7

APPLY INSULATION TAPE

Figure 8 

15.  Aluminum Indoor Coil Cleaning

      (Qualified Servicer Only)

This unit is equipped with an aluminum tube evaporator coil. 

The safest way to clean the evaporator coil is to simply flush 

the coil with water. This cleaning practice remains as the 

recommended cleaning method for both copper tube and 

aluminum tube residential evaporator coils.
It has been determined that many coil cleaners and drain 

pan tablets contain corrosive chemicals that can be harmful 

to aluminum tube and fin evaporator coils. Even a one-time 

application of these corrosive chemicals can cause premature 

aluminum evaporator coil failure. Any cleaners that contain 

corrosive chemicals including, but not limited to, chlorine and 

hydroxides, should not be used.
An alternate cleaning method is to use one of the products 

listed in TP-109* to clean the coils. The cleaners listed are 

the only agents deemed safe and approved for use to clean 

round tube aluminum coils. TP-109 is also available on the 

web site in Partner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical 
cleaners.

16.    Start-Up Procedure

WARNING

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING OR 

INSTALLING THIS UNIT.  MULTIPLE POWER SOURCES MAY 

BE PRESENT.  FAILURE TO DO SO MAY CAUSE PROPERTY 

DAMAGE, PERSONAL INJURY OR DEATH.

•.  Prior to start-up, ensure that all electrical wires are  

properly sized and all connections are properly tightened.  

•.  All panels must be in place and secured.  For Air Tight 

application, gasket must be positioned at prescribed 

locations to achieve 1.4% leakage.

•.  Tubing must be leak free.
•.  Condensate line must be trapped and pitched to allow 

for drainage.

•.  Low voltage wiring is properly connected.
•.  Auxilliary drain is installed when necessary and pitched 

to allow for drainage.

•.  Unit is protected from vehicular or other physical  

damage.

•.  Return air is not obtained from, nor are there any  

return air duct joints that are unsealed in, areas where 

there may be objectionable odors, flammable vapors or 

products of combustion such as carbon monoxide (CO), 
which may cause serious personal injury or death..

Содержание DOWNFLOW

Страница 1: ...PFLOW DOWNFLOW COILS INSTALLATION INSTRUCTIONS 2 1 Handling Use caution when transporting carrying unit Do not carry unit with hooks or sharp object The preferred method of carrying the unit after arr...

Страница 2: ...the preferred wrapping material 1 Ensure drain pan hole is NOT obstructed 2 To prevent potential sweating and dripping on finished space it may be necessary to insulate the condensate drain line loca...

Страница 3: ...Y RECOMMENDED TO PREVENT SCORCHING OR MARRING OF THE EQUIPMENT FINISH WHEN BRAZING CLOSE TO THE PAINTED SURFACES USE BRAZING ALLOY OF 5 MINIMUM SILVER CONTENT NOTE Refrigerant tubing must be routed to...

Страница 4: ...line set into liquid tube expansion and slide grommet about 18 away from braze joint 6 Insert suction line set into suction tube expansion and slide insulation and grommet about 18 away from braze joi...

Страница 5: ...onnect manifold set installation is complete NOTE ChecktheSchraderportsforleaksandtightenvalve cores if necessary Install caps finger tight SUBCOOL FORMULA SAT LIQUID LINE TEMP LIQUID LINE TEMP SUPERH...

Страница 6: ...ling Along The Panel Gap IMPORTANT NOTE To prevent cabinet sweating and airflow leak apply field provided insulation tape along all joining surfaces between the coil gas furnace duct work and panels S...

Страница 7: ...uminum coils TP 109 is also available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners 16 Start Up Procedure WARNING HIGH VOLTAGE DI...

Страница 8: ...F Heating Supply Air Temperature DB F Temperature Rise DB F Delta T Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV and EEV wiring...

Страница 9: ...9 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 10: ...10 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 12: ...oduct brand you purchased to be directed to the feedback page DAIKIN AMANA BRAND GOODMAN BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Отзывы: