Measuring the Individual Parameters of an RCD
3.4.1
Touch Voltage Uc
The displayed touch voltage refers to nominal residual current. For
safety reasons, it is multiplied by the following coefficients:
➭
Select the
Uc
function with the
FUNC
key.
➭
The nominal value for residual current can be set with the
I
N
key.
➭
RCD type is selected with the
TYPE
key.
➭
The limit value for touch voltage
Uc
is adjusted with the
xI
N
key.
Figure 3.12: Example: Settings for Touch Voltage Measurement
➭
Connect the instrument to L and PE downstream from the
RCD as shown below. Example:
Figure 3.13: Connection Example
➭
After voltage value U
L-PE
settles in, briefly press the
START
key
to trigger the measurement.
After the measurement has been completed, the results are dis-
played as follows:
Figure 3.14: Results of a Touch Voltage Measurement
RL … fault loop impedance; R
L
= Uc*/
I
N
, where Uc* is actually
measured touch voltage, i.e. without a safety coefficient from the
table at the beginning of this section.
Note
The value for fault loop impedance appears at the display
if residual current
I
N
is set to
30 mA.
➭
Remove the test instrument from the RCD under test.
3.4.2
Time to Trip – TIME
The following table shows time to trip in accordance with the
EN 61008, EN 61009 and IEC 60364-4-41 standards:
* An RCD may not trip at
½
I
N
.
➭
Select the
TIME
function by pressing the
FUNC
key.
➭
The nominal value for residual current can be set with the
I
N
key.
➭
RCD type is selected with the
TYPE
key.
➭
Select a multiplier with the help of the
xI
N
key.
Figure 3.15: Example: Settings for Time to Trip Measurement
➭
Connect the instrument to L and PE downstream from the
RCD as shown in figure 3.13.
➭
After voltage value U
L-PE
settles in, briefly press the
START
key
to trigger the measurement.
After the measurement has been completed, the results are dis-
played as follows:
Uc (touch voltage) … touch voltage value
➭
Remove the test instrument from the RCD under test.
Comment:
Selective RCDs include a delay element which makes it
necessary to wait for a certain amount of time after each mea-
surement until the RCD is returned to its initial state. A 30 second
pause is therefore specified for the measurement of selective
RCDs, the progress of which appears at the display in the form of
a countdown timer which runs from 30 seconds to 1 second:
R C D t y p e
C o n t a c t v o l t a g e i s
p r o p o r t i o n a l t o :
1 , 0 5
I
N
1 , 0 5
2
I
N
1 , 0 5
2
I
N
1 , 0 5
2 x
2
I
N
½
I
N
*
I
N
2
I
N
5
I
N
Comment
Standard
—
300 ms
150 ms
40 ms
max. permissible
tripping current
Selective
—
500 ms
200 ms
150 ms
—
130 ms
60 ms
50 ms
min. permissible
tripping current
Figure 3.16: Results of the
Time to Trip Mea-
surement
Figure 3.17: Results when the
RCD is not
Tripped