![Granby KHM SERIES Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/granby/khm-series/khm-series_installation-operation-and-service-manual_2254872014.webp)
13
Connecting non-metallic vent pipe and fittings with thermal insulation shall be prohibited.
Horizontal portions of the venting system shall be supported to prevent sagging by installing
support every 36 inches. The horizontal runs must be sloping upwards not less than ¼ inch per
foot from the boiler to the chimney connector.
A furnace shall not be connected to a chimney flue serving a separate appliance designed to
burn solid fuel.
Provisions for adequate combustion and ventilation air shall be in accordance with one of the
following:
1. Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 ,
2. Sections 7.2, 7.3 or 7.4 of Natural Gas and Propane Installation Code, CSA B149.1 ,
3. Applicable provisions of the local building code.
CONDENSATION
If you have condensation in your chimney, make sure that the
chimney size is according to the tables in THE NATIONAL FUEL
GAS CODE ANDSI Z223.1/NFPA 54 AND/OR NATIONAL GAS AND
PROPANE
INSTALLATION
CODE
CAN/CSA
B149.1.
The
temperature at the entrance of the chimney can be increased by
insulating the flue-pipe between the furnace and the chimney base.
If this is not sufficient, consider cutting or removing some flue
baffles in the furnace.
CHIMNEY/VENT Furnace is approved for factory built chimney type “L” vents. Breech is
certified for 5” vent pipe. Keep vent/flue pipe as short as possible with a
minimum upward slope of ¼’’ per foot. Vent/flue pipes MUST NOT pass
through a ceiling. Maximum flue gas temperature is 575°F.
COMBUSTION &
Install openings and ductwork to the furnace room providing fresh
VENTILATION AIR outside combustion and circulation air for cooling the furnace casing, as
installation code requires. If installed in a closed room, provide two free
air ventilation openings of at least 8” x 12” (96 sq. in.) free flow area near
ceiling and floor. Gas burners must have sufficient air to allow vent
systems to operate properly.
DRAFT
Use approved DOUBLE ACTING draft control supplied for 5” pipe. Set
specified draft minimum pressure of -0.01” wc. THE CHIMNEY MUST
BE EQUIPPED WITH A DOUBLE ACTING DRAFT REGULATOR.
FAILURE TO COMPLY WITH THIS MAY RESULT IN IMPROPER
OPERATION LEADING TO POTENTIAL DANGEROUS OPERATION
OF UNIT AND INJURIES TO PERSON AND LOSS OF LIFE.