Thank you for purchasing a GPS-DM48-AC™ air ionization system from Global Plasma Solutions.

Hardware Provided by GPS

Before you start, confirm the contents of your shipment. Each GPS-DM48-AC will consist of the following:

1. GPS-DM48-AC with weather tight clear cover and black mounting flange (preinstalled).
2. Weathertight conduit (preinstalled on unit).
3. Self-tapping sheet screws (4).
4. Expanding anchors with screws (4).

Hardware Required by Others

1. Electrical wiring, junction box, or receptacle to provide power to the GPS-DM48-AC.
2. Sealant to make duct watertight after installation, if required.
3. 4-inch hole saw or snips.

Installation Location

CAUTION: MAKE SURE POWER IS DISCONNECTED TO THE HVAC EQUIPMENT BEFORE INSTALLATION

GPS recommends mounting the GPS-DM48-AC downstream of the last filter in the HVAC system. Alternate mounting 
locations are on the supply air duct or the return air duct after the filter. The duct must have a depth greater than 8 
inches for the unit to operate properly. The weatherproof housing will allow mounting indoors or out.

NOTE: Use Temperature - Maximum Ambient temperature in which unit shall be used: 140 degree F/ 60°C

Mechanical Installation

1. Ensure power to the HVAC equipment and the GPS-DM48-AC has been disconnected.
2. Find an appropriate location. Verify the 8-inch depth clearance for the GPS-DM48-AC.
3. Cut a 4-inch round hole in the duct.
4. Install the GPS-DM48-AC so that airflow is passing by both emitters at the same time (like a football through

goalposts). The conduit and connection grommet should be pointed down or to the side. Secure to the duct
with provided screws. Do not rely on the face of the display screen as a method of aligning the product to the
proper orientation.

Wiring

1. Confirm the power is off prior to wiring. Follow all local and national electrical and building codes.
2. GPS recommends the GPS-DM48 be powered constantly and NOT switched with the system or blower.
3. The GPS-DM48-AC will self-adjust to voltages from 24VAC to 240VAC. Output and performance will not be

affected by choice of input voltage. Connect the power wires as follows:

Black 24 - 240VAC 
White Neutral or L2
Green Ground
Brown Dry Contacts/BAS terminals

4. Wire in BAS terminals (optional). The GPS-DM48-AC is equipped with dry contacts that are normally open and

close when the GPS-DM48-AC is on and has no faults. The contacts are rated up to 250VAC and 1A.

!

Содержание DM48-AC

Страница 1: ...Installation Operation Maintenance Manual GPS DM48 AC NOTICE This product is to be used only as directed Read entire manual before use Do not use unless properly installed ...

Страница 2: ... out NOTE Use Temperature Maximum Ambient temperature in which unit shall be used 140 degree F 60 C Mechanical Installation 1 Ensure power to the HVAC equipment and the GPS DM48 AC has been disconnected 2 Find an appropriate location Verify the 8 inch depth clearance for the GPS DM48 AC 3 Cut a 4 inch round hole in the duct 4 Install the GPS DM48 AC so that airflow is passing by both emitters at t...

Страница 3: ... remove the clear faceplate by using a Phillips head screwdriver to remove the mounting screws Take care with the screws and gasket Change Cleaning Cycle Frequency Press the test button so the display reads CLEA Hold the test button down for 5 seconds until the current cleaning frequency is shown on the display Repeatedly press the test button until the desired cleaning frequency is shown The choi...

Страница 4: ...en screw Verify correct height after tightening screw 2 Wiper does not clean contact emitters a Adjust height of emitters loosen screw at base of emitter and gently push or pull emitter brush to a height where the wiper just contacts emitter brush Hold the emitter in place and tighten screw Verify correct height after tightening screw b If the emitter is worn to the point where there is no adjustm...

Страница 5: ... NC 28208 980 279 5622 2021 Global Plasma Solutions Inc To access a list of applicable patents please visit www gpspatents com ZERO OZONE EMISSIONS MEASURED OZONE EMISSIONS FROM GPS DM48 AC DURING USE PHASE DOES NOT EXCEED 0 005 PPM AS TESTED BY UL 867 UL COM ECV ...

Отзывы: