background image

Warnings

Warnings

Warnings

The following warnings are for the setup, use, grounding, maintenance and repair of this equipment. The exclamation
point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risks. When these
symbols appear in the body of this manual or on warning labels, refer back to these warnings. Product-specific hazard
symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.

WARNING

WARNING

WARNING

FIRE

FIRE

FIRE AND

AND

AND EXPLOSION

EXPLOSION

EXPLOSION HAZARD

HAZARD

HAZARD

Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help
prevent fire and explosion:

• Use equipment only in a well-ventilated area.
• Eliminate all ignition sources such as pilot lights, cigarettes, portable electric lamps, and plastic

drop cloths (potential static sparking).

• Keep work area free of debris, including solvent, rags, and gasoline.
• Do not plug or unplug power cords, or turn power or light switches on or off when flammable

fumes are present.

• Ground all equipment in the work area. See Grounding

Grounding

Grounding instructions.

• Use only grounded hoses.
• Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they

are antistatic or conductive.

• Stop

Stop

Stop operation

operation

operation immediately

immediately

immediately if static sparking occurs or you feel a shock, Do not use equipment until

you identify and correct the problem.

• Keep a working fire extinguisher in the work area.

ELECTRIC

ELECTRIC

ELECTRIC SHOCK

SHOCK

SHOCK HAZARD

HAZARD

HAZARD

This equipment must be grounded. Improper grounding, setup, or usage of the system can cause
electric shock.

• Turn off and disconnect power at main switch before disconnecting any cables and before servicing

or installing equipment.

• Connect only to grounded power source.

• All electrical wiring must be done by a qualified electrician and comply with all local codes and

regulations.

2

332356E

Содержание 24N977

Страница 1: ...an an an Advanced Advanced Advanced Web Web Web Interface Interface Interface AWI AWI AWI For For For professional professional professional use use use only only only Not Not Not approved approved approved for for for use use use in in in explosive explosive explosive atmospheres atmospheres atmospheres or or or hazardous hazardous hazardous locations locations locations Important Important Impor...

Страница 2: ...rea free of debris including solvent rags and gasoline Do not plug or unplug power cords or turn power or light switches on or off when flammable fumes are present Ground all equipment in the work area See Grounding Grounding Grounding instructions Use only grounded hoses Hold gun firmly to side of grounded pail when triggering into pail Do not use pail liners unless they are antistatic or conduct...

Страница 3: ...eet SDS from your distributor or retailer Do not leave the work area while equipment is energized or under pressure Turn off all equipment and follow the Pressure Pressure Pressure Relief Relief Relief Procedure Procedure Procedure when equipment is not in use Check equipment daily Repair or replace worn or damaged parts immediately with genuine manufacturer s replacement parts only Do not alter o...

Страница 4: ...l local codes and regulations NOTICE NOTICE NOTICE To avoid damage to the circuit board wear Part No 112190 grounding strap and ground appropriately Kit Kit Kit 24N978 24N978 24N978 For For For Modbus Modbus Modbus RTU RTU RTU Communication Communication Communication The FO Converter enables Modbus RTU communication with a user supplied PLC using a serial cable Depending on your system requiremen...

Страница 5: ...Cable Cable Cable Connections Connections Connections 1 Use a fiber optic cable to make a crossover connection from the FO Converter to the Display Control Module DCM or the Advanced Display Control Module ADCM See Accessories page 13 for available Graco fiber optic cables Typical Typical Typical Color Color Color Convention Convention Convention FO FO FO Converter Converter Converter Port Port Po...

Страница 6: ... wire A Ground Ground B not used Data B C Rx IN Data A D not used not used E Tx OUT not used Set Set Set Up Up Up the the the Fiber Fiber Fiber Optic Optic Optic Converter Converter Converter 1 Set the DIP switches on the bottom of the converter as shown These settings are correct for either RS 232 or RS 485 2 wire with a 57 6 K baud rate Figure 3 2 Set the selector switch to RS 232 or RS 422 485 ...

Страница 7: ... 15V337 AWI AWI AWI Module Module Module L Serial cable customer supplied to connect from FO Converter to communication device M Programmable logic controller PLC customer supplied U Clamp end blocks Graco PN 255045 See Accessories page 13 V Existing power barrier in 16M167 Installed Installed Installed on on on User User User Supplied Supplied Supplied Din Din Din Rail Rail Rail NOTE NOTE NOTE Th...

Страница 8: ...R086 with with with power power power supply supply supply one one one converter converter converter Installed Installed Installed in in in Kit Kit Kit 24R086 24R086 24R086 with with with power power power supply supply supply more more more than than than one one one converter converter converter 8 332356E ...

Страница 9: ...VERTER Modbus TCP to Modbus RTU 1 6 121994 CABLE CAT 5 1 ft Items marked are not sold separately Electrical Electrical Electrical Connections Connections Connections 1 Use wires provided ref 2 to connect power terminals 23 and 24 on the Modbus Gateway to terminals on a power supply The Modbus Gateway has an input voltage range of 9 to 28 VDC with a 2 0 W power consumption 2 Use wires provided ref ...

Страница 10: ...X 1 RX 2 2 For For For Modbus Modbus Modbus TCP TCP TCP Communication Communication Communication with with with a a a PLC PLC PLC Connect a customer supplied ethernet CAT 5 RJ45 cable from the ethernet port T on the Modbus Gateway directly to an available ethernet port to the PLC See Accessories page 13 for available Graco CAT 5 cables For For For AWI AWI AWI Communication Communication Communica...

Страница 11: ...on device See Accessories page 13 P Personal Computer PC Note See Modbus Modbus Modbus Configuration Configuration Configuration Information Information Information on the next page if you want to communicate directly from the Modbus Gateway to a PC R Ethernet switch In Graco AWI 15V337 S AWI board U Clamp end blocks Graco PN 255045 See Accessories page 13 V Existing power barrier in 16M167 Instal...

Страница 12: ... table on this page to restore the device configuration to the factory defaults Use the OEM Netbiter Config utility found at www anybus com to change the device configuration Also see the Installation Leaflet for the Anybus Modbus Gateway supplied for more information TCP IP TCP IP TCP IP Settings Settings Settings IP Address 192 168 178 205 Subnet Mask 255 255 0 0 Default Gateway 192 168 178 200 ...

Страница 13: ...e 100 ft 30 m 15V843 CAT 5 RJ45 Cable 200 ft 61 m 16M172 Fiber Optic Cable 50 ft 15 m 16M173 Fiber Optic Cable 100 ft 30 m Components Components Components 16N575 Power Supply Unit 15 VDC used in 16M167 Power Supply Module 120369 Power Supply Unit 24 VDC used in 15V337 Advanced Web Interface Module 112443 Ground Terminal Block 255045 Clamp End Blocks 332356E 13 ...

Страница 14: ...WARRANTY WARRANTY WARRANTY AND AND AND DISCLAIMS DISCLAIMS DISCLAIMS ALL ALL ALL IMPLIED IMPLIED IMPLIED WARRANTIES WARRANTIES WARRANTIES OF OF OF MERCHANTABILITY MERCHANTABILITY MERCHANTABILITY AND AND AND FITNESS FITNESS FITNESS FOR FOR FOR A A A PARTICULAR PARTICULAR PARTICULAR PURPOSE PURPOSE PURPOSE IN IN IN CONNECTION CONNECTION CONNECTION WITH WITH WITH ACCESSORIES ACCESSORIES ACCESSORIES E...

Отзывы: