background image

IO-213D

     2/04

5

Attaching Combustion Air Intake Fitting.

 A coupling for

attaching the combustion air fitting to the furnace cabinet
is included in a plastic bag packaged with the furnace.  The
fitting is sized to accept a 3" diameter PVC pipe.  In certain
situation, a 2" diameter pipe can be used for this application.
Refer to the combustion/ vent table for sizing requirements.
Attach the fitting to the cabinet using (4) #10 x 1/2" sheet
metal screws (field supplied).  If a right hand entrance is
preferred, the plug installed on this side is to be removed
and reinstalled in the left side opening.

Non-Direct Vent Combustion Air.

  If the furnace is to be

installed as a non-direct vent appliance, the combustion air
pipe outlined previously is not used.

As a non-direct vent furnace, this must be installed in
accordance with the combustion and ventilation air
requirements found in ANSI Z221.3, section 5.3.  When
installed as a non-direct vent furnace in an area, which is
deemed as a confined area, see (ANSI Z223.1, section 1.7,
“Space, Confined”) the requirements are as follows:

All Combustion Air Taken From The Inside Of

 

The

Building.

  When installed as a non-direct vent furnace and

indoor air is used as the combustion air source, the space
is to be provided with (2) permanent openings communicating
directly with an additional room(s) of sufficient volume so
that the combined volume of all spaces meets the criteria of
an unconfined area.  The total input of all gas burning
equipment shall be used to determine the minimum size of
each opening.  Each opening shall be sized to be a minimum
of 1 square inch of free area per 1,000 Btu/hr of combined
input of gas utilization equipment in the area.  The minimum
area for each opening shall not be less than 100 square
inches, and the minimum dimension of these openings shall
not be less than 3 inches. One opening shall commence
within 12 inches of the top of the area, while the other opening
shall commence within 12 inches of the bottom of the area.

All Combustion Air Taken From Outdoors.

  If installed

as a non-direct furnace and outdoor air is selected as the
combustion air source, then area shall be serviced with an
opening(s) communicating directly with the outdoors by either
of the following two methods.  When calculating the minimum
area for each opening, the combined input of all gas utilization
equipment is to be considered.  Also, the minimum
dimension for any opening shall not be less than 3 inches.

Method 1

..... Two permanent openings communicating

directly with the outdoors via. horizontal ducts shall be
sized to be a minimum of 1 square inch per 4,000 Btu/hr
or, two permanent openings communicating directly with
the outdoors via. vertical ducts shall be sized to be a
minimum of 1 square inch per 2,000 Btu /hr.

Method 2

..... One permanent opening communicating

directly with the outdoors via a horizontal duct.  This
opening/duct shall be sized to be equal to 1 square inch
per 3,000 Btu / hr, but not less than the sum of the areas
all of the vent connectors in the confined space.

When installed as a direct vent furnace and NOT using the
concentric vent kit CVK-00 option, the combustion air is to
be terminated in the following manner;

OPTIONAL
INLET

SCREEN

COMBUSTION 

AIR INTAKE

If the optional concentric vent kit (CVK-00) is used, follow
the instructions provided with this accessory.

SOURCE OF COMBUSTION AIR

The recommended source of combustion air is to use the
outdoor air supply. However, the use of indoor air in most
applications is acceptable except as follows;
1. If the furnace is installed in a confined space, the

necessary combustion must come from outdoors by
way of the attic, crawl space, or direct opening to the
outside.

2. If indoor combustion is used, there must be no exposure

to the substances listed in #3 below.

3. The following installations may require OUTDOOR AIR

for combustion, due to chemical exposures;

• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces installed in hobby or craft rooms
• Furnaces installed near chemical storage areas

Exposures to the following substances in the combustion
air supply may also require OUTDOOR AIR for combustion;

• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials

VENTING

ANNUAL inspections of the furnace and it’s vent / combustion
air supply is strongly recommended. It is the contractor’s
responsibility to inform the user of this importance.  All venting
shall be in accordance with Part 7; Venting of Equipment,
of the National Fuel Gas Code, ANSI Z223.1, or applicable
local building and/ or air conditioning codes.

PROPER INSTALLATION OF THE VENT / COMBUSTION AIR
SYSTEMS IS CRITICAL TO SAFE OPERATION OF THIS
APPLIANCE. CAREFULLY READ AND UNDERSTAND THE
INSTRUCTIONS IN THIS SECTION. EACH VENT AND
COMBUSTION AIR SUPPLY PIPE MUST SERVE ONLY ONE

Содержание GMNT

Страница 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Страница 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Страница 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Страница 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Страница 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Страница 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Страница 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Страница 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Страница 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Страница 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Страница 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Страница 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Страница 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Страница 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Страница 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Страница 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Страница 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Страница 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Страница 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Страница 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Отзывы: