background image

8

8. Turn the thermostat system switch to “OFF” and disconnect

all power when servicing the unit.

Heat Pump Start-Up Procedure

9. Check the cooling mode for the heat pump in the same

manner as above. The reversing valve is energized when
the thermostat is placed in the cooling position. A clicking
sound should be noticeable from the reversing valve.  By lowering the temperature setting to call for cooling, the
contractor is energized.  The compressor,
blower and fan should then be running.  After
the cooling mode is checked out, turn the
thermostat system switch to “OFF

”.

10. Turn the thermostat system switch to “HEAT”

and fan switch to “AUTO

”.

11. Slowly raise the heating temperature setting.

When the heating first stage makes contact,

stop raising the temperature setting.. The

compressor, blower and fan should now be

running with the reversing valve in the de-

energized (heating) position. After giving the

unit time to settle out, make sure the unit is

supplying heated air.

12. If the out door ambient is above 80°F, the

unit may trip on its high pressure cut out when

on heating. The compressor should stop.  The

heating cycle must be thoroughly checked,

so postpone the test to another day when

conditions are more suitable but-DO NOT FAIL

TO TEST.
If the out door ambient is low and the unit

operates properly on the heating cycle, you

may check the pressure cutout operation by

blocking off the indoor return air until the

unit trips.

13. If unit operates properly in the heating cycle,

raise the temperature setting until the heating

second stage makes contact. Supplemental

resistance heat, if installed should now come

on. Make sure it operates properly.

NOTE:  If outdoor thermostats are installed

the outdoor ambient must be below the set

point of these thermostats for the heaters

to operate. It may be necessary to jumper

these thermostats to check heater

operation if outdoor ambient is mild.

14.  For thermostats with emergency heat switch,

return to step 11. The emergency heat switch

is located at the bottom of the thermostat.

Move the switch to emergency heat. The heat

pump will stop, the blower will continue to

run, all heaters will come on and the

thermostat emergency heat light will come

on.

15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at

least one defrost cycle to make sure the unit defrosts completely.

Final System Checks

16. Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best

compromise between heating and cooling.

17. Check for air leaks in the ductwork.
18. See Sections on 

Air Flow Measurement and Adjustment

 and 

Checking Charge

.

WARNING

HIGH

 

VOLTAGE

!

D

ISCONNECT 

ALL

 POWER BEFORE SERVICING OR INSTALLING

THIS UNIT. 

M

ULTIPLE POWER SOURCES MAY BE PRESENT. FAILU

TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY O

DEATH.

RE

R

E

V

A

P

O

R

A

T

O

R

COOLING

SE RV IC E VA LV E

SE RVIC E PO RT

RE VE RSING  V ALVE

C

O

N

D

E

N

S

E

R

SE RV IC E PO RT

CO M PR ESS OR

SE RVIC E PO RT

AC CUM ULATO R

EX PA NSION  DEV IC E

CH ECK  VALVE  

OR IF ICE

SE RV IC E

VA LV E

CH ECK  VAL VE  

OR IF ICE

INDO OR

CO IL

DIST RIBU TOR

OU TDO OR

CO IL

E

V

A

P

O

R

A

T

O

R

HEATIN G

SE RVIC E VA LV E

SE RV IC E PO RT

RE VE RSING  VALVE

C

O

N

D

E

N

S

E

R

CO M PR ESS OR

SE RV IC E PO RT

AC CUM UL ATO R

CH ECK  VAL VE  

OR IF ICE

SE RV IC E

VA LV E

CH ECK  VALVE 

OR IFICE

INDO OR

CO IL

DISTRIBU TOR

OU TDO OR

CO IL

DIST RIBU TOR

HEAT PUMP REFRIGERANT CIRCUIt - FIGURE 7

Содержание GPC1524H41

Страница 1: ...signed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components However proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency Installation of this product should follow the manufacturer s refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energ...

Страница 2: ...nd outside of home Note any potential obstacles or prob lems that might be encountered as noted in this manual Choose a more suitable location if necessary IMPORTANT NOTE If a crankcase heater is used the unit should be energized 24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the com pressor Compressor damage may occur if this step is not followed Before u...

Страница 3: ...EPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER WARNING THIS UNIT MUST NOT BE USED AS A CONSTRUCTION HEATER DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES CODES AND REGULATIONS General The PC ...

Страница 4: ...s and regulations MAJOR COMPONENTS General The unit includes a hermetically sealed refrigerating system consisting of a compressor condenser coil evaporator coil with flowrator an indoor blower a condenser fan and all necessary internal electrical wiring The heat pump also includes a reversing valve solenoid defrost thermostat and control and loss of charge protection The system is factory evacuat...

Страница 5: ...ons as indicated Ducts should run as directly as possible to supply and return outlets Use of non flammable weatherproof flexible connectors on both supply and return connections at the unit to reduce noise transmission is recommended It is preferable to install the unit on the roof of the structure if the registers or diffusers are located in the wall or ceiling A slab installation is recommended...

Страница 6: ...e consulted to determine the availability of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch circuit fused disconnect near the unit in accordance with the N E C or local codes Wire sizes and overcurrent protection should be determined from the unit namepla...

Страница 7: ...the unit 2 Wire size based on 60 C rated wire insulation and 30 C Ambient Temperature 86 F 3 For more than 3 conductors in a raceway or cable see the N E C for derating the ampacity of each conductor OPERATION Start Up Procedure and Checklist Begin with power turned off at all disconnects 1 Turn thermostat system switch to Cool and fan switch to Auto and turn temperature setting as high as it will...

Страница 8: ...heat if installed should now come on Make sure it operates properly NOTE If outdoor thermostats are installed the outdoor ambient must be below the set point of these thermostats for the heaters to operate It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild 14 For thermostats with emergency heat switch return to step 11 The emergency heat switch is ...

Страница 9: ...age to the product which may not be covered by the manufacturer s warranty 8 Reversing Valve Coil This coil is activated by the thermostat in the cooling mode and during defrost It positions the reversing valve pilot valve for cooling operation 9 Indoor Blower Motor Units with EEM Motors The EEM model indoor blower motor is activated by the room thermostat by COOLING HEATING or FAN ON position The...

Страница 10: ... should close To verify this check for 24 volts between DFT and C on board If the temperature at the thermostat is less than 28 F and the thermostat is open replace the unit s defrost thermostat as it is defective 7 When the unit s defrost thermostat has closed short the test pins on the defrost board until the reversing valve shifts indicating defrost This should take up to 22 seconds depending o...

Страница 11: ...meter on liquid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Systems with TXV application should have a subcooling and superheat within the range listed on the chart a If subcooling and superheat are low adjust TXV then check subcooling b If subcooling is low and superheat is high add charge to raise subcoo...

Страница 12: ... Heat Pump should operate for many years without excessive service calls if the unit is installed properly However it is recommended that the homeowner inspect the unit before a seasonal start up The coils should be free of debris so adequate airflow is achieved The return and supply registers should be free of any obstructions The filters should be cleaned or replaced These few steps will help to...

Страница 13: ...e due to 1 Solenoid not energized In order to determine if the solenoid is energized touch the nut that holds the solenoid cover in place with a screwdriver If the nut magnetically holds the screwdriver the solenoid is energized and the unit is in the cooling cycle 2 No voltage at unit s solenoid Check unit voltage If no voltage check wiring circuit 3 Valve will not shift a Undercharged check for ...

Страница 14: ... 775 720 666 Watts 97 109 122 134 147 159 172 184 CFM 1123 1068 1014 959 905 850 796 741 Watts 123 136 148 161 173 186 198 211 CFM 1462 1409 1357 1305 1252 1200 1147 1095 Watts 241 253 266 278 291 303 315 328 CFM 1005 961 918 874 831 787 744 700 Watts 91 102 114 125 137 149 160 172 CFM 1110 1067 1023 980 936 893 849 806 Watts 120 132 144 155 167 178 190 202 CFM 1462 1409 1357 1305 1252 1200 1147 1...

Страница 15: ...39 150 161 175 186 190 207 CFM 1712 1655 1587 1541 1486 1444 1393 1340 Watts 337 348 358 375 385 405 414 416 CFM 2002 1935 1885 1827 1767 1732 1669 1618 Watts 498 521 516 534 551 567 571 574 CFM 1337 1297 1218 1155 1118 1088 1022 989 Watts 179 190 203 210 225 243 249 268 CFM 1694 1646 1598 1549 1501 1453 1405 1357 Watts 296 303 311 319 327 334 342 350 CFM 1919 1870 1822 1774 1726 1678 1629 1581 Wa...

Страница 16: ...essor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage must be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective replace Low suction cool compressor a a Iced evaporator coil a Defective o...

Страница 17: ... evaporator coil The safest way to clean the evaporator coil is to sim ply flush the coil with water This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils An alternate cleaning method is to use one of the products listed in the technical publication TP 109 shipped in the literature bag with the unit to clean the coils The...

Страница 18: ...rance around the unit for safety service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place Check gas piping for leaks Verify gas pressure to the unit is within the range specified on the serial plate Check to ensure that all fans pulleys and wheels are secure Check for proper belt tension...

Страница 19: ...it 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heating Supply Air Temperature PRESSURES Gas Inlet Pressure Gas Manifold Pressure Suction Circuit 1 Suction Circuit 2 Discharge Circuit 2 Superheat Orif...

Страница 20: ...feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights For Product Registration please regi...

Отзывы: