Goodwe SECU-A Series Скачать руководство пользователя страница 7

Model

Battery Type

System Weight

Dimensions(W x D x H )

Protection

Installed Capacity

Usable Energy 

DOD

Nominal Voltage

Operating Voltage Range

Internal Resistance

Max. Charge current

Max. Discharge current

Operating Temperature Range

Humidity

Module Connect

Capacity Range

Usable Energy Range

Max. Charge Current

Max. Discharge Current

Monitoring Parameters

Communication

Certification

SECU-A5.4L

LiFePO

4

49kg

400x226.2x484.2mm

IP20 (indoor)

5.4 kWh

4.8 kWh

90%

51.2 V

48 ~ 57.6 V

≤ 20 mΩ

50 A 

50 A 

-10 °C ~ 50 °C [1]

15% ~ 85%

6 Parallels

5.4/10.8/16.2/21.6/27/32.4 kWh

4.8/9.6/14.4/19.2/24/28.8 kWh

50A (1 Module) / 100A (2~6 Modules)

50A (1 Module) / 100A (2~6 Modules)

system voltage, current, cell voltage, cell temperature, 
PCBA temperature

CAN

CE, UN38.3

7. Battery Parameters

Physical Parameters

Electrical Parameters

System Configuration

[1] When the temperature is below zero, the battery are not allowed to charge. When above 40

the power output decreased.

8. Safety Instructions

The system has been designed and tested under international safety requirements. However, to 
prevent personal injury and property damage and ensure long-term operation of the system, do 
read this section carefully and observe all safety information at all times.

Battery Module Leakage

If the battery modules leak electrolyte, please avoid contact the leaking liquid or gas. If one is 
exposed to the leaked substance, do these actions:

Inhalation: Evacuate the contaminated area, and seek for medical help immediately.

Eye contact: Rinse your eyes with clean water for at least 15 minutes and seek for medical help 
immediately.

Skin contact: Wash the affected area thoroughly with soap and clean water, and seek for medical 
help immediately.

Ingestion: Induce vomiting, and seek for medical help immediately.

Firefighting Measures

• In case of a fire, please make sure that a carbon dioxide extinguisher or Novac1230 or FM-200 is 

nearby. Water cannot be used to extinguish the fire. (ABC is not effective for this battery firefight-
ing)

• Full protective clothing and self-contained breathing apparatus are required for the firefighters to 

extinguish the fire.

Warning: Under >150

 environment, there is possibility that battery could explode

Handling and Storage Guide

• The battery modules and its components shall be protected from damage when it is in transporting 

and handling

• Please take the weight of the battery module system into account during transportation and battery 

module shall be lifted carefully

• Do not impact, pull, drag or step on the battery modules, either insert unrelated objects into any 

part of the battery modules

• The battery module shall be kept away from a fire, water, strong oxidizers or solvents

• The battery modules cannot be stored in high temperature (> 60

) or stored directly under the 

sun, or in any high humidity environment.

• Do not use the battery modules if it is defective, or appears cracked, broken.

• Do not attempt to open, disassemble, repair, tamper with, or modify the battery modules without 

official permission from GoodWe.

Warning: battery module damage may lead to electrolyte explosive air leakage, please 
contact technical support immediately.

10

09

Содержание SECU-A Series

Страница 1: ...PP LinkedIn Offical Website JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO LTD No 90 Zijin Rd New District Suzhou 215011 China www goodwe com service goodwe com SECU A Series User Manual Low Voltage Lithiu...

Страница 2: ...Connection 03 4 2 Communication Cable Connection 05 5 Battery Commissioning 06 5 1 Calibrating the DIP switch 06 5 2 Powering on the battery system 06 5 3 Setting the parameters of SECU A5 4L On PV Ma...

Страница 3: ...es work and are operated Knowledge of how an inverter works and is operated Knowledge of and adherence to the locally applicable connection requirements standards and directives the local standard for...

Страница 4: ...s on each inverter We just take SBP and ESA series inverter as example to introduce the connection in this manual 3 Product Overview 4 Cable Connection 4 1 Power Cable Connection LED Indicator Handle...

Страница 5: ...h DIP 2 3 Description To recognize the last battery connected to inverter To relize the communication between inverter and inverter unit part ON OFF Communication cable connection of SECU A5 4L with E...

Страница 6: ...S so that inverter will detect battery open circuit voltage to charge battery Select SECU A5 4L on battery page in PV Master Application Notes 1 Select wrong battery will lead to BMS communication fai...

Страница 7: ...diately Eye contact Rinse your eyes with clean water for at least 15 minutes and seek for medical help immediately Skin contact Wash the affected area thoroughly with soap and clean water and seek for...

Страница 8: ...ernal use is allowed GoodWe makes no representations or warranties express or implied with respect to this document or any of the equipment and or software it may describe including with no limitation...

Отзывы: