LEDI 6 – LEDI 6/S
4 /8
EXISTING VERSIONS
Autonomous version
Built-in quartz time base: frequency 3.6864 MHz, stability ±0.2 s/24 hours between 20° and 25°C.
Minute impulse receiver, parallel connection
24 V reversed impulse every minute.
Impulse duration: 0.1 s.
Impulse consumption: 6 mA/24 V.
Half-minute impulse receiver, series connection
Series connection with external 39 ohm shunt.
Reversed impulse every half-minute.
Impulse duration: 0.1 s.
Impulse consumption: 1.25 V.
Current strength: 60-120 mA.
AFNOR NFS 87-500 code receiver
Nominal input level: 2.2 V DC.
Input impedance: 3.5 kOhms.
Minimum input voltage: 70 mV DC.
869 MHz Radio version
The clock synchronizes itself automatically following the emitting period of the emitter. Waiting the reception,
2 points between the hours and the minutes stay off until one reception was received. Then these points
have a second period blink except a 59th second off during 3 minutes.
2 - MOUNTING
Standard case
(cf. fig. 1 - fig. 2 - fig. 3)
- Prepare the wall support for attaching the bracket. Leave at least 60 mm between the top of the case and
the ceiling.
- Fix the bracket on the wall support using two 4 mm dia. screws.
- Hook the case over the bracket.
Flush-mounted case
(fig. 5)
- Prepare the wall support. LEDI 6: 335 x 151 x 75 mm.
LEDI6/S: 415 x 198 x 75 mm
- Position the support clip in the wall recess.
- Clip the clock on to its support.
Watertight case
(fig. 6 - fig. 7)
- Prepare and drill the wall support.
- Fix the “LEDI’s support” using three M5 screws
- Hang and clip the clock on to its support, taking care to bring out the wires at the top.
3 - CONNECTIONS (fig. 4)
- Connect the 230 V/50-60 Hz mains supply to the 3-conductor cable.
- Flip the battery switch
SW1 to the ON
(lower) position after connecting the clock.
N.B. If the hours and minutes remain unlit, wait a few minutes for the internal battery to be recharged.
3.1 - WATERTIGHT case
All connections are made at the back, without having to open the case. Cables should be connected as
shown by the identification marks.
7-conductor
cable
Ascii 232 version :RXD : Blue
Ascii 422/485 version :RX- / TX- : Blue
TXD : Pink
RX+ / TX+ : Pink
GND : Brown
GND : Brown
Impuls or AFNOR NFS87500 version : Green / Grey
Pip version : White/ yellow