Regulation of SW1 to choose the Speed 6 See Airflow Tables For Tap Usage 5 4 3 2 1 CN6 BROWN CN1 CN2 PLUG LIATE BLACK C W321 ON 123 SW1 ON 123 ON 123 SW1 ON 123 ...

Страница 15: ... 6 6 7 1 0 6 7 1 0 1 2 5 1 2 3 4 5 6 7 5kW HEAT KIT HEATER KIT PLUG 7 5kW CB1 50A 10kW CB1 60A 4 8 2 6 2 4 8 2 6 5 8 2 4 5 5 5 7 8 5 7 6 7 0 6 1 6 8 5 5 7 8 5 7 6 7 0 6 1 6 8 E T I H W 2 5 8 2 W L1Ć L2Ć L1 L2 6 6 7 1 0 4 8 2 6 5 5 5 8 8 1 W 7 L1Ć L2Ć L1 L2 E U L B D E R 6 6 6 7 1 0 6 7 1 0 1 2 5 1 2 3 4 5 6 15kW HEAT KIT 10kW 5kW HEATER KIT PLUG 4 8 2 6 2 4 8 2 6 5 2 5 5 5 7 8 5 7 6 7 0 6 1 6 8 E ...

Страница 16: ...2020001C1079 V1 2 ...

Отзывы: