SPLIT SYSTEM HEATING PERFORMANCE
SSZ160601B*
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
Liq
Suct
65
276
56
284
65
293
73
301
82
310
91
319
99
328
108
336
116
345 125
354
134 363 142
70
296
56
305
65
313
73
322
82
331
90
339
99
348
107
357
116
365 125
374
133 383 142
75
317
56
326
64
335
73
344
81
352
90
361
99
370
107
378
116
387 124
395
133 404 141
65
266
56
275
64
283
73
291
81
300
90
308
98
316
107
325
115
333 124
342
132 350 141
70
286
56
294
65
303
73
311
82
320
90
328
99
336
107 345 116
353
124
361 133
370
141
75
307
56
315
65
324
74
332
82
340
91
349
99
357
108
365
116
374 125
382
133 390 142
65
260
56
268
64
276
73
284
81
292
90
300
98
309
107
317
115
325 124
333
132 342 141
70
279
56
287
64
295
73
303
82
312
90
320
99
328
107
336
116
344 124
352
133 361 141
75
299
56
307
65
316
73
324
82
332
91
340
99
348
108
356
116
364 125
372
133 380 142
65
283
56
290
63
296
70
302
78
308
85
314
92
321 100 327 107
333 114
340 122 346 129
70
304
55
310
63
317
70
323
77
329
85
335
92
341
99
347
107
353 114
359
121 365 129
75
326
55
332
63
338
70
344
77
350
84
356
92
362
99
368
106
374 114
380
121 385 128
65
274
55
280
62
286
70
292
77
298
84
304
91
310
99
316
106
322 113
328
121 334 128
70
294
56
300
63
306
70
312
77
318
85
323
92
329
99
335
106
341 114
347 121 353 128
75
315
56
321
63
327
70
333
78
338
85
344
92
350
100
355
107
361 114
367 121 372 129
65
267
55
273
62
279
70
284
77
290
84
296
91
302
99
308
106
314 113
320
120 326 128
70
287
55
292
63
298
70
304
77
310
84
315
92
321
99
327
106
333 114
338
121 344 128
75
307
56
313
63
319
70
324
78
330
85
335
92
341
99
347
107
352 114
358
121 363 129
Label p/n: 0140R00181-A
1050
Lo
w S
ta
g
e
Outdoor Air Dry Bulb Tem perature (ºF)
Liquid Valve & Compre ssor Suction Pressure
1350
17
27
37
1580
1800
2030
1200
HEATING MODE PRESSURE CHART
42
47
57
67
Indoor Return
Air Dry Bulb
Temperature
(ºF)
Hi
g
h
S
ta
g
e
Pressures show n are for most popular match indoor unit WITH NO FROST ON OUTDOOR COIL. Due to factors like airflow , charge, indoor coil & frost, pressures w ill vary
significantly. Liquid (small) service valve pressures should be ± 20 psig & suction (access port) pressures should be ±5 psig of the values listed in this chart.
62
52
22
32
Indoor
Air Flow
Rate
EXPANDED PERFORMANCE DATA
MODEL: SSZ160601B* CAPF4961D6 MBVC2000A - LOW STAGE
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
49.9
47.3
44.5
41.6
39.7
38.5
35.8
33.0
30.8
28.4
26.2
24.7
23.8
21.3
18.9
16.5
14.1
11.5
T/R
40.2
38.1
35.8
33.5
32.0
31.0
28.8
26.5
24.8
22.9
21.1
19.9
19.2
17.2
15.2
13.3
11.3
9.3
KW
3.51
3.44
3.36
3.29
3.25
3.22
3.15
3.08
3.47
3.38
3.30
3.25
3.22
3.13
3.05
2.96
2.88
2.79
AMPS
18.3
16.9
15.9
14.9
14.4
14.1
13.3
12.7
12.1
11.6
11.1
10.8
10.7
10.1
9.5
8.9
8.3
7.5
COP
4.17
4.03
3.87
3.70
3.58
3.50
3.32
3.14
2.60
2.46
2.32
2.22
2.16
2.00
1.82
1.63
1.43
1.21
EER
14.2
13.8
13.2
12.6
12.2
12.0
11.4
10.7
8.9
8.4
7.9
7.6
7.4
6.8
6.2
5.6
4.9
4.1
EXPANDED PERFORMANCE DATA
MODEL: SSZ160601B* CAPF4961D6 MBVC2000A - HIGH STAGE
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
71.0
67.2
63.3
59.2
56.5
54.7
50.9
46.9
44.6
41.2
37.9
35.8
34.5
30.9
27.4
23.9
20.4
16.7
T/R
37.6
35.6
33.5
31.3
29.9
29.0
26.9
24.8
23.6
21.8
20.1
18.9
18.2
16.4
14.5
12.7
10.8
8.8
KW
4.67
4.58
4.49
4.40
4.34
4.30
4.22
4.12
4.62
4.51
4.41
4.34
4.30
4.19
4.08
3.98
3.87
3.76
AMPS
22.9
21.2
19.9
18.7
18.0
17.7
16.6
15.8
15.1
14.4
13.7
13.4
13.2
12.6
11.7
11.0
10.2
9.2
COP
4.45
4.30
4.13
3.94
3.81
3.72
3.53
3.33
2.82
2.67
2.52
2.41
2.35
2.16
1.97
1.76
1.54
1.30
EER
15.2
14.7
14.1
13.5
13.0
12.7
12.1
11.4
9.6
9.1
8.6
8.2
8.0
7.4
6.7
6.0
5.3
4.4
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
AMPS = Outdoor unit amps (comp.+fan)
*Note: Shaded area is AHRI Rating Conditions at 47°F outdoor ambient temperature
KW = Total system power