background image

COMPACT-MULTI – INSTALLATION/OPERATION MANUAL 

 

5IM-OF-K4C0-01 

Jun/12 

2.4  MULTI - POSITION 

 

The Compact-multi is designed to operate in either upflow, downflow or horizontal mode.  The 
breech is convertible from front to rear by switching the breech pipe and cover plates.  The 
burner is always installed in an upright position by four nuts. 

 

2.5  PLACEMENT & VENTING 

 

Furnace installation should conform to the required installation code for oil-fired equipment 
(USA: NFPA 31, Canada: CSA B139). 

 

UPFLOW

 

Install the furnace close to chimney or vent and central to ductwork.  The 
furnace may be placed on a combustible floor or, if required, on a Granby 
Appliance Stand or four (4) rigid blocks.  The floor must be strong enough 
to carry the weight of the furnace.  The furnace is shipped in upflow 
configuration. 

  

DOWNFLOW 

Install the plenum and sub-base as shown in Figure - 5 or the illustration 
included with sub-base kit (K4C-KA-0500-00).  A sub-base is required to 
support the furnace.  This sub-base maintains the clearances to 
combustible materials through the floor and provides a convenient 
attachment to the plenum.  For furnaces installed on a combustible floor, 
ensure that the requirements of the authorities having jurisdiction are 
satisfied. 

 

HORIZONTAL

 

In suspended horizontal positions four 3/8”-16 x 4” eyebolts and 3/8” nuts 
are use to suspend the furnace.  Determine the appropriate side and 
remove the knockouts.  Four weld nuts (3/8 - 16 UNC) are concealed 
behind knockouts on either side of the furnace.  For installations where the 
furnace will be supported from below, use 4” long 3/8” UNC bolts as 
adjustable legs.  Eyebolts complete with locking nuts are available.  The 
locking nuts should be threaded on the eyebolt 3/4” to 1”.  This provides a 
stop for the eyebolt. 

 

CHIMNEY/VENT

  Connect the furnace to a chimney/vent system of size and condition 

required by the NFPA 31 (USA) or CSA B139 (Canada) code.  Furnace is 
approved for factory built chimney type “L” vent.  Breech is certified for 5” 
vent pipe.  Keep vent/flue pipe as short as possible with min. 1/4” per foot 
upward slope.  Use approved fitting through a wall.  Vent/flue pipes MUST 
NOT pass through a ceiling.  Maximum flue gas temperature is 575°F. 

 

THROUGH-THE- 

Furnace is approved for Granby Direct Vent with Riello burner. 

WALL VENTING

 

 

COMBUSTION & 

Install openings and ductwork to the furnace room to provide fresh outside 

VENTILATION AIR 

combustion and circulation air for cooling the furnace casing, as 
installation codes require (USA:  NFPA 31, Canada:  B139).  If installed in 
a closed room, provide two free air ventilation openings of at least 8” x 12” 
(96 sq. in.) free flow area near ceiling and floor.  Oil burners must have 
sufficient air to allow vent systems to operate properly.  See furnace 
operating label.  Not applicable to Direct Vent. 

 

Содержание COMPACT- multi

Страница 1: ...EDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA Std B140 0 Std B140 4 CONFORMS TO UL 727 GRANBY FURNACES INC PO Box 637 12118 Hwy 209 Parrsboro Nova Scotia Canada B0M 1S0 www granbyindustries com ...

Страница 2: ...tion 4 2 3 Installation Codes 4 2 4 Multi Position 5 2 5 Placement Venting 5 2 6 Assemble Install Burner 7 2 7 Changing Nozzle 7 2 8 Set Burner for Efficient Operation 7 2 9 Blower Setting 8 2 10 Air Conditioning 8 2 11 Humidifier 8 2 12 Thermostat Anticipator Setting 8 2 13 Fan Control 8 2 14 Off Cycle Air Circulation 9 3 0 Burner Specification 9 4 0 Blocked Vent Switch 9 5 0 Oil Tanks Piping 10 ...

Страница 3: ...s manual in a safe place for future reference Follow manual carefully for the correct way to install and operate this unit Do not operate this appliance until operating instructions have been read and fully understood DANGER Do not use this furnace as a construction heater Use of this furnace as a construction heater exposes it to abnormal conditions contaminated combustion air and lack of air fil...

Страница 4: ... bottom of the furnace See Figure 7 1 3 REGULAR MAINTENANCE Check complete operation at least once a year In Canada see B139 Section 14 Maintenance for recommended servicing procedure Heat exchanger ducts are accessed through breech access panels at front of unit Replace stainless steel gas baffles after cleaning Cerafelt 1 4 gaskets may have to be replaced 1 4 WARNINGS NEVER burn garbage or paper...

Страница 5: ...ocal state or provincial codes Improper installation will result in voiding of warranty 2 2 CAUTION DO NOT START THE BURNER UNTIL ALL FITTINGS COVERS AND DOORS ARE IN PLACE DO NOT TAMPER WITH THE FURNACE OR CONTROLS CALL A QUALIFIED BURNER TECHNICIAN FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE 2 3 INSTALLATION C...

Страница 6: ...8 16 x 4 eyebolts and 3 8 nuts are use to suspend the furnace Determine the appropriate side and remove the knockouts Four weld nuts 3 8 16 UNC are concealed behind knockouts on either side of the furnace For installations where the furnace will be supported from below use 4 long 3 8 UNC bolts as adjustable legs Eyebolts complete with locking nuts are available The locking nuts should be threaded ...

Страница 7: ... to high If the Compact multi is used in a down flow position with the Scotty SS a diverter base is available for easier duct connections SUB BASE The sub base kit is used to provide the proper support and clearances for a furnace that is used in the downflow position and is mounted on a floor with the supply ducting running beneath the floor K4C KA 0500 00 DIVERTER BASE The diverter base is used ...

Страница 8: ...ur nuts PUMP BY PASS For one pipe system factory setting no plug PLUG WIRING Refer to wiring label and Figure 4 for correct burner connections THERMOSTAT Connect thermostat terminals 2 7 CHANGING NOZZLE NOZZLE CHANGE If a new nozzle of a different size is installed change the heating blower speed according to the operating decal or section 3 0 BURNER SPECIFICATIONS 2 8 SET BURNER FOR EFFICIENT OPE...

Страница 9: ...ing nor cooling are required Set blower speeds to match the installation requirements On the model number the last 2 digits represent the type of motor 03 for a PSC 1 3HP motor and E3 for a 1 2HP ECM high efficiency motor 2 10 AIR CONDITIONING An air conditioning coil may be installed on the supply side only Coils installed on the return side will cause condensation on the heat exchanger that will...

Страница 10: ... 50 60A 150 2 3 75 000 22 1050 1050 3 2 0 73 2 76 102 200 0 60 60A 3 5 88 000 26 1150 1100 2 1 0 81 3 07 113 400 0 65 60A 4 0 98 000 29 1150 1100 2 1 Direct Vent K4C V1 0090 03 Riello BF3 0 61 2 31 85 400 0 50 80W 150 5 0 0 5 74 000 22 990 990 4 3 0 73 2 76 102 200 0 60 60W 6 0 1 5 88 000 26 1180 1090 3 2 The turbulator air settings found in this section should be used as a guide With ECM motors t...

Страница 11: ... vent switch should shut down the burner within 10 minutes or sooner 4 Once the system has cooled the blocked vent switch can manually be reset 5 This procedure should be tested a second time 6 After testing the blocked vent switch the chimney should be cleared of obstruction and the heating system tested on a long run cycle If the block vent switch shuts down the system check to ensure there is e...

Страница 12: ...covers are secured in place 7 0 GENERAL SPECIFICATIONS CLEARANCE TO COMBUSTIBLES UPFLOW DOWNFLOW POSITION Top 1 25 mm Front 24 610 mm Rear Front Breech 2 51 mm Rear Rear Breech 24 610 mm Side Non Access 2 51 mm Side Access 24 610 mm Return Air Side Ductwork 1 25 mm Flue Pipe 9 229 mm Floor Combustible Upflow only Downflow must have sub base K4C KA 0500 00 Horizontal Position Top 6 152 mm Front 24 ...

Страница 13: ... 1 4 1124 mm Width 19 1 2 495 mm Width w Filter Bracket 21 1 2 546 mm PLENUM DIMENSIONS Cold air return 20 x 16 508 x 406 mm Hot air supply 18 1 4 x 21 5 8 464 x 549 mm Height to plenum 44 1118 mm A C COIL LOCATION Minimum height above the heat exchanger 10 254 mm OPENING HEIGHTS from floor Burner c l 24 610 mm Smoke pipe c l 37 940 mm SMOKE VENT PIPE 5 Chimney 4 Direct Vent CLEANOUTS Front covers...

Страница 14: ...t wrong Adjust barometric regulator for 0 03 wc draft pressure at breech Oil burner keeps turning off Dirty air filter Change air filter Restricted air supply return Check all air return supply registers Limit control Check ductwork for blockage Motor over heating Check motor speed correct for nozzle on furnace label settings Dirty nozzle Call technician to replace nozzle Burner reset cuts out No ...

Страница 15: ...R MOST RECENT UPDATES PLEASE VISIT www granbyindustries com The following form MUST be completed for the warranty to be valid Installed by Address Telephone Date START UP TEST RESULTS Nozzle Pressure Air Turbulator CO2 Smoke Number Breech Draft Stack Temperature Test Performed By Staple Printout Here Staple Smoke Spot Here ...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ... 16 Rear Cabinet Cleanout Cover K40 CB 0150 00 K4C 17 Divider Assembly K4C CB 0050 00 K4C 18 Base Pan K00 CB 0028 00 K4C 19 Blower Key K00 CB 0028 00 K4C 19 Blower Key 3BU 10 00DD 00 K4C 20 G10 DD Blower 3BM 33 4SDD 00 K4C 21 Motor 1 3 hp Direct Drive 4 Speed 3BM 50 ECM0 02 K4C 22 Motor 1 2 hp Direct Drive ECM 4CA 00 505M 23 K4C 23 Motor Run Capacitor 5 micro farad Not Shown K00 BM 1033 00 K4C 24 ...

Отзывы: