background image

35

PACKAGE UNITS 

  - DUAL FUEL  & GAS

HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed

by a 

qualified service agency

 before the heating and cooling seasons begin.

R

EPLACE

 

OR

 C

LEAN

 F

ILTER

IMPORTANT NOTE: 

Never operate unit without a filter installed as

dust and lint will build up on internal parts resulting in loss of
efficiency, equipment damage and possible fire.
A return air filter is not supplied with this unit; however, there must
be a means of filtering the return air. An indoor air filter must be
used with your comfort system.  A properly maintained filter will
keep the indoor coil of your comfort system clean. A dirty coil could
cause poor operation and/or severe equipment damage.
The installer of your unit can tell you where your filter(s) are and
how to clean or replace them.
Check your return filter(s) at least once every two months. When
they are dirty, replace or clean as required. Disposable type
filters should be replaced. Reusable type filters may be cleaned.

NOTE:

  Reusable type filters should be washed with warm water,

dried completely and sprayed with an adhesive according to the
manufacturers recommendations.
You may want to ask your dealer about high efficiency filters. High
efficiency filters are available in both electronic and non-electronic
types. These filters can do a better job of catching small airborne
particles.
Improper filter maintenance is the most common cause of inad-
equate heating or cooling performance.  Filters should be cleaned
(permanent) or replaced (disposable) every two months or as re-
quired.  When replacing a filter, it must be replaced with a filter of
the same type and size and always make certain the air flow
arrows on the filter point in the proper direction.

C

ONDENSER

, E

VAPORATOR

 

AND

 I

NDUCED

 D

RAFT

 M

OTORS

The bearings on the air circulating blower motor, condenser motor
and the combustion fan motor are permanently lubricated and
require no further lubrication.

C

OMPRESSOR

The compressor motor is hermetically sealed and does not re-
quire additional oiling.

A

NNUAL

 I

NSPECTION

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

Your package unit should be inspected by a qualified installer,
or service agency at least twice every year. This check should
be performed before the heating and cooling seasons begin.
This will ensure that adequate combustion air is being drawn
and the vent system is working properly. Particular attention
should be paid to the following items. Repair as necessary.

Check physical support of the unit. Ensure it is sound
without any sagging, cracks, or gaps, around the base.

Check for obvious signs of deterioration of the unit.

•         Flue Hood and Combustion Air Inlet. Check for blockage

(wasp nest, etc.) and corrosion.

F

LUE

 H

OOD

 

(Q

UALIFIED

 S

ERVICER

 O

NLY

)

Return  Air Connection. Check for physical soundness
and ensure that the connection is firmly sealed to the
package unit casing.

Heat exchanger. Check for corrosion and/or obstructions
within the heat exchanger passageways.

Burners. Check for proper ignition, burner flame, and
flame sense.

Wiring. Check wires for damage. Check electrical
connections for tightness and/or corrosion.

Filters. Check that filters are clean and in the proper
placement in the unit or duct system.

Louvers. Inspect air inlet louvers inside the heat
exchanger compartments. Ensure the area is clean and
free of dirt and debris.

Clean Outside Coil (Qualified Servicer Only)

The outdoor coil should be inspected annually. It is important to
keep the outdoor coil clean. Dirt, leaves, or debris could restrict the
airflow. If cleaning of the outdoor coil becomes necessary, hire a
qualified servicer. Inexperienced people could easily puncture the
tubing in the coil.

                                         

           B

EFORE

 C

ALLING

 Y

OUR

 S

ERVICER

Check the thermostat to confirm that it is properly set.

Check  the disconnect switch near the unit to confirm that
it is closed.

Check the electrical panel  for tripped circuit breakers  or
failed  fuses . Reset the circuit breakers or replace fuses
as necessary.

Check  for blockage of the indoor air inlets and outlets.
Confirm that they are open and have not been blocked by
objects (rugs, curtains or furniture).

Check  for obstructions on the unit . Confirm that it has
not been covered on the sides or the top. Remove any
obstruction that can be safely  removed. If  the unit is
covered with dirt or debris, call a qualified servicer to
clean it.

Check the filter. If it is dirty, clean or replace it.

Содержание Maytag Amana A/GPG14 M Series

Страница 1: ...ational Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thorough...

Страница 2: ...Operation 12 HEATING 12 COOLING 12 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 GAS SUPPLY PRESSURE MEASUREMENT 14 GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT 15 COOLING START...

Страница 3: ...ODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARN...

Страница 4: ...ces from the enclosure for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit m...

Страница 5: ...oftopInstallation The unit may be installed directly on wood floors or on Class A Class B or Class C roof covering material To avoid possible personal injury a safe flat surface for service personnel...

Страница 6: ...aled damage carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond...

Страница 7: ...2 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressu...

Страница 8: ...PIPE OR TUBING LENGTH FEET Table 3 Propane Gas Pipe Sizing GAS PIPING CHECKS CAUTION TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GA...

Страница 9: ...NE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A CONFINED SPACE A WARNING DEVICE IS REQUIRED DUE TO PROPANE GAS IS HEAVIER THAN AIR AND...

Страница 10: ...transformer primary lead as shown on the unit wiring diagram HEAT ANTICIPATORSETTING The heat anticipator is to be set by measuring the load amperage at the R circuit Follow the instructions provided...

Страница 11: ...ossible unit operating sound transmission FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS NE...

Страница 12: ...fan are energized Two Stage Models If the thermostat call is for low stage cooling the compressor and outdoor fan are energized at low stage If the thermostat call is for high stage cooling the compr...

Страница 13: ...NJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE Rollout Prote...

Страница 14: ...re boss plug Install an 1 8 NPT hose barb fitting into the outlet pressure tap b White Rodgers 36G22 or 36G54 valve Back inlet pressure test screw inlet pressure boss out one turn counterclockwise not...

Страница 15: ...ase pressure or counterclockwise to decrease pressure Replace regulator cover screw Two Stage Models White Rodgers 36G54 valve Remove regulator cover screw from the low LO outlet pressure regulator ad...

Страница 16: ...his motor is energized by 24V Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor Single Stage Models Heating White Lead Cooling Yellow Lead T1 L...

Страница 17: ...place adjustment cap Wait a minimum of 10 minutes between adjustments to allow time for the TXV and pressures to stabilize NOTE The expansion valve will not need adjustment for most applications Ensur...

Страница 18: ...flashes Pressure Switch Stuck Closed A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control encounters a pressure switch stuck closed the induced draf...

Страница 19: ...filters should be discarded and replaced with a new clean filter Dirty permanent filters should be washed with water thoroughly dried and sprayed with a filter adhesive before being reinstalled Filte...

Страница 20: ...of burners in retention slots 6 Reconnect electrical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATI...

Страница 21: ...M WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS 0 1 680 61 45 840 103 37 1 035 174 30 1 035 174 1 225 276 0 2 640 72 48 795 109 39 995 184 31 995 184 1 185 275 0 3 605 80 51 750 117 41 960 192 32 960...

Страница 22: ...140 338 1 295 456 0 6 450 115 X 895 242 X 1 055 319 58 1 095 349 1 255 456 0 7 395 118 X 845 248 X 1 010 326 X 1 050 350 1 220 465 0 8 345 126 X 785 252 X 960 335 X 1 010 357 1 180 468 CFM WATTS RISE...

Страница 23: ...1 305 343 47 1 480 468 1 695 661 0 4 880 181 X 1 220 327 50 1 260 353 49 1 425 479 1 640 679 0 5 825 189 X 1 160 336 53 1 200 359 51 1 380 479 1 595 675 0 6 760 204 X 1 115 342 55 1 150 371 53 1 335 4...

Страница 24: ...296 1 655 638 1 825 857 0 5 905 199 64 1 295 351 59 1 135 308 1 610 656 1 790 865 0 6 840 215 X 1 235 359 62 1 085 318 1 560 659 1 735 867 0 7 770 218 X 1 180 371 X 1 040 328 1 520 664 1 700 877 0 8...

Страница 25: ...Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only IGNITION CONTROL DIAGNOSTIC INDICATOR CHART SINGLE STAGE MODELS ONLY 0 15 22 45 52 0 29 1...

Страница 26: ...tdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Signal Refer to Abnor...

Страница 27: ...27 APPENDIX UNIT DIMENSIONS EXHAUST FLUE HOOD CONTROL WIRE ENTRANCE POWER WIRE ENTRANCE HEAT EXCHANGE ACCESS PANEL B B A FLUE EXHAUST BLOWER ACCESS PANEL FLUE EXHAUST HOOD...

Страница 28: ...BR BR RD OR BL BL BL RD RD RD RD PU WH OR RD YL YL Y IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 150 120 ECON 135 P1 F1 FUSE 3 AMP MAX P3 G...

Страница 29: ...D YELLOW WIRE HEATING SPEED WHITE WIRE T4 LOW SPEED T1 LOW SPEED T5 HIGH SPEED T2 MED SPEED T3 HIGH SPEED 5 USE COOPER CONDUCTORS ONLY 6 L1 AND L2 ON IIC CONTROL IS 24V INPUT ALS AUXILLARY LIMIT SWITC...

Страница 30: ...BR RD OR BL BL BL BL RD RD RD RD PU WH OR RD YL YL Y Y2 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 1 5 0 1 2 0 ECON 1 3 5 P1 F1 FUSE 3 AM...

Страница 31: ...ANDTYPEOF INS ULATIONAS O RIGINAL USE COPPERCONDU CTORONLY 2 FOR208 VOLT TRA NSFORMEROPERATION MOVE BLACK WIRE FROMTER MINAL 3 TOTERM INAL 2 O NTRA NSFORMER 3 CRANKC ASE HEATERNOT SUPPLIEDON ALL U NIT...

Страница 32: ...CER L2 BK YL RD GR SEE NOTE 3 EM 208 PU YL PU BK N G L T5 T4 T3 T2 T1 240 3 TR 2 RD 24V C 1 YL BL 208 230 1 60 POWER SUPPLY GND C PU PU RD BK BR PU BK R S COMP C T2 T1 CC L2 L1 ALS CM LPS HPS PARK BK...

Страница 33: ...LS TR EM VM H F RCCF C L2 T2 208 230 1 60 CM L1 R T1 S COMP C L1 SUPPLY VOLTAGE P1 INTEGRATED IGNITION CONTROL CC CC COM HLI SEE NOTE 2 INTERGRATED IGNITION CONTROL F Y1 R C Y2 W2 W1 TO MICRO TO MICRO...

Страница 34: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Страница 35: ...ED SERVICER ONLY Your package unit should be inspected by a qualified installer or service agency at least twice every year This check should be performed before the heating and cooling seasons begin...

Страница 36: ...th refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed Verify that the crankcase heaters have been energized for 24 hours Verify the scroll compres...

Страница 37: ...Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heatin...

Страница 38: ...38 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 39: ...39 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 40: ...San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com 2014 2016 Goodman Manufacturing Company L P is a registered trademark of Maytag Corporation or its related companies and...

Отзывы: