background image

6

IO-101G

06/04

SPECIAL NOTE: Systems with MORE than 15’ of
interconnecting tubing, please refer to Table 5 for line
charge allowance per foot of tubing.

LINE

LIQUID

SUCTION

O. D. (IN)

LINE

LINE

1/4

0.22

3/8

0.58

1/2

1.14

5/8

1.86

0.04

3/4

0.06

7/8

0.08

1 1/8

0.15

1 3/8

0.22

LINE CHARGE ALLOWANCE (R-22) (oz./ft.)

TABLE 5

NOTE:  System with over 50’ separation between
condensing unit and evaporator may require oil charge
adjustment.

1 - 1 1/2

2 - 5

UNIT MODEL 

(TONS)

0.5

ADDITIONAL OIL CHARGE PER EACH

ADDITIONAL 10' OF LINE (OZ.)*

0.25

OIL CHARGE ADJUSTMENT

*Use either Texaco WF-32 (formerly cappella B)

or Suniso 3G-S oil

TABLE 6

Содержание Split System Condensing Units IO-101G

Страница 1: ...STEM CONDENSING UNITS All information contained herein is subject to change without notice Goodman Manufacturing Company L P I0 101G 2550 North Loop West Suite 400 Houston TX 77092 06 04 www goodmanmfg com 2003 2004 Goodman Manufacturing Company L P ...

Страница 2: ...ncorrect unit is shipped it must be returned to the supplier and must NOT be installed The manufacturer assumes no responsibility for installation of incorrectly shipped units REPLACEMENT PARTS Order all replacement parts through your local distributor When ordering parts give complete model and serial number as shown on the unit s rating plate Replacement parts for this appliance are available th...

Страница 3: ...d above the air handler the maximum lift should not exceed 70 suction line If air handler is mounted above condensing unit the lift should not exceed 50 liquid line Refer to Figure 3 and Table 1 for maximum refrigerant line lenghts PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1 2 FOR EVERY 10 OF LINE INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT INDOOR UNIT LIQUID LINE OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT...

Страница 4: ...TO BE MADE Field Connection to the Valve and Valve Opening 1 Tubing should be cut square Make sure it is round and free of burrs at the connecting ends Clean the tubing to prevent contaminants from entering the system 2 Wrap a wet rag around the copper valve stub before brazing 3 Braze or silver solder the joint 4 After brazing quench with a wet rag to cool the joint Evacuate and charge the connec...

Страница 5: ...superheat Add charge to lower superheat Remove charge to raise superheat 5 Remove gauge lines carefully WARNING ESCAPING LIQUID REFRIGERANT CAN CAUSE BURNS AMBIENT CONDENSER INLET TEMPERATURE F DRYBULB 65 70 75 80 85 100 5 5 95 5 5 5 90 7 12 18 85 5 10 17 20 80 5 12 21 26 75 5 10 17 25 29 70 5 14 20 28 32 65 13 19 26 32 35 60 17 25 30 33 37 RETURN AIR TEMPERATURE F DRYBULB SYSTEM SUPERHEAT TABLE 2...

Страница 6: ... 58 1 2 1 14 5 8 1 86 0 04 3 4 0 06 7 8 0 08 1 1 8 0 15 1 3 8 0 22 LINE CHARGE ALLOWANCE R 22 oz ft TABLE 5 NOTE System with over 50 separation between condensing unit and evaporator may require oil charge adjustment 1 1 1 2 2 5 UNIT MODEL TONS 0 5 ADDITIONAL OIL CHARGE PER EACH ADDITIONAL 10 OF LINE OZ 0 25 OIL CHARGE ADJUSTMENT Use either Texaco WF 32 formerly cappella B or Suniso 3G S oil TABLE...

Страница 7: ...F COOL COIL FAN RELAY COIL C CH THERMOSTAT FAN SWITCH HP 3 COMP 2 C T3 L3 C T2 L2 MOTOR AUTO ON G CONTACTOR 1 CAP C T1 L1 OUTDOOR POWER SUPPLY Y LINE SPLICE WIRE NUT C T1 L1 BL V V LOW VOLTAGE BK ANTICIPATOR THERMOSTAT BULB THERMOSTAT ADJ HEAT THERMOSTAT ANTICIPATOR HIGH VOLTAGE LOW VOLTAGE OPTIONAL START ASSIST WIRE NUT REPLACEMENT WIRE MUST BE SAME GAGE AND INSULATION THICKNESS 105 C APPLIANCE W...

Страница 8: ... units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www goodmanmfg com for information on Goodman products Warranties Customer Services Parts Contractor Prog...

Отзывы: