Local Control Box (optional accessory)
311592Z
21
Local Control Box (optional accessory)
See F
IG
. 1 on page 9, and F
IG
. 14. Install the local con-
trol box (C) in the hazardous area as close to pump as
possible.
See F
IG
. 2 on page 10 to wire the local control box to the
VFD. All cabling in the hazardous area must be in explo-
sion-proof conduit and secured by explosion-proof seal
fittings. See
Hazardous Area Cabling and Conduit
Requirements (Explosion Proof)
, page 13 and T
ABLE
2.
Local Control Box has a conduit connection point on top
and bottom for installation convenience.
F
IG
. 14. Local Control Box
120991 ATEX Control Box
120373 UL/CSA Control Box
TI10719A
SECURE
DISABLE
START/STOP
FAULT
RESET
Not Used
with an ACS
Module
Not Used with
an ACS Module
SECURE
DISABLE
START/STOP
FAULT
RESET