Page 7.1

SECTION 7

TroubleShooting

7

SYMPTOM:

 The air conditioning does not attempt to 

          turn on.

CAUSE:

 The compressor timer lockout may prevent the 

          air conditioner from turning on for a period of time.

REMEDY:

 Consult the Owner's Manual in the Setup 

          section to defeat the cycles per hour and 
          compressor timeguard.

SYMPTOM:

 The display is blank.

CAUSE:

 Lack of proper power.

REMEDY:

 Make sure power is turned on to the furnace 

          and that you have 24vac between 

R

 & 

and 

          24vac between 

C

.

SYMPTOM:

 The air conditioning does not attempt to 

          turn on.

CAUSE:

 The cooling setpoint is set too high.

REMEDY:

 Consult the Owner's Manual in the Setup 

          section to lower the cooling setpoint limit.

SYMPTOM:

 The heating does not attempt to turn on.

CAUSE:

 The heating setpoint is set too low.

REMEDY:

 Consult the Owner's Manual in the Setup 

          section to raise the heating setpoint limit.

Air  Conditionin

g

  &  Heatin

g

AU

TO

I2:0

0

Pm

HE

AT

CO

OL

72

74

AU

TO

I2:0

0

Pm

HE

AT

CO

OL

72

74

AU

TO

I2:0

0

Pm

HE

AT

CO

OL

72

74

AU

TO

I2:0

0

Pm

HE

AT

CO

OL

72

74

Содержание TSTATG2111

Страница 1: ...ng up to 2 Heat 1 Cool up to 2 Heat 1 Cool CONFIGURABLE IN SETUP Auto or Manual changeover Programmable or Non Programmable Aux Heat Indicator Outdoor Sensor Ready with High Low Readouts for the Day A...

Страница 2: ...ce must accept any interference received including interference that may cause undesired operation Follow the Installation Instructions before proceeding Set the thermostat mode to OFF prior to changi...

Страница 3: ...4 5 Preparation Remove Replace the Old Thermostat Sample Wiring Diagrams Calibrating the Thermostat Sensors Test Operation TroubleShooting Page iii Table of Contents Wire Connections Air Conditioning...

Страница 4: ...ng Air Conditioning system at the main fuse panel Most residential systems have a separate breaker for disconnecting power to the furnace Proper installation of the thermostat will be accomplished by...

Страница 5: ...eep the old thermostat for reference purposes until your new thermostat is functioning properly Disconnect the wires from the old thermostat Tape the ends of the wires as you disconnect them and mark...

Страница 6: ...structions on connecting these terminals see page 4 6 Wire from the old thermostat terminal marked Function Install on the new thermostat connector marked G or F Fan G Y1 Y or C Cooling Y1 W1 W or H H...

Страница 7: ...Page 4 1 Section 4 Contents HVAC Equipment Wiring 4 2 Installing the Outdoor Sensor 4 6 SECTION 4 Sample Wiring Diagrams 4 Air Conditioning Heating...

Страница 8: ...return fan relay compressor relay 1st stage heat circuit W1 W2 G R C Y1 5 Wire 1 Stage Cooling 1 Stage Heat 24 vac common 2nd stage heat circuit HP GAS B O ELEC GAS FAN Residential Commercial 1 Stage...

Страница 9: ...tial Commercial 1 Stage Cooling with 1st stage Electric Heat 5 Wire 1 Stage Cooling 1 Stage Electric Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay 1st stage heat circuit W1 G R...

Страница 10: ...with O Reversing Valve 1 Stage Cooling with 2 stage Heat 6 Wire 1 Stage Cooling 2 Stage Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay Reversing Valve O W2 G R C Y1 24 vac comm...

Страница 11: ...Pump with b Reversing Valve 1 Stage Cooling with 2 stage Heat 6 Wire 1 Stage Cooling 2 Stage Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay Reversing Valve b W2 G R C Y1 24 vac...

Страница 12: ...This is an unshielded cable with four twisted pairs of 24 gauge solid wire DO NOT use stranded cable The cable length should not exceed 250 feet If less than 75 feet of cable is required to connect t...

Страница 13: ...re The air conditioner should turn on Press the UP Turn the power on to the Heating Air Conditioning system Press the UP button until the setpoint is equal to the room temperature Press the FAN button...

Страница 14: ...rocedure MODE Place the thermostat in the OFF mode MODE Press button While holding the MODE button press and hold the FAN button for 5 seconds All icons will appear on the display and hold the MODE CA...

Страница 15: ...d on to the furnace and that you have 24vac between R W and 24vac between R C SYMPTOM The air conditioning does not attempt to turn on CAUSE The cooling setpoint is set too high REMEDY Consult the Own...

Страница 16: ...set for b REMEDY Set the reversing valve jumper for O See pages 4 4 and 4 5 SYMPTOM When calling for cooling both the heat and cool come on CAUSE The thermostat equipment jumper is configured for HP a...

Отзывы: