![Goodman GPC 14 SEER R-410A Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/goodman/gpc-14-seer-r-410a/gpc-14-seer-r-410a_technical-manual_2243269009.webp)
PACKAGE COOLING SPECIFICATIONS
9
All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
WARNING
WARNING
GPC14[42-60]H41*
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.
GPC1442H41*
GPC1448H41*
GPC1460H41*
COOLING
COOLING CAPACITY, BTUH
40,500
46,500
57,500
CAPACITY
SEER / EER
14.5 / 12.0
14.5 / 12.1
14.2 / 12.0
UNIT
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
208-230/1/60
ELECTRICAL
AMPS (TOTAL)
22.2
24.2
30.7
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
26.6
29.1
37.3
MAXIMUM OVERCURRENT PROTECTION
(1)
40
45
60
COMPRESSOR
TYPE
SCROLL
SCROLL
SCROLL
RATED LOAD AMPS
17.9
19.9
26.4
LOCKED ROTOR AMPS
112
109
134
CONDENSER
HORSEPOWER
1/4
1/4
1/4
FAN MOTOR
RPM
1075
1075
1075
FULL LOAD AMPS
1.4
1.4
1.4
LOCKED ROTOR AMPS
2.9
2.9
2.9
CONDENSER FAN
BLADE DIAMETER (INCHES) / NUMBER OF BLADES
22 / 4
22 / 4
22 / 4
CONDENSER
FACE AREA - SQ. FT.
17.0
19.1
19.1
COIL
NUMBER OF ROWS
1
1
2
FINS PER INCH
24
21
16
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS
1/2 - 5
3/4 - 5
3/4 - 5
BLOWER
FULL LOAD AMPS
2.9
2.9
2.9
MOTOR
LOCKED ROTOR AMPS
NA
NA
NA
MOTOR SPEED TAP - COOLING
T2
T2
T2
RPM
1050
1050
1050
EVAPORATOR
DIAMETER X W IDTH (INCHES)
10 x 8
10 x 8
11 x 8
BLOWER
HI EFFICIENCY COOLING CFM
1,300
1,600
1,600
5 TON NO MINAL CO OLING CFM
NA
NA
1,800
FAN ONLY COOLING CFM
1,200
1,400
1,600
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
6.2
6.2
7.0
COIL
NUMBER OF ROWS
4
4
4
FINS PER INCH
14
14
14
GENERAL
FILTER SIZE - SQ. FT. *
(2) 20 x 20 x 1
(2) 20 x 20 x 1
(2) 20 x 25 x 1
INFO RM ATIO N
DRAIN SIZE (INCHES)
3/4"
3/4"
3/4"
EXPANSIO N DEVICE
ORIFICE (0.072)
ORIFICE (0.076)
ORIFICE (0.088)
REFRIGERANT CHARGE R-410A (Oz.)
118
123
188
POWER SUPPLY CONDUIT KNOCKOUT SIZE (INCHES)
3/4, 1, 1-1/4
3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (INCHES)
1/2
1/2
1/2
SHIPPING WEIGHT LBS.
370
400
400
OPERATING WEIGHT LBS.
360
390
390