Wiring
1. Confirm the power is off prior to wiring. Follow all local and national electrical and building codes.
2. GPS recommends the GPS-FC24 be powered constantly and NOT switched with the system or blower.
3. The GPS-FC24-AC will self-adjust to voltages from 24VAC to 240VAC. Output and performance will not be
effected by the choice of input voltage. Connect the power wires as follows:
Black 24 - 240VAC
White Neutral or L2
Green Ground
Brown Dry Contacts/BAS Alarm
4. Wire in BAS terminals (optional) The GPS-FC24-AC is equipped with a set of dry contacts that are normally
open and close when the GPS-FC24-AC is on and has no faults. The contacts are rated up to 250VAC and 1A.
Operation
CAUTION!
NEVER TOUCH BRUSHES WHILE OPERATING, SHOCK MAY OCCUR
MISE EN GARDE!
NE JAMAIS TOUCHER AUX BROSSES PENDANT LE FONCTIONNEMENT, UN CHOC PEUT SE
PRODUIRE
Once powered and the inline switch is in the on position, the unit initiates an internal check of all systems. If the
auto cleaning wiper blade is not in the “home” position, it will move to the home position in series with the airflow.
Cleaning Cycle
The GPS-FC24-AC comes with a preset cleaning cycle designed to clean the brushes once per day. The cleaning
process may be activated by pushing the clean button located on the side of the unit. To change the cycle frequen-
cy, press the cleaning cycle button once. While cleaning is in progress press and hold the cleaning cycle button for 5
seconds. The LED will start flashing. Pressing the cleaning cycle button again will begin to cycle through the settings for
number of days between cleaning cycles. The speed of flashes increases with number of days (slowest = 1 day, next =
3days, next = 5 days, fastest = 10 days).
!
!