4 www.goodmanmfg.com
SS-GSCC
GSC10 C
ommerCial
p
roduCt
S
peCifiCationS
GSC10
0903A*
GSC10
0904AC
GSC10
1203A*
GSC10
1203B*
GSC10
1204B*
Cooling Capacities
Nominal Cooling (BTU/h)
87,000
87,000
109,000
114,000
109,000
EER/IEER
11.2/11.5
11.2/11.5
11.2/---
11.2/11.2
11.2/11.2
Decibels
84
84
84
84
84
Compressor
RLA / LRA
25.6 / 196
12.8 / 100
30.1 / 225
30.1 / 225
15.5/ 114
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Condenser Fan Motor
Horsepower
1
1
1
1
1
FLA
5.6
3.5
5.6
5.6
3.5
Refrigeration System
Liquid Valve Size (“O.D.)
⅝"
⅝"
⅝"
⅝"
⅝"
Suction Valve Size (“O.D.) (7½ tons)
1⅜"
1⅜"
1⅜"
1⅜"
1⅜"
Suction Valve Size (“O.D.) (10 tons)
1⅝"
1⅝"
1⅝"
1⅝"
1⅝"
Refrigerant Charge
35
35
35
35
35
Valve Type
Sweat
Sweat
Sweat
Sweat
Sweat
Electrical Data
AC Volts/ Hz
208-230/ 60
460/ 60
208-230/ 60
460/ 60
Min. Circuit Ampacity ¹
37.6
19.5
43.2
43.2
22.9
Max. Overcurrent Device ²
60
30
70
70
35
Min / Max Volts
197/253
414/ 506
197/253
197/253
414/ 506
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Ship Weight (lbs)
315
315
334
334
334
¹ Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
³ Installer will need to supply ¾” to ⅞” adapters for suction line connections.
4
Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.