7
The heater and it’s individual shut-off must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 50 mbar.
The heater must be isolated from the gas supply piping system by closing it’s individual man-
ual shut-off valve during any pressure testing of the gas supply piping system at pressures
equal to or less than 50mBAR.
If this heater is installed in conjunction with an air conditioning coil, the coil must be down-
stream of the heat exchanger.
A gas-fired heater for installation in a residential garage must be installed in a definite purpose
sealed enclosure with all air for combustion and ventilation originating outdoors.
When installed in a commercial garage the ignition source must be above the level where pet-
rol vapors or any other flammable vapors may accumulate. The circulating ductwork must be
above the level where recirculation of vapors may occur. The heater must be protected from
damage, especially from vehicles.
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE HEATER
CASING. THE AREA AROUND THE HEATER MUST BE KEPT FREE OF ALL
COMBUSTIBLE MATERIAL INCLUDING PETROL AND OTHER FLAMMABLE VAPORS AND
LIQUIDS. THE HEATER ROOM MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY
OTHER STORAGE PURPOSE.
WARNING
THIS HEATER IS EQUIPPED WITH A SOLID BASE PLATE. IT MUST BE LEFT IN PLACE
WHEN USING SIDE RETURN DUCTS. FAILURE TO LEAVE THIS BASE PLATE INSTALLED
COULD CAUSE PRODUCTS OF COMBUSTION, INCLUDING
CARBON MONOXIDE
, TO BE
CIRCULATED INTO THE LIVING SPACE. THIS CAN CREATE A POTENTIALLY
HAZARDOUS CONDITION, INCLUDING
CARBON MONOXIDE
POISONING. REFER TO
THE SECTION ON “CIRCULATING AIR SUPPLY” FOR RETURN DUCT INSTRUCTIONS.
VENTING
WARNING
THE VENT MUST TERMINATE OUTDOORS.
ANNUAL inspections of the heater and its vent system is strongly recommended. There should
be no separation, corrosion, or perforation. It is also the contractor’s responsibility to inform the
user of this importance of the results of this inspection.
PROPER INSTALLATION OF THE VENTING SYSTEM IS CRITICAL TO SAFE OPERATION
OF THIS APPLIANCE. CAREFULLY READ AND UNDERSTAND THE INSTRUCTIONS IN
THIS SECTION.
CAUTION
Due to the possibility of CO poisoning -
This appliance
SHALL NOT
be connected to a vent servicing a solid fuel fireplace.
This appliance
SHALL NOT
be connected to a flue serving a factory built fireplace.
This appliance
SHALL NOT
be connected to an unlined masonry chimney.