All electrical wiring in the hazardous area must be
encased in Class I, Division I, Group D approved
explosion-proof conduit. Follow all national, state,
and local electric codes.
A conduit seal (D) is required within 18 in. (457 mm)
of the motor for the US and Canada. See Figs. 3
and 4.
All cables must be rated at 70°C (158°F).
Flame
Flame
Flame Proof
Proof
Proof (ATEX)
(ATEX)
(ATEX)
Use appropriate conduit, connectors, and cable
glands rated for ATEX II 2 G. Follow all National,
State, and Local electric codes.
All cable glands and cables must be rated at 70°C
(158°F).