18
AIRFLOW LABEL
0140A00706-A
Airflow Settings Instructions
1) For non-communicating installations, select the type of unit installed
in the OdS menu (1AC = single-stage air conditioner,
1HP = single-stage heat pump, 2AC = 2 stage air conditioner,
2HP = 2 stage heat pump) Default = OFF (no outdoor unit).
2) Use the Tonnage Menu (ton) to select Cooling/Heat Pump Airflow
(non-communicating installation). Tonnage selection options and
corresponding airflow CFM can be found to the right.
[Airflow = Tonnage Selection x 400] Default selection is 6.0 tons.
3) [Optional] Use the Cooling Trim Menu (CtF) to adjust the cooling
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units. For inverter outdoor units use
Cooling Trim Factor High, Intermediate and Low menus (CtH, CtI,
and CtL) for trim adjustment.
4) [Optional] Use the Heating Trim Menu (HtF to adjust the heat pump
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units. For inverter outdoor units use
Heating Trim Factor High, Intermediate and Low menus (HtH, HtI,
and HtL) for trim adjustment.
5) [Optional] Use the Constant Fan Menu (FSD) to select the
percentage of maximum airflow for continuous fan
6) [Optional] Use the Cooling Airflow Profile Menu (CAP) to select
between 4 cooling airflow profiles. Profile options 1-4 are listed above.
See installation manual for further details
Profiles
Pre-Run
Short-Run
OFF Delay
1
--------
--------
60 sec/100%
2
--------
30 sec/50% 60 sec/100%
3
--------
7.5 min/82% 60 sec/100%
4
30 sec/50% 7.5 min/82% 60 sec/100%
Selecting Heater Kit: Use the Electric Heating Wattage Menu (EHt) to select heater kit size. See "Menu Navigation and Selection
Instructions" above. Default selection is 0 (No Heat Kit). Select installed heater kit for heater kit operation.
NR - Not Rated
Electric Heat Airflow Table
Menu Navigation and Selection Instructions
Using Phone Application over Bluetooth Network:
1) Connect to the air handler (instructions provided by phone during
connection process).
2) Select desired settings menu
3) Select item that requires adjustment and make necessary selection
4) Submit Changes
Using On-Board Push Buttons:
1) Use the Right and Left Buttons to scroll between menus
2) Use the Center Button to select desired menu when menu code is
shown on 7-segment displays
3) Use the Left and Right Buttons to scroll through options within the
desired menu (the display will flash while scrolling through options for
selection)
4) Use the Center Button to select the displayed option (when selected
the display will stop flashing)
5) Use the Center Button to finalize selection and return to the main
menu
*If airflow is set above the model's maximum value, the output will be the
maximum value
Maximum Airflow Output
Tonnage
Selection
Airflow
1.0
400
1.1
440
1.2
480
1.3
520
1.4
560
1.5
600
1.6
640
1.7
680
1.8
720
1.9
760
2.0
800
2.1
840
2.2
880
2.3
920
2.4
960
2.5
1000
2.6
1040
2.7
1080
2.8
1120
2.9
1160
3.0
1200
3.1
1240
3.2
1280
3.3
1320
3.4
1360
3.5
1400
Tonnage Menu (t o n)
Tonnage
Selection
Airflow
3.5
1400
3.6
1440
3.7
1480
3.8
1520
3.9
1560
4.0
1600
4.1
1640
4.2
1680
4.3
1720
4.4
1760
4.5
1800
4.6
1840
4.7
1880
4.8
1920
4.9
1960
5.0
2000
5.1
2040
5.2
2080
5.3
2120
5.4
2160
5.5
2200
5.6
2240
5.7
2280
5.8
2320
5.9
2360
6.0
2400
MBVC1201AA-1
MBVC1601AA-1
MBVC2001AA-1
1400
2000
2000
Htr Kw
MBVC1201AA-1
MBVC1601AA-1
MBVC2001AA-1
3
600
800
800
5
600
800
800
6
635
800
800
8
740
1000
1000
10
1000
1000
1200
15
1400
1500
1500
19
NR
NR
NR
20
NR
NR
NR
21
NR
NR
NR
25
NR
NR
NR