Installation of this equipment involves potentially
hazardous procedures. Only trained and qualified
personnel who have read and who understand
the information in this manual should install this
equipment.
NOTE:
NOTE:
NOTE: For complete Technical Specification
information, see Driver Operation manual.
Power
Power
Power Supply
Supply
Supply Requirements
Requirements
Requirements
Improper wiring may cause electric shock or other
serious injury if work is not performed properly.
Have a qualified electrician perform any electrical
work. Be sure your installation complies with all
local codes and regulations.
See the table below for power supply requirements.
The driver requires a dedicated circuit protected with
a circuit breaker.
Model
Model
Model
Voltage
Voltage
Voltage
Phase
Phase
Phase
Hz
Hz
Hz
kVA
kVA
kVA
24X901
200–240
Vac
1
50/60
2.5
NOTE:
NOTE:
NOTE: The protective earthing ground conductor
must be equal to the phase conductions..
Hazardous
Hazardous
Hazardous Area
Area
Area Cabling
Cabling
Cabling and
and
and Conduit
Conduit
Conduit
Requirements
Requirements
Requirements
Explosion
Explosion
Explosion Proof
Proof
Proof
All electrical wiring in the hazardous area must be
encased in Class I, Division I, Group D approved
explosion-proof conduit. Follow all National, State,
and Local electric codes.
A conduit seal is required within 18 in. (457
mm) of the driver for the US and Canada. See
.
All cables must be rated 70°C minimum.
Flame
Flame
Flame Proof
Proof
Proof (ATEX)
(ATEX)
(ATEX)
Use appropriate conduit, connectors, and cable
glands rated for ATEX II 2 G. Follow all local codes
and regulations.
All cable glands and cables must be rated 70°C
minimum.