background image

5

IO-101G

06/04

The recommended procedure for processing and charge
adjustment is as follows:
1.

Connect vacuum pump to both base valve service
ports.

2.

Evacuate tubing and evaporator through liquid and
suction base valve ports, to 500 microns or less for a
minimum of 30 minutes.  Close valve to pump and
wait 15 minutes.  Vacuum should not rise above 800
microns. If unable to obtain 500 micorns, or vacuum
rises above 800 microns over a 15 minute period,
discontinue evacuation, pressurize and check for
leaks.  Repair any leaks found and repeat step 2.

3.

Close valve to vacuum pump and stop pump.  Break
vacuum by opening liquid and suction base valves.
Fully open base valves and remove pump lines.
Connect service gauges making sure lines are purged.

4.

Set thermostat system switch to “COOL” and
temperature to highest setting.  Close all disconnects.

5.

Set thermostat to call for cooling.  Check for operation
of indoor and outdoor fans.  Allow for at least 10
minutes.

6.

Check charge and adjust if necessary.  Refer to
appropriate “Check Charge” section.

Charge Checks
Capillary Tube/Fixed Orifice System

1.

Fully open both base valves.

2.

Connect service gauge manifold to base-valve service
ports being sure to purge lines.  Run system at least
10 minutes to allow pressure to stabilize.

3.

Temporarily install thermometer on suction (large) line
near condensing unit.  Be sure of good contact
between the thermometer and line.  Wrap thermometer
with insulating material to assure accurate reading.

4.

Refer to Table 2 for proper system superheat.  Add
charge to lower superheat.  Remove charge to raise
superheat.

5.

Remove gauge lines carefully.

WARNING

ESCAPING LIQUID REFRIGERANT CAN CAUSE
BURNS.

AMBIENT CONDENSER

INLET TEMPERATURE

°F DRYBULB

65

70

75

80

85

100

5

5

95

5

5

5

90

7

12

18

85

5

10

17

20

80

5

12

21

26

75

5

10

17

25

29

70

5

14

20

28

32

65

13

19

26

32

35

60

17

25

30

33

37

RETURN AIR TEMPERATURE

( °F DRYBULB)

SYSTEM SUPERHEAT

TABLE 2

Superheat Determination

1.

Read suction pressure.  Using Table 3, determine
saturated suction temperature.

2.

Read suction line temperature.

3.

Use the following formula to determine superheat:

Superheat = Suction Line Temp. - Saturated Suction Temp.

SUCTION

SATURATED SUCTION

PRESSURE PSIG

TEMPERATURE °F

50

26

53

28

55

30

58

32

61

34

63

36

66

38

69

40

72

42

75

44

78

46

81

48

SATURATED SUCTION PRESSURE (R-22)

TABLE 3

Expansion Valve System

1.

Fully open both base valves.

2.

Connect service gauge manifold to base-valve service
parts making sure lines are purged.  Run system at
least 10 minutes to allow pressure to stabalize.

3.

Temporarily install the thermometer to liquid (small)
line near condensing unit.  Be sure that the contact
between thermometer and line is good.  Wrap
thermometer with insulating material to ensure
accurate reading.

4.

Referring to Table 4, adjust charge to obtain a
temperature 12-15°F below the saturated liquid
temperature.

Example:
If the Liquid Pressure is 260 PSIG then the Saturated
Temperature will be 120

°

F.   Adjust the Saturated

Temperature by subtracting 12-15

°

F.  This will give you a

Liquid Line Temperature of 105

°

 - 108

°

F.

LIQUID PRESSURE

SATURATED 

(PSIG)

TEMPERATURE °F

200

102

210

105

220

108

230

111

240

114

250

117

260

120

270

123

280

126

290

128

300

131

SATURATED LIQUID TEMPERATURE

TABLE 4

Содержание Split System Condensing Units IO-101G

Страница 1: ...STEM CONDENSING UNITS All information contained herein is subject to change without notice Goodman Manufacturing Company L P I0 101G 2550 North Loop West Suite 400 Houston TX 77092 06 04 www goodmanmfg com 2003 2004 Goodman Manufacturing Company L P ...

Страница 2: ...ncorrect unit is shipped it must be returned to the supplier and must NOT be installed The manufacturer assumes no responsibility for installation of incorrectly shipped units REPLACEMENT PARTS Order all replacement parts through your local distributor When ordering parts give complete model and serial number as shown on the unit s rating plate Replacement parts for this appliance are available th...

Страница 3: ...d above the air handler the maximum lift should not exceed 70 suction line If air handler is mounted above condensing unit the lift should not exceed 50 liquid line Refer to Figure 3 and Table 1 for maximum refrigerant line lenghts PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1 2 FOR EVERY 10 OF LINE INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT INDOOR UNIT LIQUID LINE OUTDOOR UNIT OUTDOOR UNIT INDOOR UNIT...

Страница 4: ...TO BE MADE Field Connection to the Valve and Valve Opening 1 Tubing should be cut square Make sure it is round and free of burrs at the connecting ends Clean the tubing to prevent contaminants from entering the system 2 Wrap a wet rag around the copper valve stub before brazing 3 Braze or silver solder the joint 4 After brazing quench with a wet rag to cool the joint Evacuate and charge the connec...

Страница 5: ...superheat Add charge to lower superheat Remove charge to raise superheat 5 Remove gauge lines carefully WARNING ESCAPING LIQUID REFRIGERANT CAN CAUSE BURNS AMBIENT CONDENSER INLET TEMPERATURE F DRYBULB 65 70 75 80 85 100 5 5 95 5 5 5 90 7 12 18 85 5 10 17 20 80 5 12 21 26 75 5 10 17 25 29 70 5 14 20 28 32 65 13 19 26 32 35 60 17 25 30 33 37 RETURN AIR TEMPERATURE F DRYBULB SYSTEM SUPERHEAT TABLE 2...

Страница 6: ... 58 1 2 1 14 5 8 1 86 0 04 3 4 0 06 7 8 0 08 1 1 8 0 15 1 3 8 0 22 LINE CHARGE ALLOWANCE R 22 oz ft TABLE 5 NOTE System with over 50 separation between condensing unit and evaporator may require oil charge adjustment 1 1 1 2 2 5 UNIT MODEL TONS 0 5 ADDITIONAL OIL CHARGE PER EACH ADDITIONAL 10 OF LINE OZ 0 25 OIL CHARGE ADJUSTMENT Use either Texaco WF 32 formerly cappella B or Suniso 3G S oil TABLE...

Страница 7: ...F COOL COIL FAN RELAY COIL C CH THERMOSTAT FAN SWITCH HP 3 COMP 2 C T3 L3 C T2 L2 MOTOR AUTO ON G CONTACTOR 1 CAP C T1 L1 OUTDOOR POWER SUPPLY Y LINE SPLICE WIRE NUT C T1 L1 BL V V LOW VOLTAGE BK ANTICIPATOR THERMOSTAT BULB THERMOSTAT ADJ HEAT THERMOSTAT ANTICIPATOR HIGH VOLTAGE LOW VOLTAGE OPTIONAL START ASSIST WIRE NUT REPLACEMENT WIRE MUST BE SAME GAGE AND INSULATION THICKNESS 105 C APPLIANCE W...

Страница 8: ... units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www goodmanmfg com for information on Goodman products Warranties Customer Services Parts Contractor Prog...

Отзывы: