Setup
6
312864B
Fieldbus Connectors
PROFINET
The Ethernet interface operates at 100Mbit, full duplex, as required by PROFINET. The Ethernet interface is auto
polarity sensing and auto-crossover capable.
Network Status (NS)
Module Status (MS)
Link/Activity (Link)
F
IG
. 4
TI11814A
NS
MS
Link
State
Description
Comments
Off
Offline
- No power
- No connection with IO Controller
Green
On-line, (RUN)
- Connection with IO Controller established
- IO Controller with RUN state
Flashing Green
On-line, (STOP)
- Connection with IO Controller established
- IO Controller in STOP state
State
Description
Comments
Off
Not initialized
No power or module in “SETUP” or “NW_INIT” state
Green
Normal operation
Diagnostic event(s) present
Flashing Green
Initialized, diagnostic event(s) present
Used by engineering tools to identify node on net-
work
Red
Exception error
Module in state “EXCEPTION”
Red (1 flash)
Configuration error
Expected Identification differs from Real Identifica-
tion
Red (2 flashes)
IP Address not set
Set IP address via system monitor or DNS server
Red (3 flashes)
Station Name not set
Set Station Name via system monitor
Red (4 flashes)
Major Internal Error
Cycle system power; replace module
State
Description
Off
No Link, no communication present
Green
Link established, no communication present
Green, flashing
Link established, communication present