background image

18

cycle is completed, and ignition is reattempted.  The control
will repeat this routine three times if a measurable combustion
is not established.  The control will then shut off the induced
draft blower and go into a lockout state.
If flame is established but lost, the control will energize the
circulator blower at the heat speed and then begin a new
ignition sequence.  If flame is established then lost on
subsequent attempts, the control will recycle for four (4)
consecutive ignition attempts (five attempts total) before
locking out.
The diagnostic fault code is 1 flash for a lockout due to failed
ignition attempts or flame dropouts.  The integrated control
will automatically reset after one hour, or it can be reset by
removing the thermostat signal or disconnecting the electrical
power supply for over five seconds. If the diagnostic LED
indicates an external lockout, perform the following checks:

Check the supply and manifold pressures

Check the gas orifices for debris

Check gas valve for proper operation

Check secondary limit

A dirty filter, excessive duct static, insufficient air flow, a
faulty limit, or a failed circulator blower can cause this
limit to open.  Check filters, total external duct static,
circulator blower motor, blower motor speed tap (see
wiring diagram), and limit.  An interruption in electrical
power during a heating cycle may also cause the
auxiliary limit to open.  The automatic reset secondary
limit is located on top of the circulator blower assembly.

Check rollout limit

If the burner flames are not properly drawn into the
heat exchanger, the flame rollout protection device will
open.  Possible causes are restricted or blocked flue
passages, blocked or cracked heat exchanger, a failed
induced draft blower, or insufficient combustion air. The
rollout protection device is a manual reset limit located
on the burner bracket.  The cause of the flame rollout
must be determined and corrected before resetting
the limit.

Check flame sensor

A drop in flame signal can be caused by nearly invisible
coating on the sensor.  Remove the sensor and carefully
clean with steel wool.

Check wiring

Check wiring for opens/shorts and miswiring.

Important:

  If you have to frequently reset your gas/electric

package unit, it means that a problem exists that should
be corrected. Contact a qualified servicer for further
information.

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty
pressure switch, faulty wiring, a disconnected or damaged
hose, a blocked or restricted flue, or a faulty induced draft
blower.
If the control senses an open pressure switch during the pre-
purge cycle, the induced draft blower only will be energized. If
the pressure switch opens after ignition has begun the gas
valve is de-energized, the circulator blower heat off cycle
begins, and the induced draft blower remains on. The
diagnostic fault code is two flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty
pressure switch or faulty wiring. If the control encounters a
pressure switch stuck closed, the induced draft blower
remains off. The diagnostic LED code for this fault is three (3)
flashes.

Open Thermal Protection Device

If the primary limit switch opens, the gas valve is immediately
de-energized, the induced draft and air circulating blowers
are energized. The induced draft  and air circulator blowers
remain energized until the limit switch recloses. The
diagnostic fault code for an open limit is four (4) flashes.
A primary limit will open due to excessive supply air
temperatures.  This can be caused by a dirty filter, excessive
duct static, insufficient air flow, or a faulty limit.  Check filters,
total external duct static, blower motor, blower motor speed
tap (see wiring diagram), and limit.  This limit will automatically
reset once the temperature falls below a preset level.

Primary Limit

A primary limit will open due to excessive supply air
temperatures. This can be caused by a dirty filter, excessive
duct static, insufficient air flow, or a faulty limit. Check filters,
total external duct static, blower motor, blower motor speed
tap (see wiring diagram), and limit. This limit will automatically
reset once the temperature falls below a preset level.

Auxiliary/Secondary Limit

A dirty filter, excessive duct static, insufficient air flow, a faulty
limit, or a failed circulator blower can cause this limit to open.
Check filters, total external duct static, circulator blower motor,
blower motor speed tap (see wiring diagram), and limit. An
interruption in electrical power during a heating cycle may
also cause the auxiliary limit to open. The automatic reset
secondary limit is located on top of the circulator blower
assembly.

Rollout Limit

If the burner flames are not properly drawn into the heat
exchanger, the flame rollout protection device will open.
Possible causes are restricted or blocked flue passages,
blocked or cracked heat exchanger, a failed induced draft
blower, or insufficient combustion air. The rollout protection
device is a manual reset limit located on the burner bracket.
The cause of the flame rollout must be determined and
corrected before resetting the limit.

Flame Detected with Gas Valve Closed

If flame is detected with the gas valve de-energized, the
combustion and air circulator blowers are energized. The
diagnostic fault code is five (5) flashes for this condition. The
control can be reset by removing the power supply to the unit
or it will automatically reset after one hour. Miswiring is the
probable cause for this fault.

Low Flame Signal (Two-Stage Models ONLY)

Under some conditions, the fuel or air supply can create a
nearly invisible coating on the flame sensor. This coating acts
as an insulator causing a drop in the flame signal. If the flame
signal drops below a predetermined value, the ignition control
will display an error code of (1) flash on the amber diagnostic
LED. The unit will continue to operate until the control can no
longer detect flame.

Содержание Maytag Amana A/GPG14 M Series

Страница 1: ...ational Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thorough...

Страница 2: ...Operation 12 HEATING 12 COOLING 12 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 GAS SUPPLY PRESSURE MEASUREMENT 14 GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT 15 COOLING START...

Страница 3: ...ODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARN...

Страница 4: ...ces from the enclosure for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit m...

Страница 5: ...oftopInstallation The unit may be installed directly on wood floors or on Class A Class B or Class C roof covering material To avoid possible personal injury a safe flat surface for service personnel...

Страница 6: ...aled damage carrier should be notified as soon as possible preferably within 5 days 4 File the claim with the following supporting documents a Original Bill of Lading certified copy or indemnity bond...

Страница 7: ...2 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressu...

Страница 8: ...PIPE OR TUBING LENGTH FEET Table 3 Propane Gas Pipe Sizing GAS PIPING CHECKS CAUTION TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GA...

Страница 9: ...NE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A CONFINED SPACE A WARNING DEVICE IS REQUIRED DUE TO PROPANE GAS IS HEAVIER THAN AIR AND...

Страница 10: ...transformer primary lead as shown on the unit wiring diagram HEAT ANTICIPATORSETTING The heat anticipator is to be set by measuring the load amperage at the R circuit Follow the instructions provided...

Страница 11: ...ossible unit operating sound transmission FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS NE...

Страница 12: ...fan are energized Two Stage Models If the thermostat call is for low stage cooling the compressor and outdoor fan are energized at low stage If the thermostat call is for high stage cooling the compr...

Страница 13: ...NJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE Rollout Prote...

Страница 14: ...re boss plug Install an 1 8 NPT hose barb fitting into the outlet pressure tap b White Rodgers 36G22 or 36G54 valve Back inlet pressure test screw inlet pressure boss out one turn counterclockwise not...

Страница 15: ...ase pressure or counterclockwise to decrease pressure Replace regulator cover screw Two Stage Models White Rodgers 36G54 valve Remove regulator cover screw from the low LO outlet pressure regulator ad...

Страница 16: ...his motor is energized by 24V Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor Single Stage Models Heating White Lead Cooling Yellow Lead T1 L...

Страница 17: ...place adjustment cap Wait a minimum of 10 minutes between adjustments to allow time for the TXV and pressures to stabilize NOTE The expansion valve will not need adjustment for most applications Ensur...

Страница 18: ...flashes Pressure Switch Stuck Closed A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control encounters a pressure switch stuck closed the induced draf...

Страница 19: ...filters should be discarded and replaced with a new clean filter Dirty permanent filters should be washed with water thoroughly dried and sprayed with a filter adhesive before being reinstalled Filte...

Страница 20: ...of burners in retention slots 6 Reconnect electrical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATI...

Страница 21: ...M WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS 0 1 680 61 45 840 103 37 1 035 174 30 1 035 174 1 225 276 0 2 640 72 48 795 109 39 995 184 31 995 184 1 185 275 0 3 605 80 51 750 117 41 960 192 32 960...

Страница 22: ...140 338 1 295 456 0 6 450 115 X 895 242 X 1 055 319 58 1 095 349 1 255 456 0 7 395 118 X 845 248 X 1 010 326 X 1 050 350 1 220 465 0 8 345 126 X 785 252 X 960 335 X 1 010 357 1 180 468 CFM WATTS RISE...

Страница 23: ...1 305 343 47 1 480 468 1 695 661 0 4 880 181 X 1 220 327 50 1 260 353 49 1 425 479 1 640 679 0 5 825 189 X 1 160 336 53 1 200 359 51 1 380 479 1 595 675 0 6 760 204 X 1 115 342 55 1 150 371 53 1 335 4...

Страница 24: ...296 1 655 638 1 825 857 0 5 905 199 64 1 295 351 59 1 135 308 1 610 656 1 790 865 0 6 840 215 X 1 235 359 62 1 085 318 1 560 659 1 735 867 0 7 770 218 X 1 180 371 X 1 040 328 1 520 664 1 700 877 0 8...

Страница 25: ...Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only IGNITION CONTROL DIAGNOSTIC INDICATOR CHART SINGLE STAGE MODELS ONLY 0 15 22 45 52 0 29 1...

Страница 26: ...tdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Signal Refer to Abnor...

Страница 27: ...27 APPENDIX UNIT DIMENSIONS EXHAUST FLUE HOOD CONTROL WIRE ENTRANCE POWER WIRE ENTRANCE HEAT EXCHANGE ACCESS PANEL B B A FLUE EXHAUST BLOWER ACCESS PANEL FLUE EXHAUST HOOD...

Страница 28: ...BR BR RD OR BL BL BL RD RD RD RD PU WH OR RD YL YL Y IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 150 120 ECON 135 P1 F1 FUSE 3 AMP MAX P3 G...

Страница 29: ...D YELLOW WIRE HEATING SPEED WHITE WIRE T4 LOW SPEED T1 LOW SPEED T5 HIGH SPEED T2 MED SPEED T3 HIGH SPEED 5 USE COOPER CONDUCTORS ONLY 6 L1 AND L2 ON IIC CONTROL IS 24V INPUT ALS AUXILLARY LIMIT SWITC...

Страница 30: ...BR RD OR BL BL BL BL RD RD RD RD PU WH OR RD YL YL Y Y2 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 1 5 0 1 2 0 ECON 1 3 5 P1 F1 FUSE 3 AM...

Страница 31: ...ANDTYPEOF INS ULATIONAS O RIGINAL USE COPPERCONDU CTORONLY 2 FOR208 VOLT TRA NSFORMEROPERATION MOVE BLACK WIRE FROMTER MINAL 3 TOTERM INAL 2 O NTRA NSFORMER 3 CRANKC ASE HEATERNOT SUPPLIEDON ALL U NIT...

Страница 32: ...CER L2 BK YL RD GR SEE NOTE 3 EM 208 PU YL PU BK N G L T5 T4 T3 T2 T1 240 3 TR 2 RD 24V C 1 YL BL 208 230 1 60 POWER SUPPLY GND C PU PU RD BK BR PU BK R S COMP C T2 T1 CC L2 L1 ALS CM LPS HPS PARK BK...

Страница 33: ...LS TR EM VM H F RCCF C L2 T2 208 230 1 60 CM L1 R T1 S COMP C L1 SUPPLY VOLTAGE P1 INTEGRATED IGNITION CONTROL CC CC COM HLI SEE NOTE 2 INTERGRATED IGNITION CONTROL F Y1 R C Y2 W2 W1 TO MICRO TO MICRO...

Страница 34: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Страница 35: ...ED SERVICER ONLY Your package unit should be inspected by a qualified installer or service agency at least twice every year This check should be performed before the heating and cooling seasons begin...

Страница 36: ...th refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed Verify that the crankcase heaters have been energized for 24 hours Verify the scroll compres...

Страница 37: ...Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heatin...

Страница 38: ...38 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 39: ...39 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 40: ...San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com 2014 2016 Goodman Manufacturing Company L P is a registered trademark of Maytag Corporation or its related companies and...

Отзывы: