Goodman GPC 14 SEER R-410A Скачать руководство пользователя страница 4

4

PRODUCT DESIGN

GPC Package Cooling Units are designed for outdoor instal-
lations only in either residential or light commercial applica-
tions.

The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow. In the vertical
application a matching Roof Curb is recommended.

A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion.  Under no circumstances should the unit be operated
without return air filters.

A 3/4” PVC pipe is provided for removal of condensate water
from the indoor coil In order to provide proper condensate
flow, a drain trap is supplied and shipped loose inside the
unit for field installation. (Do not reduce the drain line size.)

Refrigerant flow control is achieved by use of restrictor ori-
fices. GPC units use the FasTest Access Fitting System
with a saddle that is either soldered to the suction and liquid
lines or is fastened with a locking nut to the access fitting
box (core) and then screwed into the saddle. 

Do not re-

move the core from the saddle until the refrigerant
charge has been removed.  Failure to do so could re-
sult in property damage or personal injury.

The single phase units use permanent split capacitor (PSC)
design compressors.  Starting components are therefore not
required for these units.  A low microfarad run capacitor as-
sists the compressor to start and remains in the circuit dur-
ing operation.

All GPC14 units have X-13 indoor blower motors that are en-
ergized by a 24V signal from the thermostat and are con-
stant torque motors with very low power consumption. The X-
13 features an integral control module.

Air for condensing (cooling cycle) is drawn through the out-
door coil by a propeller fan, and is discharged vertically out
the top of the unit.  The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.

Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.

GPC1424-30H41* use Copeland Reciprocating Compressors.
GPC1436-60H41* use Copeland Scroll Compressors. There
are a number of design characteristics which are different
from the traditional reciprocating compressor.

-

Due to their design Scroll Compressors are inherently
more tolerant of liquid refrigerant. 

NOTE

: Even though the

compressor section of a Scroll compressor is more toler-
ant of liquid refrigerant, continued floodback or flooded
start conditions may wash oil from the bearing surfaces
causing premature bearing failure.

-

Scroll Compressors use white oil which is compatible
with 3GS oil which may be used if additional oil is re-
quired.

-

Operating pressures and amp draws may differ from stan-
dard reciprocating compressors. This information may be
found in the "Cooling Performance Data" section.

Location and Clearances

NOTE: 

To ensure proper condensate drainage, unit must be

installed in a level position.

36"

36"

10"

UNIT

WALL

36"

Outside Slab Installation - Horizontal (H)

Minimum clearances are required to avoid air recirculation and
keep the unit operating at peak efficiency.

Содержание GPC 14 SEER R-410A

Страница 1: ...ified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person Refer to Service Manual RS6300011 Horizontal for installation operation and troubleshooting information All safety information must be followed as provided in the Service Manual Refer t...

Страница 2: ...air this unit without such background may result in product damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a license to install or servic...

Страница 3: ...A office WARNING WARNING Do not connect or use any device that is not design certified by Goodman for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING WARNING To prevent the risk of property damage personal injury or death do not store combustible materials or use gasoline or...

Страница 4: ...e compressor to start and remains in the circuit dur ing operation All GPC14 units have X 13 indoor blower motors that are en ergized by a 24V signal from the thermostat and are con stant torque motors with very low power consumption The X 13 features an integral control module Air for condensing cooling cycle is drawn through the out door coil by a propeller fan and is discharged vertically out t...

Страница 5: ... codes or ordinances or in their absence with the latest edition of the Uniform Mechanical Code Section 305 NOTE Unit can also use roof curb WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS TO FACILITATE LIFTING AND MOVING IF A CRANE ISUSED PLACETHEUNITINANADEQUATECABLE SLING Refer to Roof Curb Installation Instructi...

Страница 6: ...10 C 45 52 60 60 9 50 32 400 HKR15 C 45 52 60 60 22 25 30 30 14 25 48 600 GPH1436H41A HKR05 C 24 27 30 30 4 75 16 200 HKR08 C 34 39 40 40 7 00 23 800 HKR10 C 45 52 60 60 9 50 32 400 HKR15 C 45 52 60 60 22 25 30 30 14 25 48 600 GPH1442H41A HKR05 C 25 27 30 30 4 75 16 200 HKR08 C 34 39 40 40 7 00 23 800 HKR10 C 46 52 60 60 9 50 32 400 HKR15 C 46 52 60 60 22 25 30 30 14 25 48 600 HKR20 C 46 52 60 60 ...

Страница 7: ...A Chassis Model A B GPC1424 33 30 GPC1430 33 30 GPC1436 33 35 GPC1442 33 35 GPC1448 33 38 GPC1460 33 38 Dimensions in inches Large Small Medium 34 075 66 542 4 512 14 000 14 000 SUPPLY 6 500 RETURN 4 500 BACK VIEW DUCT OPENINGS A 14 000 B ...

Страница 8: ...14 0 12 0 UNIT VOLTAGE NAMEPLATE 208 230 1 60 208 230 1 60 208 230 1 60 ELECTRICAL AMPS TOTAL 10 5 13 16 20 06 SPECIFICATION MINIMUM CIRCUIT AMPACITY 12 5 15 6 24 2 MAXIMUM OVERCURRENT PROTECTION 1 20 25 40 COMPRESSOR TYPE RECIP RECIP SCROLL RATED LOAD AMPS 7 9 9 8 16 7 LOCKED ROTOR AMPS 41 55 79 CONDENSER HORSEPOWER 1 6 1 4 1 4 FAN MOTOR RPM 815 830 830 FULL LOAD AMPS 1 1 1 5 1 5 LOCKED ROTOR AMP...

Страница 9: ...IT VOLTAGE NAMEPLATE 208 230 1 60 208 230 1 60 208 230 1 60 ELECTRICAL AMPS TOTAL 22 2 24 2 30 7 SPECIFICATION MINIMUM CIRCUIT AMPACITY 26 6 29 1 37 3 MAXIMUM OVERCURRENT PROTECTION 1 40 45 60 COMPRESSOR TYPE SCROLL SCROLL SCROLL RATED LOAD AMPS 17 9 19 9 26 4 LOCKED ROTOR AMPS 112 109 134 CONDENSER HORSEPOWER 1 4 1 4 1 4 FAN MOTOR RPM 1075 1075 1075 FULL LOAD AMPS 1 4 1 4 1 4 LOCKED ROTOR AMPS 2 ...

Страница 10: ...orizontal Applications SQRPCH101 Square to Round Adapters 16 14 SQRPCH102 103 Square to Round Adapters 18 14 SQRPC101 Square to Round Adapter For Use With PCCP101 103 Curb 16 Rounds SQRPC102 103 Square to Round Adapter For Use With PCCP101 103 Curb 18 Rounds PCFR101 103 External Horizontal Filter Rack PCEF101 103 Elbow Flashing w R 8 Liner CDK36 Flush Mount Concentric Duct Kit CDK36515 Flush Mount...

Страница 11: ...4 CFM 1537 1478 1431 1386 1336 1293 1253 1208 WATTS 244 258 274 288 303 317 329 341 CFM 1418 1383 1349 1312 1275 1228 1178 1141 WATTS 242 258 273 282 299 308 320 338 CFM 1175 1635 1645 1515 1510 1450 1430 1400 WATTS 395 420 435 445 455 465 470 475 CFM 1845 1790 1715 1685 1590 1580 1530 1500 WATTS 490 505 520 535 550 560 570 575 CFM 1775 1635 1645 1515 1510 1450 1430 1400 WATTS 395 420 435 445 455 ...

Страница 12: ...0 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 ...

Страница 13: ...6 7 28 6 23 4 24 1 26 0 28 0 22 8 23 5 25 4 27 3 21 7 22 3 24 1 25 9 20 1 20 7 22 4 24 0 S T 0 84 0 76 0 57 0 37 0 88 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 40 0 96 0 86 0 65 0 42 0 97 0 87 0 66 0 42 Delta T 20 18 15 10 20 19 15 11 20 19 15 11 20 19 15 11 20 18 15 10 19 17 14 10 955 KW 1 58 1 62 1 67 1 73 1 71 1 75 1 81 1 87 1 82 1 87 1 93 2 00 1 92 1 97 2 04 2 11 2 01 2 06 2 13 2 20 ...

Страница 14: ...2 304 292 314 332 346 332 358 378 394 374 403 425 443 413 445 470 490 LO PR 109 116 127 135 115 123 134 143 120 127 139 148 126 134 146 156 132 140 153 163 136 145 158 169 NOTE Shaded area reflects AHRI rating conditions MBh 25 4 25 9 27 1 28 9 24 8 25 3 26 5 28 2 24 2 24 7 25 8 27 6 23 6 24 1 25 2 26 9 22 4 22 9 24 0 25 6 20 8 21 2 22 2 23 7 S T 0 97 0 94 0 85 0 69 1 00 0 97 0 88 0 71 1 00 1 00 0...

Страница 15: ... 33 1 27 0 27 8 30 1 32 3 26 3 27 1 29 3 31 5 25 0 25 8 27 9 29 9 23 2 23 9 25 8 27 7 S T 0 86 0 77 0 58 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 67 0 43 0 99 0 89 0 67 0 43 Delta T 19 18 14 10 19 18 15 10 19 18 15 10 19 18 15 10 19 18 14 10 18 16 14 9 1180 KW 1 88 1 92 1 98 2 05 2 03 2 07 2 14 2 22 2 16 2 21 2 29 2 36 2 28 2 33 2 41 2 49 2 38 2 43 2 52 2 61 2 4...

Страница 16: ... 312 300 322 340 355 341 367 388 404 384 413 436 455 424 456 482 503 LO PR 109 116 127 135 115 123 134 143 120 128 139 148 126 134 146 156 132 140 153 163 136 145 159 169 NOTE Shaded area reflects AHRI rating conditions MBh 29 3 29 9 31 3 33 4 28 6 29 2 30 6 32 6 27 9 28 5 29 8 31 8 27 3 27 8 29 1 31 1 25 9 26 4 27 7 29 5 24 0 24 5 25 6 27 3 S T 0 99 0 96 0 87 0 70 1 00 0 99 0 90 0 73 1 00 1 00 0 ...

Страница 17: ... 33 8 34 8 37 7 40 5 33 0 34 0 36 8 39 5 31 4 32 3 34 9 37 5 29 0 29 9 32 4 34 7 S T 0 87 0 77 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 99 0 88 0 67 0 43 0 99 0 89 0 67 0 43 Delta T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 21 19 16 11 20 18 15 10 1349 KW 2 35 2 40 2 47 2 56 2 53 2 59 2 67 2 76 2 69 2 75 2 84 2 94 2 84 2 90 3 00 3 10 2 96 3 03 3 13 3 24 3 06 3 ...

Страница 18: ...8 310 298 320 338 353 339 365 385 402 382 411 434 452 422 454 479 500 LO PR 105 112 122 130 111 118 129 138 116 123 134 143 121 129 141 150 127 135 148 157 132 140 153 163 NOTE Shaded area reflects AHRI rating conditions MBh 36 7 37 4 39 2 41 8 35 9 36 6 38 3 40 9 35 0 35 7 37 4 39 9 34 2 34 8 36 5 38 9 32 5 33 1 34 7 37 0 30 1 30 7 32 1 34 3 S T 1 00 0 96 0 87 0 70 1 00 1 00 0 90 0 73 1 00 1 00 0...

Страница 19: ... 38 5 39 6 42 9 46 0 37 5 38 7 41 8 44 9 35 7 36 7 39 7 42 7 33 0 34 0 36 8 39 5 S T 0 85 0 76 0 58 0 37 0 88 0 79 0 60 0 39 0 91 0 81 0 61 0 40 0 94 0 84 0 63 0 41 0 97 0 87 0 66 0 42 0 98 0 88 0 66 0 43 Delta T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11 1461 KW 2 56 2 62 2 70 2 79 2 77 2 83 2 92 3 02 2 94 3 01 3 11 3 21 3 10 3 17 3 28 3 39 3 23 3 31 3 42 3 54 3 35 3 ...

Страница 20: ...5 308 295 318 335 350 336 362 382 398 378 407 430 448 418 450 475 495 LO PR 107 114 125 133 113 121 132 140 118 125 137 146 124 132 144 153 130 138 151 160 134 143 156 166 NOTE Shaded area reflects AHRI rating conditions MBh 41 8 42 6 44 6 47 6 40 8 41 6 43 6 46 5 39 9 40 6 42 5 45 4 38 9 39 6 41 5 44 3 36 9 37 6 39 4 42 1 34 2 34 9 36 5 39 0 S T 0 98 0 95 0 85 0 69 1 00 0 98 0 89 0 72 1 00 1 00 0...

Страница 21: ...1 44 2 45 5 49 2 52 8 43 1 44 4 48 0 51 6 41 0 42 2 45 6 49 0 37 9 39 1 42 3 45 4 S T 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 99 0 88 0 67 0 43 1 00 0 89 0 67 0 43 Delta T 21 19 15 11 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 19 18 15 10 1800 KW 2 97 3 03 3 13 3 23 3 20 3 27 3 37 3 48 3 40 3 47 3 59 3 71 3 58 3 66 3 78 3 90 3 73 3 81 3 94 4 07 3 86 3...

Страница 22: ...94 307 295 317 335 349 336 361 381 398 378 406 429 447 417 449 474 494 LO PR 108 115 126 134 114 122 133 141 119 126 138 147 125 133 145 154 131 139 152 162 135 144 157 167 NOTE Shaded area reflects AHRI rating conditions MBh 48 0 48 9 51 2 54 7 46 9 47 8 50 0 53 4 45 8 46 6 48 8 52 1 44 6 45 5 47 7 50 8 42 4 43 2 45 3 48 3 39 3 40 0 41 9 44 7 S T 1 00 0 96 0 87 0 70 1 00 1 00 0 90 0 73 1 00 1 00 ...

Страница 23: ... 54 6 56 3 60 9 65 3 53 3 54 9 59 4 63 8 50 6 52 1 56 4 60 6 46 9 48 3 52 3 56 1 S T 0 81 0 73 0 55 0 35 0 84 0 75 0 57 0 37 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 83 0 63 0 40 0 93 0 83 0 63 0 41 Delta T 24 22 18 12 24 22 18 13 24 22 18 13 24 22 18 13 24 22 18 12 22 21 17 12 1800 KW 3 73 3 82 3 94 4 07 4 03 4 12 4 26 4 41 4 30 4 40 4 55 4 70 4 53 4 64 4 79 4 96 4 73 4 84 5 01 5 18 4 90 5 ...

Страница 24: ...8 310 298 321 339 353 339 365 386 402 382 411 434 452 422 454 479 500 LO PR 106 112 123 131 112 119 130 138 116 123 135 143 122 130 141 151 128 136 148 158 132 140 153 163 NOTE Shaded area reflects AHRI rating conditions MBh 59 3 60 5 63 3 67 6 58 0 59 1 61 9 66 0 56 6 57 7 60 4 64 4 55 2 56 3 58 9 62 9 52 4 53 5 56 0 59 7 48 6 49 5 51 9 55 3 S T 0 93 0 90 0 81 0 66 0 97 0 93 0 84 0 68 0 99 0 96 0...

Страница 25: ...rature drop Delta T Low and high side pressures and power will not change 2 As indoor CFM decreases a slight increase will occur in indoor temperature drop Delta T A slight decrease will occur in low and high side pressures and power A properly operating unit should be within plus or minus 3 degrees of the typical Delta T value shown A properly operating unit should be within plus or minus 7 PSIG ...

Страница 26: ... PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION COMPONENT LEGEND C CM COMP EM GND LVJB PLF RCCF SA TR HPS CONTACTOR CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR EQUIPMENT GROUND LOW VOLTAGE JUNCTION BOX FEMALE PLUG CONNECTOR RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWITCH WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLO...

Отзывы: