GMC-I Messtechnik GmbH
R2700–52
Replacing an R2600 Controller with an R2700 Controller
Replacement with regard to feature A
(A3) The continuous output is used for reading out the actual value and/or setpoint value. For R2700, feature A4 or A6 is to be selected.
* 0xxx may also be 1xxx, 2xxx, 3xxx;
4xxx may also be 5xxx, 6xxx, 7xxx;
8x4x may also be 9x4x, Ax4x, bx4x.
•
When configured as a step-action controller (R2600, features A2, A4), the configuration of the corresponding output is not Outx = CooL in the case of the R2700, but rather Outx = HcLo.
R2600
R2700
Feature
Heating Output Cooling Output
CnF1 *)
Feature Configuration
A1 (A3)
Transistor
—
0x2x
A1 (A4)
Out1 = HEAt
Out2 = oFF
A1 (A3)
Relay
—
0x2x
A3 (A6)
Out1 = oFF
Out2 = oFF
Out3 = HEAt Out4 = oFF
A1 (A3)
—
Transistor
0x3x
A1 (A4)
Out1 = CooL
Out2 = oFF
A1 (A3)
—
Relay
0x3x
A3 (A6)
Out1 = oFF
Out2 = oFF
Out3 = CooL
Out4 = oFF
A2, A4 (A3)
Transistor
Transistor
0x4x, 0x5x
A1 (A4)
Out1 = HEAt
Out2 = CooL
A2, A4 (A3)
Relay
Transistor
0x4x, 0x5x
A3 (A6)
Out1 = oFF
Out2 = CooL Out3 = HEAt
Out4 = oFF
A2, A4 (A3)
Transistor
Relay
0x4x, 0x5x
A3 (A6)
Out1 = HEAt
Out2 = oFF
Out3 = oFF
Out4 = Cool
A2, A4 (A3)
Relay
Relay
0x4x, 0x5x
A3 (A6)
Out1 = oFF
Out2 = oFF
Out3 = CooL
Out4 = HEAt
A3
Continuous
—
4x2x
A4
Out1 = oFF
Out2 = oFF
Cont = HEAt
A3
Continuous
Transistor
4x4x, 4x5x
A4
Out1 = oFF
Out2 = CooL Cont = HEAt
A3
Continuous
Relay
4x4x, 4x5x
A6
Out1 = oFF
Out2 = oFF
Out3 = oFF
Out4 = Cool
Cont = HEAt
A3
—
Continuous
4x3x
A4
Out1 = oFF
Out2 = oFF
Cont = CooL
A3
Transistor
Continuous
8x4x
A4
Out1 = HEAt
Out2 = oFF
Cont = CooL
A3
Relay
Continuous
8x4x
A6
Out1 = oFF
Out2 = oFF
Out3 = HEAt
Out4 = oFF
Cont = CooL