25
HEATING SPECIFICATIONS
*To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU)
capacity
btuh
c.o.p.
4.8
9.6
14.4
19.2
65
30.17
4.93
46.55
62.93
79.32
95.70
60
28.56
4.76
44.94
61.32
77.71
94.09
55
26.88
4.57
43.26
59.64
76.03
92.41
50
25.13
4.37
41.51
57.89
74.28
90.66
45
23.26
4.13
39.64
56.02
72.40
88.79
40
21.60
3.91
37.98
54.36
70.75
87.13
35
19.92
3.69
36.30
52.68
69.07
85.45
30
18.69
3.26
35.07
51.45
67.84
84.22
25
17.25
3.08
33.63
50.01
66.40
82.78
20
15.89
2.91
32.27
48.65
65.03
81.41
15
14.45
2.71
30.83
47.21
63.59
79.97
10
12.96
2.49
29.34
45.72
62.11
78.49
5
11.49
2.27
27.87
44.25
60.64
77.02
0
10.02
2.03
26.40
42.78
59.17
75.55
-5
8.55
1.78
24.93
41.31
57.70
74.08
-10
7.01
1.50
23.39
39.77
56.15
72.53
Outdoor
Ambient
°F.
SSZ160241A* / CA*F3636*6A*+TXV/ MBE1600**-1
Conditions: 875 CFM @ 70°F Indoor Air
Capacity of Unit
With KW of Auxiliary heat
Basic Unit without
Auxiliary Heat
capacity
btuh
c.o.p.
4.8
9.6
14.4
19.2
65
59.08
4.68
75.46
91.84
108.23
124.61
60
55.93
4.52
72.31
88.69
105.08
121.46
55
52.64
4.35
69.02
85.40
101.79
118.17
50
49.21
4.15
65.59
81.97
98.36
114.74
45
45.54
3.93
61.93
78.31
94.69
111.07
40
42.30
3.72
58.68
75.06
91.45
107.83
35
39.01
3.51
55.39
71.77
88.16
104.54
30
35.37
3.30
51.75
68.13
84.52
100.90
25
32.64
3.12
49.03
65.41
81.79
98.17
20
30.06
2.94
46.44
62.83
79.21
95.59
15
27.34
2.74
43.72
60.10
76.48
92.87
10
24.53
2.52
40.91
57.29
73.67
90.06
5
21.74
2.29
38.13
54.51
70.89
87.27
0
18.96
2.05
35.34
51.73
68.11
84.49
-5
16.18
1.80
32.56
48.94
65.33
81.71
-10
13.26
1.51
29.64
46.02
62.40
78.79
Outdoor
Ambient
°F.
Basic Unit without
Auxiliary Heat
SSZ160481A* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 1550 CFM @ 70°F Indoor Air
Capacity of Unit
With KW of Auxiliary heat
capacity
btuh
c.o.p.
4.8
9.6
14.4
19.2
65
71.65
4.44
88.03 104.41 120.80
137.18
60
67.83
4.29
84.21 100.59 116.98
133.36
55
63.84
4.12
80.22
96.60
112.99
129.37
50
59.68
3.94
76.06
92.44
108.83
125.21
45
55.23
3.73
71.62
88.00
104.38
120.76
40
51.30
3.54
67.68
84.06
100.45
116.83
35
47.31
3.34
63.69
80.07
96.46
112.84
30
44.86
3.08
61.24
77.62
94.00
110.39
25
41.40
2.91
57.78
74.16
90.55
106.93
20
38.12
2.75
54.51
70.89
87.27
103.65
15
34.67
2.56
51.05
67.43
83.82
100.20
10
31.10
2.36
47.49
63.87
80.25
96.63
5
27.58
2.15
43.96
60.34
76.72
93.11
0
24.05
1.92
40.43
56.81
73.20
89.58
-5
20.52
1.69
36.90
53.28
69.67
86.05
-10
16.81
1.42
33.19
49.58
65.96
82.34
SSZ160601A* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions:1800 CFM @ 70°F Indoor Air
C a p ac it y o f U ni t
W i t h KW o f A ux il i a r y heat
O ut d o o r
A mb i ent
°F .
B as ic U ni t w i t ho ut
A ux i li a r y Hea t
capacity
btuh
c.o.p.
4.8
9.6
14.4
19.2
65
43.24
4.68
59.62
76.01
92.39
108.77
60
40.94
4.52
57.32
73.70
90.08
106.47
55
38.53
4.35
54.91
71.29
87.68
104.06
50
36.02
4.15
52.40
68.78
85.16
101.55
45
33.33
3.93
49.72
66.10
82.48
98.86
40
30.96
3.73
47.34
63.72
80.11
96.49
35
28.55
3.52
44.93
61.32
77.70
94.08
30
26.17
3.12
42.55
58.93
75.31
91.70
25
24.15
2.95
40.53
56.91
73.30
89.68
20
22.24
2.78
38.62
55.00
71.39
87.77
15
20.22
2.59
36.61
52.99
69.37
85.75
10
18.14
2.39
34.53
50.91
67.29
83.67
5
16.09
2.17
32.47
48.85
65.23
81.62
0
14.03
1.95
30.41
46.79
63.18
79.56
-5
11.97
1.71
28.35
44.73
61.12
77.50
-10
9.81
1.44
26.19
42.57
58.95
75.34
SSZ160361A* / CA*F4860*6A*+TXV/ MBE2000**-1
Conditions: 1200 CFM @ 70°F Indoor Air
Capacity of Unit
With KW of Auxiliary heat
Basic Unit without
Auxiliary Heat
Outdoor
Ambient
°F.