Goodman GME80603B Series Скачать руководство пользователя страница 5

P

roDuct

 s

PeciFications

P

roDuct

 s

PeciFications

SS-GME8

  

www.goodmanmfg.com 

5

a

irFlow

 D

ata

(CFM & Temperature Rise vs. External Static Pressure)

Model

Motor 

Speed

Tons 

AC¹ 

External Static Pressure, (Inches Water Column)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

CFM

CFM

GME8

0603B*B

T1

875

 ---

793

 ---

736

 ---

674

 ---

592

 ---

556

509

460

T2

2

1,032

43

965

46

914

49

861

 ---

810

 ---

756

712

659

T3

1,217

37

1,153

39

1,098

40

1,051

42

1,009

44

964

918

877

T4

3

1,365

33

1,313

34

1,268

35

1,221

36

1,172

38

1,129 1,086 1,054

T5

1,549

29

1,505

30

1,460

30

1,420

31

1,378

32

1,350 1,305 1,268

GME8

0805C*B

T1

1,268

47

1,198

49

1,151

51

1,092

54

1,041

57

988

932

883

T2

3

1,362

44

1,305

45

1,261

47

1,212

49

1,170

51

1,121 1,074 1,021

T3

1,576

38

1,519

39

1,473

40

1,426

42

1,398

42

1,341 1,290 1,252

T4

4

1,755

 ---

1,711

35

1,657

36

1,627

36

1,579

38

1,548 1,502 1,463

T5

5

2,183

 ---

2,128

 ---

2,094

 ---

2,060

 ---

2,014

 ---

1,992 1,944 1,847

GME8

1005C*B

T1

3

1,466

51

1,415

52

1,357

55

1,306

57

1,248

59

1,202 1,144 1,088

T2

1,642

45

1,596

46

1,552

48

1,499

49

1,449

51

1,388 1,352 1,306

T3

4

1,750

42

1,750

42

1,707

43

1,667

44

1,610

46

1,574 1,531 1,486

T4

4

1,870

40

1,805

41

1,782

42

1,737

43

1,701

44

1,656 1,606 1,571

T5

5

2,297

 ---

2,297

 ---

2,224

 ---

2,106

35

2,014

37

1,896 1,813 1,669

¹   @ 0.5” ESP

Notes

•  CFM in chart is without filter(s).  Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this 

chart assumes both filters are installed.

•  All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling and heating speed as needed.
•  For most jobs, about 375 - 400 CFM per ton when cooling is desirable.
•  INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
•  This chart is for information only.  For satisfactory operation, external static pressure should not exceed value shown on the rating plate.
•  The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise 

at a particular CFM, while ESP at the CFM will be lower.

•  Factory Motor Speed Setting: T1 = 1st Stage Ht, T2 = 2nd Stage Ht, T5 = Cooling
•  Temperature rise data is based on second-stage heat.  First-stage heat is 75% of rise indicated above.

Содержание GME80603B Series

Страница 1: ...tempera ture without an outdoor temperature sensor Certain models available with low NOx emissions Cabinet Features Fully insulated heavy gauge steel cabinet with durable baked enamel finish Foil face...

Страница 2: ...tal NOx D Dedicated Down ow N Natural Gas H High Air ow X Low NOx K Dedicated Up ow M Up ow Horizontal Cabinet Width A 14 Descrip2on B 17 V Two Stage Variable speed C 21 H Two Stage Mul speed D 24 S S...

Страница 3: ...upon Isolated Combustion System ICS Vent diameter may vary depending upon vent length Refer to the latest editions of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and the Canada National...

Страница 4: ...ibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater Refer to the appropriate USA and Canadian codes In the USA the National Fuel Gas Co...

Страница 5: ...1 352 1 306 T3 4 1 750 42 1 750 42 1 707 43 1 667 44 1 610 46 1 574 1 531 1 486 T4 4 1 870 40 1 805 41 1 782 42 1 737 43 1 701 44 1 656 1 606 1 571 T5 5 2 297 2 297 2 224 2 106 35 2 014 37 1 896 1 813...

Страница 6: ...60 70 80 90 110 120 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2...

Страница 7: ...ect to change Always refer to the wiring diagram or the unit for the most up to date wiring W arning High Voltage Disconnect all power before servicing or installing this unit Multiple power sources m...

Страница 8: ...er This furnace is capable of the following heating modes Single Stage Factory Setting Modified Two Stage Fixed 5 Min Low Stage Auto Time 1 12 Min Low Stage Start Call for Heat Safety Circuit Check St...

Отзывы: