SECTION 6

Calibrating the Thermostat Sensors

6

Calibrating the Temperature and Humidity Sensors

After calibration is complete, press the MODE button

 once 

to return to 

normal operation.

Under  normal  circumstances  it  will  not  be  necessary  to  adjust  the 
calibration of the temperature and humidity sensors.  If calibration is 
required,  please  contact  a  trained  HVAC  technician  to  correctly 
perform the following procedure.  

MODE

Place the thermostat in the 
OFF mode.

MODE

Press 
button.    While  holding  the
MODE button, press and hold 
the FAN button for 5 seconds.
All  icons  will  appear  on  the
display.

and  hold  the  MODE

CALIBRATE

PRESS

TWICE

Press the UP and 

buttons 

at  the  same  time  twice.

The 

thermostat  temperature  will  be 
displayed  and  may  be  calibrated 
using the UP or DOWN buttons.

DOWN 

   

THERMOSTAT SENSOR

Evening

FanOn

     A

UX

H

EAT

C

OOL

AUTO

OFFON

Morning

DayNight

SuMoTuWeThFrSa

Service Filter
Pan UV Light 

Program On

StartStop

DeHumidify

Setup

Outside

Vacation

L

O

H

I

     188

88

88

18:88

Am

Pm

OFF

Pm

72

12:00

72

FAN

Air  Conditionin

g

  &  Heatin

g

Содержание TSTATG2111

Страница 1: ...ng up to 2 Heat 1 Cool up to 2 Heat 1 Cool CONFIGURABLE IN SETUP Auto or Manual changeover Programmable or Non Programmable Aux Heat Indicator Outdoor Sensor Ready with High Low Readouts for the Day A...

Страница 2: ...ce must accept any interference received including interference that may cause undesired operation Follow the Installation Instructions before proceeding Set the thermostat mode to OFF prior to changi...

Страница 3: ...4 5 Preparation Remove Replace the Old Thermostat Sample Wiring Diagrams Calibrating the Thermostat Sensors Test Operation TroubleShooting Page iii Table of Contents Wire Connections Air Conditioning...

Страница 4: ...ng Air Conditioning system at the main fuse panel Most residential systems have a separate breaker for disconnecting power to the furnace Proper installation of the thermostat will be accomplished by...

Страница 5: ...eep the old thermostat for reference purposes until your new thermostat is functioning properly Disconnect the wires from the old thermostat Tape the ends of the wires as you disconnect them and mark...

Страница 6: ...structions on connecting these terminals see page 4 6 Wire from the old thermostat terminal marked Function Install on the new thermostat connector marked G or F Fan G Y1 Y or C Cooling Y1 W1 W or H H...

Страница 7: ...Page 4 1 Section 4 Contents HVAC Equipment Wiring 4 2 Installing the Outdoor Sensor 4 6 SECTION 4 Sample Wiring Diagrams 4 Air Conditioning Heating...

Страница 8: ...return fan relay compressor relay 1st stage heat circuit W1 W2 G R C Y1 5 Wire 1 Stage Cooling 1 Stage Heat 24 vac common 2nd stage heat circuit HP GAS B O ELEC GAS FAN Residential Commercial 1 Stage...

Страница 9: ...tial Commercial 1 Stage Cooling with 1st stage Electric Heat 5 Wire 1 Stage Cooling 1 Stage Electric Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay 1st stage heat circuit W1 G R...

Страница 10: ...with O Reversing Valve 1 Stage Cooling with 2 stage Heat 6 Wire 1 Stage Cooling 2 Stage Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay Reversing Valve O W2 G R C Y1 24 vac comm...

Страница 11: ...Pump with b Reversing Valve 1 Stage Cooling with 2 stage Heat 6 Wire 1 Stage Cooling 2 Stage Heat HP GAS B O ELEC GAS FAN 24 vac return fan relay compressor relay Reversing Valve b W2 G R C Y1 24 vac...

Страница 12: ...This is an unshielded cable with four twisted pairs of 24 gauge solid wire DO NOT use stranded cable The cable length should not exceed 250 feet If less than 75 feet of cable is required to connect t...

Страница 13: ...re The air conditioner should turn on Press the UP Turn the power on to the Heating Air Conditioning system Press the UP button until the setpoint is equal to the room temperature Press the FAN button...

Страница 14: ...rocedure MODE Place the thermostat in the OFF mode MODE Press button While holding the MODE button press and hold the FAN button for 5 seconds All icons will appear on the display and hold the MODE CA...

Страница 15: ...d on to the furnace and that you have 24vac between R W and 24vac between R C SYMPTOM The air conditioning does not attempt to turn on CAUSE The cooling setpoint is set too high REMEDY Consult the Own...

Страница 16: ...set for b REMEDY Set the reversing valve jumper for O See pages 4 4 and 4 5 SYMPTOM When calling for cooling both the heat and cool come on CAUSE The thermostat equipment jumper is configured for HP a...

Отзывы: