Installation
313903B
5
Terminal Strip -
Right Side Power Connections
Terminal Strip Bottom - Fault Relay Connections
Terminals 9 - 14, Zone 1 Fault Relay:
The zone fault relay is a double-pole, double-throw (DPDT), Form-C relay. Relay contacts are wired directly to the ter-
minal strip. Pole “A” uses terminals 9 (N.C.), 10 (com) and 11 (N.O.). Pole “B” uses terminal 12 (N.C.), 13 (com) and
14 (N.O.). Power is not supplied to these contacts. Contacts are rated 0.5 ampere at 125VAC and 1.0 ampere at
30VDC. The relays may be programmed to either energize or deenergize during a fault. (See F
. 3.)
Terminals
Power Connection
1 & 2
115/230 VAC power input terminals
(polarity insensitive)
3
Earth Ground
4
+24 VDC Input
5
0 VDC Input
6
+24 VDC Out (for sensor use)
7
0 VDC Out (for sensor use)
8
0 VDC Out (for sensor use)
F
IG
. 2
F
IG
. 3: Examples of Wiring for Zone 1 Faults
Ignition Shutdown*
Magneto Grounding
External Flow/No Flow Lights
Energize External Load
(relay coil, etc.)
*NOTE:
Do not
connect to high
voltage.
Connect to
controls only.