E
SPECIFICACIONES
DEL
P
RODUCTO
6 www.goodmanmfg.com
SS-GPC13H-SP
A
IRFLOW
D
ATA
(
CONT
.)
Modelo
Velocidad
Voltios
Presión estática externa (pulgadas de H2O)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
GPC13
42H21**
Bajo
230
CFM
1,425
1,410
1,355
1,310
1,245
1,170
1,080
-
Watts
450
445
430
420
405
390
370
-
Mediano
230
CFM
1,620
1,595
1,545
1,485
1,425
1,345
1,250
1,160
Watts
550
540
525
510
495
475
450
425
Alto
230
CFM
1,945
1,935
1,875
1,800
1,730
1,635
1,535
1,440
Watts
765
755
735
715
695
670
640
615
GPC13
42H41**
Bajo
230
CFM
1,425
1,410
1,355
1,310
1,245
1,170
1,080
-
Watts
450
445
430
420
405
390
370
-
Mediano
230
CFM
1,620
1,595
1,545
1,485
1,425
1,345
1,250
1,160
Watts
550
540
525
510
495
475
450
425
Alto
230
CFM
1,945
1,935
1,875
1,800
1,730
1,635
1,535
1,440
Watts
765
755
735
715
695
670
640
615
GPC13
48H21**
Bajo
230
CFM
1,425
1,410
1,355
1,310
1,245
1,170
1,080
-
Watts
450
445
430
420
405
390
370
-
Mediano
230
CFM
1,720
1,660
1,585
1,520
1,460
1,365
1,270
-
Watts
560
555
540
530
520
490
470
-
Alto
230
CFM
2,110
2,060
1,980
1,895
1,795
1,705
1,590
1,500
Watts
785
780
765
745
720
705
665
625
GPC13
48H41**
Bajo
230
CFM
1,425
1,410
1,355
1,310
1,245
1,170
1,080
-
Watts
450
445
430
420
405
390
370
-
Mediano
230
CFM
1,720
1,660
1,585
1,520
1,460
1,365
1,270
-
Watts
560
555
540
530
520
490
470
-
Alto
230
CFM
2,110
2,060
1,980
1,895
1,795
1,705
1,590
1,500
Watts
785
780
765
745
720
705
665
625
GPC13
60H21**
“T” 1
Bajo
230
CFM
1,860
1,800
1,745
1,695
1,650
1,600
1,555
1,500
Watts
410
425
440
455
470
480
495
500
“T” 2
Mediano
230
CFM
1,990
1,945
1,885
1,835
1,785
1,740
1,695
1,645
Watts
510
520
530
545
555
570
585
590
“T” 3
Alto
230
CFM
2,100
2,045
1,985
1,945
1,895
1,850
1,800
1,750
Watts
595
610
620
630
645
660
670
680
GPC13
60H41**
“T” 1
Bajo
230
CFM
1,775
1,635
1,645
1,515
1,510
1,450
1,430
1,400
Watts
395
420
435
445
455
465
470
475
“T” 2
Mediano
230
CFM
1,845
1,790
1,715
1,685
1,590
1,580
1,530
1,500
Watts
490
505
520
535
550
560
570
575
“T” 3
Alto
230
CFM
2,025
1,900
1,840
1,780
1,725
1,650
1,620
1,580
Watts
575
595
620
630
645
655
660
670
Notes
• Data shown is dry coil; wet coil pressure drop is approximate.
• 0.1”
H
2
O, for 2-row indoor coil; 0.2” H
2
O, for 3-row indoor coil; and 0.3” H
2
O, for 4-row indoor coil
• Data shown does not include
fi
lter pressure drop, approx. 0.08” H
2
O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON, USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM.
See Repair Parts list.
• Reduce
air
fl
ow by 2% for 208V operation.