background image

IO-213D

2/04

16

This control is located in the circulating air blower
compartment. Upon a demand for heat, the venter is
energized. After a short purge, the electronic ignition device
is energized. The burners are ignited after a short delay and
the burner flame is proven. The circulating air blower is
energized at approximately 30 seconds after the burners
are ignited. The circulating air blower off time is field
selectable at  90, 120 or 150 seconds. THIS CONTROL IS
NOT FIELD SERVICEABLE.

CIRCULATING AIR FILTERS

One of the most common causes of problems in a forced
air heating system is blocked or dirty filters. Circulating air
filters must be inspected monthly for dirt accumulation and
replaced if necessary. Failure to maintain clean filters can
cause premature heat exchanger failure. A new home may
require more frequent replacement until all construction dust
and dirt is removed. Circulating air filters must be installed
external to the furnace cabinet.

CAUTION

BEFORE PERFORMING ANY SERVICE ON THIS FURNACE,
DISCONNECT THE MAIN POWER SUPPLY.

CAUTION

DO NOT

 OPERATE THE FURNACE WITHOUT THE

CIRCULATING AIR FILTERS IN PLACE.  DUST AND DIRT IN
THE AIR WILL RESTRICT THE AIR MOVEMENT OVER THE
SECONDARY COIL CAUSING NUISANCE CYCLING OF
SAFETY CONTROLS, WHICH MAY RESULT IN A “NO HEAT
CONDITION.”

TEMPERATURE RISE

The temperature difference between the outlet air and the
inlet air of the furnace is known as the temperature rise.
This furnace is designed to operate within the temperature
rise displayed on the furnace series and rating plate. To
ensure satisfactory performance, the temperature rise of
the furnace must be measured and adjusted if necessary.
Use the following procedure to measure and adjust the
temperature rise;

• Prior to starting the furnace, visually inspect all joints and

seams in the supply and return air ducts for leaks. Repair
them if necessary.

• Adjust the room thermostat to obtain constant operation.
• Allow the furnace to operate for at least fifteen (15) minutes.
• With an accurate thermometer, measure the temperature

at the return air grille. If a combination indoor / outdoor
system is used, the temperature must be measured
downstream of the connection.

• Measure the outlet air temperature at a point approximately

twelve to eighteen (12 -18) inches from the supply air duct
opening of the furnace. It may be necessary to measure
the outlet air at several places to obtain an accurate
average. NOTE: IF AN AIR CONDITIONING COIL IS
INSTALLED, TAKE CARE SO AS NOT TO DAMAGE THAT
COIL.

• Adjust the temperature rise by changing circulating air

blower speed tap.

MOTOR LUBRICATION AND MAINTENANCE

The circulating air blower is equipped with bearings that are
permanently lubricated by the motor manufacturer and
require no additional lubrication. At the time of the monthly
filter inspection, clean the exterior of the circulating air motor,

especially around the perimeter air holes to prevent the
possibility of overheating due to an accumulation of dust or
dirt on the windings and motor casing. As suggested
elsewhere in these instructions, the air filters are to be kept
clean. Dirty filters will restrict the airflow over the motor
windings and possibly cause an overheating condition. The
venter motor has bearings that are prelubricated by the motor
manufacturer and require no attention.

SERVICE INSTRUCTIONS

DO 

keep the circulating air filters clean. The heating system

will operate more efficiently and economically.

DO

 arrange drapes and furniture so that the supply air

registers and return air grilles are unobstructed.

DO

 close doors and windows. This will reduce the heat

load on the system.

DO 

avoid excessive use of bathroom and kitchen exhaust

fans.

DO NOT

 let heat generated by televisions, lamps, direct

sunlight, etc. influence the thermostat operation.

DO NOT

 use the furnace room as a storage area.

DO NOT

 store gasoline or other flammable liquids or vapors

in the vicinity of the furnace.

EXCLUSIVE

 of the mounting platform, keep all

combustible materials at least 3 feet from the Furnace.

SEQUENCE OF OPERATION

This appliance is controlled by the thermostat. Within this
section, the term lockout is referenced. This lockout is a
“soft” lockout, which will reset after one hour. It is the
obligation of the installer to educate the user on the proper
use of the thermostat and the sequence of operation in both
the heating and cooling modes. It is also important that any
repair or service be performed by a QUALIFIED service
person, not by the user.

Heating Mode

• The furnace control checks for an open main limit (this

limit is normally closed). If the limit is open, the furnace
will remain inoperable until the limit is closed. During an
open limit, the circulating air blower will be energized. The
status light will blink four (4) times.

• The room thermostat reacts to a demand for heat.
• The control will then check to insure that the vent pressure

switch is open. If, at this point, the vent pressure switch is
closed, the control will blink two (2) times and will remain
inoperable until this situation is corrected.

• The venter blower is energized.
• The vent pressure switch will close when it detects a

pressure in excess of its setting. If the pressure switch
fails to close, the status light will flash three (3) times. The
sequence cannot continue until the pressure switch closes.

• After a pre-purge of about fifteen (15) seconds, the

electronic ignition device will be energized.

• The flame rollout switches are then checked to assure

they are in the closed position.

• After a slight delay, the gas valve will open if the flame

rollout switches are closed.

• The burners will ignite and the flame sensor will detect the

presence of flame. The ignition device will deenergize. If
the sensor does not detect the burner flame, the gas valve
will close and the ignition cycle will be repeated for a total
of three attempts. If, after the third attempt, the presence of
flame is not detected, the furnace will go into a lockout
condition for one (1) hour. It will then repeat the ignition
cycle. This one (1) hour lockout and retry will occur
indefinitely.

Содержание GMNT

Страница 1: ...SYSTEMAND ANY GAS CONTROL THAT HAS BEEN UNDER WATER WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY C US INSTALLATION OPERATING INSTRUCTIONS for GMNT C...

Страница 2: ...ary coil Collector Box ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners...

Страница 3: ...INTAINED AND MONITORED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ALL WATER BEARING PIPES SHOULD BE DRAINED THE BUILDING SHOULD BE PROPERLY WINTERIZED AN...

Страница 4: ...BUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS...

Страница 5: ...Two permanent openings communicating directly with the outdoors via horizontal ducts shall be sized to be a minimum of 1 square inch per 4 000 Btu hr or two permanent openings communicating directly...

Страница 6: ...k for blockage of the condensate disposal system Hoses may be disconnected to determine that proper flow is maintained Should an obstruction be observed it can be dislodged by forcing a stream of wate...

Страница 7: ...air may be obtained from the bottom of the unit providing there is at least 4 of unobstructed space It is recommended that the plug is removed and the combustion air supply is obtained from both open...

Страница 8: ...AL REQUIREMENT THE COMBUSTION PRODUCTS IN THE FLUE GASES WILL CONDENSE THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING SURFACES SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED When sele...

Страница 9: ...IO 213D 2 04 9 DRAIN CONNECTIONS HORIZONTAL RIGHT SIDE HORIZONTAL LEFT SIDE AIR FLOW AIR FLOW...

Страница 10: ...IO 213D 2 04 10 DRAINCONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Страница 11: ...ip e o f d iffe re n t d ia m e te rs a n d le n g th in ft 3 h r w ith a p re s s u re d ro p o f 0 3 W C a n d a s p e c ific g ra v ity o f 0 6 0 n a tu ra l g a s After the length of pipe has bee...

Страница 12: ...he furnace for electrical connection The junction box may be moved to either side The entry holes for supply and low voltage control wires are for use with electrical connectors All electrical wiring...

Страница 13: ...ES RATING PLATE INPUT 1000 Example Corrected input for a 100 000 Btu hr appliance installed at an altitude of 6 000 ft utilizing natural gas with a heating value of 1 000 But ft3 is determined by Corr...

Страница 14: ...d 3 Attach a 5 16 inch hose and manometer to the outlet pressure boss of the valve see fig 1 Hose should overlap boss 3 8 inch 4 Turn on system power and set thermostat to call for heat 5 Using a leak...

Страница 15: ...function contact a qualified service person to determine the cause of function before resetting To reset this switch press the button on top of the switch after the furnace has cooled To test the oper...

Страница 16: ...overheating due to an accumulation of dust or dirt on the windings and motor casing As suggested elsewhere in these instructions the air filters are to be kept clean Dirty filters will restrict the a...

Страница 17: ...replace dampers d Follow lighting instructions Place the appliance being inspected in operation Adjust the thermostat so the appliance shall operate continuously e Test for draft hood equipped applian...

Страница 18: ...any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control switch or knob Neve...

Страница 19: ...GAS VALVE HSI HOT SURFACE IGNITOR IDBR2 IDBR1 INDOOR BLOWER HEAT RELAY PV POWER VENTOR FS FLAME SENSOR PS LS DS IDB GV FS HSI SO W COOL HEAT M1 M2 HSI IND NEUTRALS PRI TRANS W G R L2 W W R LIMIT PSI P...

Страница 20: ...t causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know...

Отзывы: